background image

84

Wiring

7.2.7  Synchronized Input from INX-10A Two Stage Wiring - Class B Multiple 

Slaves 

Figure 47    Synchronized Input from INX-10A Wiring - Class B Multiple Slaves 

Attention: SYCNHRONIZING SIGNALS FROM THE INX-10A CAN USE CLASS B

WIRING ONLY

MIRCOM RECOMMENDED SETUP FOR MULTIPLE SLAVES

SYNCH SIGNAL FROM INX-10A CLASS B ONLY

1

8

1

8

1

8

1

8

1

8

POWER ON

CPU FAIL

BATTERY/
CHARGER
TROUBLE

JW1

P

P3

P4

P1

P2

AUX OUTPUT TROUBLE

SYNCH. OUT TROUBLE

GFAULT

JW2

MAIN DISPLAY PANEL

ACK. 
BUTTON

1

8

1

8

1

8

1

8

1

8

POWER ON

CPU FAIL

BATTERY/
CHARGER
TROUBLE

JW1

P

P3

P4

P1

P2

AUX OUTPUT TROUBLE

SYNCH. OUT TROUBLE

GFAULT

JW2

MAIN DISPLAY PANEL

ACK. 
BUTTON

MASTER

SLAVE 1

-

+ + -

SYNCH INPUT1

-

+

+

-

SYNCH OUTPUTS

1

2

1

8

1

8

1

8

1

8

1

8

POWER ON

CPU FAIL

BATTERY/
CHARGER
TROUBLE

JW1

P

P3

P4

P1

P2

AUX OUTPUT TROUBLE

SYNCH. OUT TROUBLE

GFAULT

JW2

MAIN DISPLAY PANEL

ACK. 
BUTTON

SLAVE 2

MP-300 3.9K EOL

-

+ + -

SYNCH INPUT2

MP-300 3.9K EOL

-

+ + -

SYNCH INPUT1

-

+

+

-

SYNCH OUTPUTS

1

2

MP-300 3.9K EOL

-

+ + -

SYNCH INPUT2

MP-300 3.9K EOL

ADD. LINE
ACTIVITY/
ALARM

COMMON
TROUBLE

ADD. LINE
ACTIVITY/
ALARM

COMMON
TROUBLE

ADD. LINE
ACTIVITY/
ALARM

COMMON
TROUBLE

!

Содержание INX-10A Series

Страница 1: ...INX 10A Series Intelligent NAC Expander Panel LT 899 Rev 6 1 September 2014 Installation and Operation Manual ...

Страница 2: ......

Страница 3: ... 17 3 1 Enclosure Dimensions 17 3 2 INX 10ADS Mechanical Installation 17 3 2 1 Installation Tips 18 3 3 INX 10AC Mounting Instructions 19 3 4 Enclosure Dimensions 20 3 5 Installing the INX 10A Enclosure 20 3 5 1 Installation Tips 22 3 6 Chassis Board Connections 23 4 0 Indication Controls 24 4 1 Indication and Controls 25 4 1 1 Common Indicators 26 4 1 2 Trouble LEDs 26 4 1 3 Other LEDs 27 4 1 4 F...

Страница 4: ... 6 3 2 Software Configuration Single Stage with Basic Reporting Addressing 45 6 3 3 Single Stage with Enhanced Trouble Reporting Addressing 47 6 3 4 Software Configuration Single Stage with Enhanced Trouble Reporting Addressing 48 6 3 5 Single Stage with Basic Reporting and Power Supply Output Addressing 50 6 3 6 Software Configuration Single Stage with Basic Reporting and Power Supply Output Addr...

Страница 5: ...tiple Slaves 83 7 2 7 Synchronized Input from INX 10A Two Stage Wiring Class B Multiple Slaves 84 7 2 8 Relay Contact Activation from FACP Single Stage 85 7 2 9 Relay Contact Activation from FACP Two Stage 86 7 2 10 Relay Ground Supervision and Auxiliary Supply Wiring 87 7 2 11 Supervision of Auxiliary Supply Wiring 87 7 2 12 NAC CIrcuit Wiring Class B 88 7 2 13 NAC CIrcuit Wiring Class A 88 7 3 P...

Страница 6: ...6 Table of Contents 11 3 Minimal ULC Two Stage Addressable System 100 12 0 Appendix D FX 2000 and FleX Net Series ULI Compatible Devices 101 12 1 Horns and Bells 101 12 2 Synchronized Strobes 101 ...

Страница 7: ...e with Basic Reporting and Power Supply Output 51 Figure 22 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Single Stage with Basic Reporting and Power Supply Output 52 Figure 23 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Single Stage with Basic Reporting and Power Supply Output 52 Figure 24 FX 2000 Configurator Settings INX 10A Single Stage with Enhanced Reporting and Power Su...

