6.4.3 Two Stage Address Assignment with Enhanced Trouble Reporting
To configure the recommended base address
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Mircom
System
To configure the INX for Two Stage with Enhanced Trouble Reporting in a Secutron
System
Set DIP switch SW1 as:
1-0-1-0-1-0-1-0
ON-OFF-ON-OFF-ON-OFF-ON-OFF
Set DIP switch SW2-1 to SW2-4 as:
0-0-0-0
OFF-OFF-OFF-OFF
Set DIP switch SW2-1 to SW2-4 as:
0-1-0-1
OFF-ON-OFF-ON
Attention: Two Stage Enhanced reporting is mandatory to meet ULC requirements.
Attention: If NACs are configured the Evacuation Rate must be set on SW2 4-6. For
more information see Setting Alert Rates, Evacuation Rates, NAC 5
Output Functions on page 42.
Table 15 Configuring Two Stage Address Assignment with Enhanced Trouble
Reporting
Function
Address
Recommended
Device Address
Common Trouble
Base Address
85
Signal Silence
Base A 1
86
Monitor AC trouble
Base A 2
87
Monitor Battery/Charger trouble
Base A 3
88
Monitor Earth Ground Fault
Base A 4
89
Activate NAC1, return NAC1 line status
Base A 5
90
Activate NAC2, return NAC2 line status
Base A 6
91
Activate NAC3, return NAC3 line status
Base A 7
92
Activate NAC4, return NAC4 line status
Base A 8
93
SW1
1
8
2 3 4 5 6 7
1
8
2 3 4 5 6 7
SW2
ON
1
8
2 3 4 5 6 7
SW2
ON
!
!