Configuration
6.3.5 Single Stage with Basic Reporting and Power Supply Output Addressing
In order to maximize the amount of addresses available, if a NAC circuit is configured as a
Power Supply, the next configured NAC Circuit is assigned the address reserved for the
previous Circuit.
Example Application
•
NAC 5 configured as a Power Supply.
•
INX-10A Common Trouble reporting address is 194.
To configure the recommended base address
To configure the INX for Single Stage with Basic Reporting in a Mircom System
To configure the INX for Single Stage with Basic Reporting in a Secutron System
To configure NAC 5 as a Continuous Power Supply
Set DIP switch SW1 as:
0-1-1-1-1-0-1-0
OFF-ON-ON-ON-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as:
0-0-1-1
OFF-OFF-ON-ON
Set DIP switch SW2-1 to SW2-4 as:
0-1-0-1
OFF-ON-OFF-ON
Set DIP switch SW4-7 and SW4-8 as:
1-0
ON-OFF
Attention: If NACs are configured the Evacuation Rate must be set on SW2 4-6. For
more information see Setting Alert Rates, Evacuation Rates, NAC 5
Output Functions on page 42.
SW1
1
8
2 3 4 5 6 7
SW2
ON
1
8
2 3 4 5 6 7
SW2
ON
1
8
2 3 4 5 6 7
SW4
ON
1
8
2 3 4 5 6 7
!