Страница 8: ...C Loop Wiring Class A 80 Figure 43 Synchronized Input from FACP Wiring Class B 81 Figure 44 Synchronized Input from FACP Wiring Class A 81 Figure 45 Synchronized Input from INX 10A Wiring Class B Single Slave 82 Figure 46 Synchronized Input from INX 10A Wiring Class B Multiple Slaves 83 Figure 47 Synchronized Input from INX 10A Wiring Class B Multiple Slaves 84 Figure 48 Relay Contact Activation f...

Страница 9: ...put 51 Table 13 Assigning Addresses Single Stage Application 1 Power Supply Output 54 Table 14 Configuring Two Stage Functions 57 Table 15 Configuring Two Stage Address Assignment with Enhanced Trouble Reporting 61 Table 16 Assigning Addresses Two Stage Application 1 Power Supply Output 65 Table 17 Configuring Two Stage Address Assignment with Enhanced Trouble Reporting and Power Supply Addressing...

Страница 10: ...10 List of Tables ...

Страница 11: ...successful installation operation and configuration of the INX 10A the INX 10ADS and the INX 10AC Unless specifically mentioned INX 10A can hereafter be used to refer to any of the INX 10A the INX 10ADS or the INX 10AC This chapter explains Feature Overview Contact Information ...

Страница 12: ...1 1 2 Features Supports 2 synchronized panels on one node to meet sync timing requirements Supports up to 14 panels per node using minimal configuration 7 SLC points per booster Supports up to 6 panels per node using maximum configuration 15 points for extended trouble reporting and two stage operation Outputs used as power supply outputs do not require panel configuration or SLC addresses Utilize...

Страница 13: ...p to and including 40 Ah storage capacity Enclosure fits 4 Ah 7 Ah and 12 Ah batteries 18 Ah batteries will fit in the INX 10ADS only The INX 10A series can charge 40 Ah batteries but they must be placed in an external battery cabinet BC 160 2 5 Amp max current per output 1 7 Amp auxiliary power output Unit includes power supply and charger red enclosure cam lock transformer and battery leads Comp...

Страница 14: ...a Only Local 905 660 4655 Email mail mircomgroup com 1 2 2 Customer Service Toll Free 1 888 MIRCOM5 North America Only Local 905 695 3535 Toll Free Fax 1 888 660 4113 North America Only Local Fax 905 660 4113 Email salessupport mircomgroup com 1 2 3 Technical Support Toll Free 1 888 MIRCOM5 North America Only 888 647 2665 International 905 647 2665 Email techsupport mircomgroup com 1 2 4 Website w...

Страница 15: ...15 INX 10A Overview 2 0 INX 10A Overview This chapter lists the components of the INX 10A This chapter explains INX 10A Components ...

Страница 16: ...ander 10 Amps INX 10ADS Intelligent NAC Expander 10 Amps Mounts into the BBX 1024DS INX 10AC Intelligent NAC Expander 10 Amps Addressable Chassis Mounts into the BB 5008 or BB 5014 enclosure BA 104 BA 1065 BA 110 BA 117 12 VOLT Batteries 4 Ah to 12 Ah 18 Ah batteries fit in the INX 10ADS only Maximum 40 Ah batteries with an external enclosure W 5 94 H 3 94 D 3 86 BA 110 10AH ...

Страница 17: ...e Dimensions 3 2 INX 10ADS Mechanical Installation The INX 10ADS comes with an BBX 1024DS or BBX 1024DSR enclosure which are suitable for flush or surface mounting and have a built in trim ring Dimensions of Enclosure minus built in trim ring 14 5 x 4 2 x 26 Distance between horizontal mounting screws 12 Distance between vertical mounting screws 23 5 Complete Dimensions of Enclosures 16 3 x 5 5 x ...

Страница 18: ... and neatness Be sure to connect a solid Earth Ground from building system ground to a cold water pipe to the Chassis Earth Ground Mounting Lug and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the Backbox Attention DO NOT install cable through bottom of the box This space is reserved for Batteries 1 3 1 7 2 0 Top View 2 1 1 3 6 0 9 5 Side View 14 50 26 00 4 20...

Страница 19: ...gure 2 Figure 2 INX 10AC Mounting Instructions All twelve black circles represent mounting studs Use 6 HEX nuts provided to secure to backbox BB 5008 or BB 5014 All twelve black circles represent mounting studs Use 6 HEX nuts provided to secure chassis to backbox BB 5008 or BB 5014 INX 10A Board Battery Battery Transformer ...

Страница 20: ...hown in Figure 5 on page 21 Figure 3 INX 10A Dimensions Outer Dimensions 14 23 x 4 42 x 19 85 Distance between upper mounting screws 11 Distance between lower mounting screws 11 Distance between upper and lower mounting screws 14 1 FA 300TR Dimensions 17 x 22 5 19 85 14 23 4 42 1 00 1 20 3 45 Top View 1 00 1 42 Side View 11 00 14 10 External Dimensions Mounting Dimensions ...

Страница 21: ...lace the screws halfway into the wall in the position shown using a suitable screw 3 Hang the box onto the two screws 4 Screw the other two screws at the bottom of the panel 5 Tighten all four screws into place Figure 4 FA 300TR Dimensions Figure 5 Flush mounting the enclosure 17 22 5 Adhere to surface around the INX 10A backbox Trim Ring Dimensions TRIM RING WALL WOOD OR METAL STUD BACKBOX ...

Страница 22: ...top of the enclosure Use a wire tie to group wires for easy identification and neatness Be sure to connect a solid Earth Ground from building system ground to a cold water pipe to the Chassis Earth Ground Mounting Lug and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on the Backbox Note Figure 3 shows a cross section of the semi flush mounted backbox and the trim ...

Страница 23: ...ers on page 23 Figure 6 INX 10A Chassis Board Connectors and Jumpers Table 3 INX 10A Chassis Board Connectors and Jumpers Connector Jumper Description P1 2 Connection for 29VAC AC In P3 4 Connection to Battery Red to P3 Black to P4 JW1 Auxiliary Power Supervision Factory set ON Leave in place for supervision Remove for non supervision JW2 Factory set closed leave in place 1 8 1 8 1 8 1 8 1 8 POWER...

Страница 24: ...cation Controls 4 0 Indication Controls This chapter describes the LED indicators and controls of the INX 10A This chapter explains Main Chassis Board LED Indicators Flash Rates Acknowledge button DIP switches ...

Страница 25: ...sed for configuration For additional information see 6 0 Configuration on page 34 Figure 7 displays the LED indicators and the control button on the INX 10A main board Figure 7 Main Board highlighting Common Indicators Trouble LED s Other LED s 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE ACKNOWLEDGE BUTTON JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBL...

Страница 26: ... main board can provide more information on what the trouble is See 4 1 2 Trouble LEDs below for a description Battery Charger Trouble The Battery Charger Trouble LED Indicator activates steady amber when the Battery is either low below 20 4 VDC or the Battery or Charger are disconnected It flashes amber for a restored trouble For configuration information see 6 2 2 Setting Protocols Reporting Cha...

Страница 27: ...LED that is steady red when an alarm is activated NAC Circuit Indicators Each NAC Circuit has one red LED that flashes when activated and one amber that activates solid when a trouble occurs To clear the trouble and reset the panel press the acknowledge button Synchronized Output Indicators Two LEDs One LED on each output that flashes green for outgoing activity 4 1 4 Flash Rate Trouble Flash 20 f...

Страница 28: ...28 Operation 5 0 Operation This chapter describes operational capabilities of the INX 10A This chapter explains Circuit Types Synchronization Modes Power Supply Modes Evacuation Codes ...

Страница 29: ...n order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Program feature or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 Second Stage Enabled YES Second Stage Enabled Disabled...

Страница 30: ...When one of the Sync Inputs is activated the INX 10A outputs follow the signal pattern of the Sync Input The INX 10A must be configured as a slave to operate in this mode All synchronization signals are supplied from the FACP or Master INX 10A To enable this mode for Bell Signals set DIP SW3 Bit 8 to one and set Alert DIP SW4 Bits 1 3 Evacuation DIP SW4 Bits 4 6 and Strobe DIP SW5 Bits 1 3 rates t...

Страница 31: ...ny NAC output can be configured as a power supply SLC and Sync Inputs are ignored for the power supply outputs For configuration information see Chapter 6 2 4 Setting Alert Rates Evacuation Rates NAC 5 Output Functions on page 42 and Chapter 6 2 5 Setting Strobe Types NAC 1 3 Supply Settings NAC 4 Output Function on page 43 5 3 2 NAC Outputs for Door Release Only NAC 4 and or 5 can configured for ...

Страница 32: ... Code 5 seconds on 10 seconds off 5 4 2 Two stage codes Alert Code 0 5 second on 2 5 seconds off General Alarm Evacuation code as selected from above 5 5 Horn Strobe Rates Horn Strobe rates are fixed at the following rates 5 5 1 Single Stage Temporal Code 3 of 0 5 second on 0 5 second off 1 5 second pause then repeat 5 5 2 Two stage codes Alert Code 0 5 second on 2 5 seconds off Temporal Code 3 of...

Страница 33: ...33 Operation Figure 11 Evacuation Codes ...

Страница 34: ...ocated on the main board This chapter explains Using DIP Switches Single Stage and Two Stage Addressing Adding Functions in the FX 2000 configurator Assigning Protocols Trouble Reporting AC Fail Delay Charger and Battery Settings Synchronization Settings Configuring NACs Alert and Evacuation Rates Strobe Types ...

Страница 35: ... has 8 switches numbered 1 to 8 Flipping a switch up places it in the ON position For the purposes of the configuration tables ON 1 and OFF 0 For an illustration of the DIP switch settings see Figure 12 Figure 12 DIP switch positions 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE P DIP SW1 DIP SW5 DIP SW4 DIP SW3 DIP SW2 ACK BUTTON 1 2 4 8 0 1 ...

Страница 36: ...e all switches to 0 Figure 13 DIP switch address example Table 4 Setting INX 10A Base Address Disabling Addressable Loop Interface DIP switch 1 Bits Default Setting 0 Activated Setting 1 Notes Additional Diagrams All 1 8 Addressable Loop Disabled Sets the INX 10A base address For an addressing example see Figure 13 ALL SWITCHES OFF ALL SWITCHES OFF 1 8 2 3 4 5 6 7 ALL SWITCHES ON ALL SWITCHES ON 1...

Страница 37: ...0000 39 1110 0100 64 0000 0010 89 1001 1010 15 1111 0000 40 0001 0100 65 1000 0010 90 0101 1010 Single Stage Application with Enhanced Reporting 16 0000 1000 41 1001 0100 66 0100 0010 91 1101 1010 17 1000 1000 42 0101 0100 67 1100 0010 92 0011 1010 18 0100 1000 43 1101 0100 68 0010 0010 93 1011 1010 Single Stage Application with Basic Reporting 19 1100 1000 44 0011 0100 69 1010 0010 94 0111 1010 2...

Страница 38: ...ault the entire address space is assigned to AP devices and there is no address space reserved for CLIP modules That is Allowable CLIP Addresses is set to None for both Sensors and Modules To reserve address space for CLIP devices you must add the number of CLIP devices to the AP Start value 3 Enter 100 in the AP Start column for the loop that your INX 10A is connected to and then press the Tab ke...

Страница 39: ...dules and the number of CLIP devices you can add are reduced For example if you enter 50 in the AP Start column the CLIP module address space for the loop changes to 201 249 and you can only configure 49 CLIP modules for that loop Note For all the FX 3500 3500RCU and MR 2350 examples in this chapter the maximum CLIP device address space is assumed That is the AP Start is set to 100 and the CLIP mo...

Страница 40: ...nd See Board LED s for further trouble shooting Free loop addresses base 2 to base 4 Base address is set by SW1 4 Second Stage Enabled Free loop addresses base 8 to base 12 or if Enhanced Reporting is enabled frees addresses base 11 to base 15 Base address is set by SW1 5 6 Configure Report Delay for AC fail The digits below refer to the corresponding bit number i e 01 means that bit 5 0 and bit 6...

Страница 41: ...t Mode NAC 1 to 3 Signals Configured NAC s Sync Strobes For a comprehensive description of Independent Mode options see 6 5 Independent Mode Configuration Options on page 74 Independent mode is active if SW4 Bit 4 6 Evacuation Rates is set to 010 110 001 101 or 011 AND SW5 Bit 1 3 Setting Strobe Manufacturer Type set to 100 110 001 or 101 8 Synchronous Signal Master Synchronous Signal Slave Attent...

Страница 42: ...ed or a trouble will sound 4 6 100 Uses Strobe Manufacturer Sync Rate NOT AFFECTED BY SIGNAL SILENCE 4 6 010 Continuous 4 6 110 Temporal 4 6 001 March Time 4 6 101 California 4 6 011 120 PPM 50 Duty Cycle 7 8 NAC 5 Output Settings 7 8 00 Normal NAC 7 8 10 Continuous Supply 7 8 01 Cut on Alarm 7 8 11 4 seconds Cut on Reset ALL SWITCHES OFF ALL SWITCHES OFF 1 8 2 3 4 5 6 7 ALL SWITCHES ON ALL SWITCH...

Страница 43: ...d 1 3 110 System Sensor 1 3 001 Secutron Gentex 1 3 101 Wheelock 1 3 011 System Sensor 2 Alternate Setting 4 NAC 1 NAC NAC 1 Continuous Supply 5 NAC 2 NAC NAC 2 Continuous Supply 6 NAC 3 NAC NAC 3 Continuous Supply 7 8 NAC 4 Output Settings 7 8 00 NAC 7 8 10 Continuous Supply 7 8 01 Cut on Alarm 7 8 11 4 seconds Cut on Reset ALL SWITCHES OFF ALL SWITCHES OFF 1 8 2 3 4 5 6 7 ALL SWITCHES ON ALL SWI...

Страница 44: ...To configure the recommended base address To configure the INX for Single Stage with Basic Reporting in a Mircom system To configure the INX for Single Stage with Basic Reporting in a Secutron system Attention Ensure that the configuration is set correctly on the INX 10A DIP switches and the Fire Panel Configuration Software Set DIP switch SW1 as 1 0 1 1 1 0 1 0 ON OFF ON ON ON OFF ON OFF Set DIP ...

Страница 45: ...ss 4 97 Activate NAC4 return NAC4 line status Base Address 5 98 Activate NAC5 return NAC5 line status Base Address 6 99 Notes Table 10 represents all NACs configured as NAC circuits Mircom recommends always using the upper range of addresses available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900 configurations add 100 to the recommended device address see Figures 15 and 16 ...

Страница 46: ...guration Figure 16 Secutron MR 2100 2200 2900 Configuration Settings INX 10A Single Stage with Basic Reporting Figure 17 FX 3500 3500RCU MR 2350 Configuration Settings INX 10A Single Stage with Basic Reporting ...

Страница 47: ... 6 For more information see Setting Alert Rates Evacuation Rates NAC 5 Output Functions on page 42 Table 11 Configuring Single Stage with Enhanced Reporting Functions Function Address Recommended Device Address Common Trouble Base Address 90 Signal Silence Base Address 1 91 Monitor AC trouble Base Address 2 92 Monitor Battery Charger trouble Base Address 3 93 Monitor Earth Ground Fault Base Addres...

Страница 48: ...ng the upper range of addresses available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900 configurations add 100 to the recommended device address see Figures 18 and 19 When adding devices to FX 3500 3500RCU and MR 2350 configurations add 200 to the recommended device address see Figure 20 If any NAC circuit is configured as a Power Supply see 6 3 7 Single Stage with Enhanced ...

Страница 49: ...ration Figure 19 Secutron MR 2100 2200 2900 Configuration Settings INX 10A Single Stage with Enhanced Reporting Figure 20 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Single Stage with Enhanced Reporting ...

Страница 50: ...ngle Stage with Basic Reporting in a Mircom System To configure the INX for Single Stage with Basic Reporting in a Secutron System To configure NAC 5 as a Continuous Power Supply Set DIP switch SW1 as 0 1 1 1 1 0 1 0 OFF ON ON ON ON OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 0 1 1 OFF OFF ON ON Set DIP switch SW2 1 to SW2 4 as 0 1 0 1 OFF ON OFF ON Set DIP switch SW4 7 and SW4 8 as 1 0 ON OFF A...

Страница 51: ...s Base Address 2 96 Activate NAC2 return NAC2 line status Base Address 3 97 Activate NAC3 return NAC3 line status Base Address 4 98 Activate NAC4 return NAC4 line status Base Address 5 99 Notes Mircom recommends always using the upper range of addresses available for the INX 10A Mircom recommends always using the upper range of NACs NAC5 then NAC4 then NAC3 etc when configuring as a Power Supply W...

Страница 52: ...tron MR 2100 2200 2900 Configurator Settings INX 10A Single Stage with Basic Reporting and Power Supply Output Figure 23 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Single Stage with Basic Reporting and Power Supply Output ...

Страница 53: ...tage with Enhanced Reporting in a Mircom System To configure the INX for Single Stage with Enhanced Trouble Reporting in a Secutron System To configure NAC 5 as a Continuous Power Supply Set DIP switch SW1 as 1 1 0 1 1 0 1 0 ON ON OFF ON ON OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 0 0 1 OFF OFF OFF ON Set DIP switch SW2 1 to SW2 4 as 0 1 0 1 OFF ON OFF ON Set DIP switch SW4 7 and SW4 8 as 1 0...

Страница 54: ...AC2 line status Base Address 6 97 Activate NAC3 return NAC3 line status Base Address 7 98 Activate NAC4 return NAC4 line status Base Address 8 99 Notes Mircom recommends always using the upper range of addresses available for the INX 10A Mircom recommends always using the upper range of NACs NAC5 then NAC4 then NAC3 etc when configuring as a Power Supply When adding devices to FX 2000 and MR 2100 ...

Страница 55: ...nhanced Reporting and Power Supply Output Addressing Figure 24 FX 2000 Configurator Settings INX 10A Single Stage with Enhanced Reporting and Power Supply Output Figure 25 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Single Stage with Power Supply Output ...

Страница 56: ...56 Configuration Figure 26 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Single Stage with Enhanced Reporting and Power Supply Output ...

Страница 57: ...ctly on the INX 10A DIP switches and the Fire Panel Configuration Software Set DIP switch SW1 as 0 0 0 1 1 0 1 0 OFF OFF OFF ON ON OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 0 1 0 OFF OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 1 1 0 OFF ON ON OFF Attention If NACs are configured the Evacuation Rate must be set on SW2 4 6 For more information see Setting Alert Rates Evacuation Rates NAC 5 Out...

Страница 58: ... upper range of addresses available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900 configurations add 100 to the recommended device address see Figures 27 and 28 When adding devices to FX 3500 3500RCU and MR 2350 configurations add 200 to the recommended device address see Figure 29 If any NAC circuit is configured as a Power Supply see 6 4 5 Two Stage with Basic Reporting an...

Страница 59: ... Configuration Two Stage with Basic Reporting Addressing Figure 27 FX 2000 Configurator Settings INX 10A Two Stage with Basic Reporting Figure 28 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Two Stage with Basic Reporting ...

Страница 60: ...60 Configuration Figure 29 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Two Stage with Basic Reporting ...

Страница 61: ...NACs are configured the Evacuation Rate must be set on SW2 4 6 For more information see Setting Alert Rates Evacuation Rates NAC 5 Output Functions on page 42 Table 15 Configuring Two Stage Address Assignment with Enhanced Trouble Reporting Function Address Recommended Device Address Common Trouble Base Address 85 Signal Silence Base Address 1 86 Monitor AC trouble Base Address 2 87 Monitor Batter...

Страница 62: ... available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900 configurations add 100 to the recommended device address see Figures 30 and 31 When adding devices to FX 3500 3500RCU and MR 2350 configurations add 200 to the recommended device address see Figure 32 If any NAC circuit is configured as a Power Supply see 6 4 7 Two Stage Address Assignment with Enhanced Trouble Reporti...

Страница 63: ...n Two Stage Address Assignment with Enhanced Trouble Reporting Figure 30 FX 2000 Configurator Settings INX 10A Two Stage with Enhanced Reporting Figure 31 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Two Stage with Enhanced Reporting ...

Страница 64: ...64 Configuration Figure 32 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Two Stage with Enhanced Reporting ...

Страница 65: ...as a Continuous Power Supply Set DIP switch SW1 as 0 1 0 1 1 0 1 0 OFF ON OFF ON ON OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 0 1 0 OFF OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 1 1 0 OFF ON ON OFF Set DIP switch SW4 7 and SW4 8 as 1 0 ON OFF Attention If NACs are configured the Evacuation Rate must be set on SW2 4 6 For more information see Setting Alert Rates Evacuation Rates NAC 5 Outpu...

Страница 66: ... the upper range of addresses available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900 configurations add 100 to the recommended device address see Figures 33 and 34 When adding devices to FX 3500 3500RCU and MR 2350 configurations add 200 to the recommended device address see Figure 35 Troubles occurring on a NAC circuit are only reported via the first stage address Table 16...

Страница 67: ...wo Stage with Basic Reporting and Power Supply Output Addressing Figure 33 FX 2000 Configurator Settings INX 10A Two Stage with Power Supply Output Figure 34 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Two Stage with Power Supply Output ...

Страница 68: ...68 Configuration Figure 35 FX 3500 3500RCU MR 2350 Configurator Settings INX 10A Two Stage with Power Supply Output ...

Страница 69: ...g in a Mircom System To configure the INX for Two Stage with Enhanced Trouble Reporting in a Secutron System To configure NAC 5 as a Continuous Power Supply Attention Two Stage Enhanced reporting is mandatory to meet ULC requirements Set DIP switch SW1 as 1 1 1 0 1 0 1 0 ON OFF ON OFF ON OFF ON OFF Set DIP switch SW2 1 to SW2 4 as 0 0 0 0 OFF OFF OFF OFF Set DIP switch SW2 1 to SW2 4 as 0 1 0 1 OF...

Страница 70: ...vate NAC3 return NAC3 line status Base Address 7 94 Activate NAC4 return NAC4 line status Base Address 8 95 Second Stage NAC1 Base Address 10 96 Second Stage NAC2 Base Address 11 97 Second Stage NAC3 Base Address 12 98 Second Stage NAC4 Base Address 13 99 Notes Mircom recommends always using the upper range of addresses available for the INX 10A When adding devices to FX 2000 and MR 2100 2200 2900...

Страница 71: ...ed Trouble Reporting and Power Supply Addressing Figure 36 FX 2000 Configurator Settings INX 10A Two Stage with Enhanced Reporting and Power Supply Addressing Figure 37 Secutron MR 2100 2200 2900 Configurator Settings INX 10A Two Stage with Enhanced Reporting and Power Supply Addressing ...

Страница 72: ...4 From the Add Devices window use the drop down menus to select the type of virtual device Supv Opt Mod the base address of the INX panel how many NAC circuits are being supervised 5 Click ADD CLOSE to return to the main window Figure 39 Add Devices Window 6 Add the appropriate TAG s to the new devices by double clicking the appropriate cell 7 To assign correlations to each virtual device right cl...

Страница 73: ...20 PPM as in FA 1000 or FX 2000 001 20 PPM 50 Duty Cycle Table 18 Independent Mode DIP Switch Settings NAC1 and NAC2 configured as Signals NAC3 NAC4 and NAC5 NAC1 and NAC2 CONFIGURE SWITCHES AS SHOWN Strobe Manufacturer SW5 1 3 Signal Rate SW4 4 6 SW3 SW4 SW5 Mircom Amseco Continuous Mircom Amseco Temporal Mircom Amseco March Time Mircom Amseco California Mircom Amseco 120 PPM 50 Duty Cycle System...

Страница 74: ... 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON ...

Страница 75: ...ngs NAC1 NAC2 and NAC3 configured as Signals NAC4 and NAC5 NAC1 NAC2 and NAC3 CONFIGURE SWITCHES AS SHOWN Strobe Manufacturer SW5 1 3 Signal Rate SW4 4 6 SW3 SW4 SW5 Mircom Amseco Continuous Mircom Amseco Temporal Mircom Amseco March Time Mircom Amseco California Mircom Amseco 120 PPM 50 Duty Cycle System Sensor Continuous System Sensor Temporal i ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4...

Страница 76: ...4 4 6 SW3 SW4 SW5 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON 1 8 2 3 4 5 6 7 ON...

Страница 77: ...77 Wiring 7 0 Wiring This chapter describes the proper field wiring for the INX 10A This chapter explains Maximum wiring distances Wiring Terminal Connections Wiring Power Supply Connections ...

Страница 78: ...E 18AWG 16AWG 14AWG 12AWG Amperes ft m ft m ft m ft m Ohms 0 06 2350 716 3750 1143 6000 1829 9500 2895 30 0 12 1180 360 1850 567 3000 915 4720 1438 15 0 30 470 143 750 229 1200 366 1900 579 6 0 60 235 71 375 114 600 183 950 289 3 0 90 156 47 250 76 400 122 630 192 2 1 20 118 36 185 56 300 91 470 143 1 5 1 50 94 29 150 46 240 73 380 115 1 2 1 70 78 24 125 38 200 61 315 96 1 0 2 0 70 21 112 34 178 5...

Страница 79: ...isabled IF it is interfering the FACPs Ground Fault Detection operation AND the FACP is used to manage the Ground Fault Detection Notes The Terminal Blocks are depluggable for ease of wiring All power limited circuits must use type FPL FPLR or FPLP power limited cable 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT T...

Страница 80: ...1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON FX 2000 ADDRESSABLE LOOP CONNECTIONS B A TO NEXT DEVICE IN LOOP ADDRESSABLE LOOP 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON FX 2000 ADDRESSABLE LOOP CON...

Страница 81: ...SYNCH SIGNAL FROM FACP SYNCH INPUT1 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON NAC CIRCUIT FROM FACP MP 300 3 9K EOL SYNCH SIGNAL FROM FACP SYNCH INPUT1 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER ...

Страница 82: ... 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON SYNCH OUTPU...

Страница 83: ...ER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON 1 8 1 8 1 8 1 8 1 8 POWER ON CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON MASTER SLAVE 1 SYNCH INPUT1 SYNCH OUTPUTS 1 2 1 8 1 8 1 8 1 8 1 8 POWER ON CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPU...

Страница 84: ...ULT JW2 MAIN DISPLAY PANEL ACK BUTTON 1 8 1 8 1 8 1 8 1 8 POWER ON CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON MASTER SLAVE 1 SYNCH INPUT1 SYNCH OUTPUTS 1 2 1 8 1 8 1 8 1 8 1 8 POWER ON CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON ...

Страница 85: ...ption SLC Interface Contact Interface All Call N A N A NAC by NAC activation Yes No NAC circuit trouble reporting Yes No Common trouble reporting Yes Yes Enhanced trouble reporting Yes No RELAY CONTACT ACTIVATION FROM FACP SINGLE STAGE SYNCH INPUT1 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TRO...

Страница 86: ... all 0 OFF RELAY CONTACT ACTIVATION FROM FACP TWO STAGE SYNCH INPUT1 1 8 1 8 1 8 1 8 1 8 POWER ON ADD LINE ACTIVITY ALARM COMMON TROUBLE CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON FACP Second Stage Alarm Relay COM NO NC Aux Power TROUBLE RELAY NO NC C P To FACP input configured for trouble FACP First Stage Alarm ...

Страница 87: ...DC 1 AMP RESISTIVE LOAD AUX SUPPLY SUPV GF EGND REMOVE TO DISABLE GROUND FAULT SUPERVISION 1 7AMPS MAXIMUM 24VDC REGULATED ATTENTION Ground Fault Detection is required at all times INX Ground fault detection can only be disabled IF it is interfering the FACP s Ground Fault Detection operation AND the FACP is used to manage the Ground Fault Detection C P NC NO ADD LINE ACTIVITY ALARM COMMON TROUBLE...

Страница 88: ... JW2 MAIN DISPLAY PANEL ACK BUTTON NAC 1 YZ Z Z YZ NAC 5 YZ Z Z YZ NAC 4 YZ Z Z YZ NAC 3 YZ Z Z YZ NAC 2 YZ Z Z YZ 3 9K 1 2W ELR Listed S5434 Mircom Model MP 300 ADD LINE ACTIVITY ALARM COMMON TROUBLE 1 8 1 8 1 8 1 8 1 8 POWER ON CPU FAIL BATTERY CHARGER TROUBLE JW1 P P3 P4 P1 P2 AUX OUTPUT TROUBLE SYNCH OUT TROUBLE GFAULT JW2 MAIN DISPLAY PANEL ACK BUTTON NAC 1 YZ Z Z YZ NAC 5 YZ Z Z YZ NAC 4 YZ ...

Страница 89: ...er Description Electrical input ratings 120 VAC 60 Hz 2 A 240 VAC 50 Hz 1A Power supply total current 10 A maximum Battery Fuse Replace with WX 058 Battery Cable Assembly Attention DO NOT exceed power supply ratings Wire as shown using proper wire gauges Connect batteries after the system main A C power is turned on to reduce sparking P1 P2 P3 P4 _ BATTERY SEC TX _ _ Battery Battery red green blk ...

Страница 90: ...inate the Common Trouble LED should flash and the Trouble Relay on the main board will be active 3 Connect the batteries while observing correct polarity the red wire is positive and black wire is negative 4 All indicators should extinguish except for normal power AC ON green LED 7 5 Troubleshooting The following are common methods to solving Circuit Ground Fault Battery and Common troubles 7 5 1 ...

Страница 91: ...uble If only a common trouble is indicated on the main panel and none of those above confirming trouble indicators are on then check the following for possible fault any missing interconnection wiring improperly secured cabling ...

Страница 92: ...wever brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations which may damage electronic equipment such as a fire alarm system After a power interruption has occurred immediately conduct a complete system test to ensure that the system operates as intended Failure of Replaceable Batteries Systems with w...

Страница 93: ...d or awakened Audible notification appliances may be interfered with by other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired person Telephone Lines If telephone lines are used to transmit alarms they may be out of service or busy for certain periods of time ...

Страница 94: ...sible for any customs fees taxes or VAT that may be due Conditions to Void Warranty This warranty applies only to defects in parts and workmanship relating to normal use It does not cover damage incurred in shipping or handling damage caused by disaster such as fire flood wind earthquake or lightning damage due to causes beyond the control of MGC such as excessive voltage mechanical shock or water...

Страница 95: ...etermined and which may be revised from time to time will be charged for each unit repaired Products which MGC determines not to be repairable will be replaced by the nearest equivalent product available at that time The current market price of the replacement product will be charged for each replacement unit The foregoing information is accurate as of the date of publishing and is subject to chan...

Страница 96: ...4 VDC Filtered special application 1 7 A 49 C Auxiliary relays resistive loads Must be connected to a Listed Power Limited Source of Supply Terminals are labelled GROUND and TROUBLE Ground Fault Form C 1 Amp 28 VDC Common Trouble Form C 1 Amp 28 VDC Electrical ratings AC line voltage Maximum allowable current 120V 60Hz 240V 50Hz 2 Amps 1 Amp primary 120V 4 25A 240V 2 125A NAC Circuits 24VDC regula...

Страница 97: ...for thirty minutes of alarm as a multiplier figure IMPORTANT NOTICE The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous power without provision of any disconnect devices Use 12 AWG wire with 600 volt insulation and proper over current circuit protection that complies with the local codes Refer to9 0 Appendix A Specifications And Features for specif...

Страница 98: ...ddresses The following are the specs for the system Base Address 193 Protocol System Sensor AC Failure Report Delay No Delay Charger Yes Battery Yes Cut Charger when NACs activated Yes Alert Rate N A Evacuation Rate Temporal Strobe Type None NAC 4 Output Settings NAC NAC 5 Output Settings NAC ON SW1 SW4 SW3 SW5 SW2 ON ON ON ON 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3...

Страница 99: ...ystem Base Address 188 Protocol System Sensor AC Failure Report Delay 2 hour Charger Yes Battery Yes Cut Charger when NACs activated Yes Alert Rate Follow Inputs Evacuation Rate Temporal Strobe Type None NAC 4 Output Settings NAC NAC 5 Output Settings Continuous Supply ON SW1 SW4 SW3 SW5 SW2 ON ON ON ON 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 ...

Страница 100: ...e system Base Address 185 Protocol System Sensor AC Failure Report Delay 2 hour Charger Yes Battery Yes Cut Charger when NACs activated Yes Alert Rate Follow Inputs Evacuation Rate Temporal Strobe Type None NAC 4 Output Settings NAC NAC 5 Output Settings Continuous Supply ON SW1 SW4 SW3 SW5 SW2 ON ON ON ON 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 1 8 2 3 4 5 6 7 ...

Страница 101: ...trobe NAC System Sensor SpectrAlert Horn H12 24 n a Horn H12 24W n a Wheelock Horn AH 24 R n a Horn AH 24 WP R n a Horn MT 12 24 ULC n a Horn AMT 12 24 R ULC n a Bell MB G6 24 R n a Bell MB G10 24 R n a Table 26 FX 2000 and FLeX Net Series ULI Compatible Synchronized Strobes Manufacturer Brand Strobe Model Max Strobe NAC Amseco Potter Mircom FHS 240 110 15 Gentex Corp Secutron MRA HS3 24ww 20 Spec...

Страница 102: ......

Страница 103: ......

Страница 104: ...Fax 905 660 4113 MGC 2014 Printed in Canada Subject to change without prior notice www mircomgroup com U S A 4575 Witmer Industrial Estates Niagara Falls NY 14305 Tel 888 660 4655 Fax 905 660 4113 TECHNICAL SUPPORT North America Tel 888 Mircom5 888 647 2665 International Tel 905 647 2665 ...

Отзывы: