The configuration parameters available are in sequence:
code 11
Max settable temperature for pre-heating. Configure the adjustment limit of the
hP
parameter. The absolute maximum that can be set is 100°.
code 12
Max settable temperature for heating. Configure the adjustment limit of the parameter
ht
. When the adjustment with potentiometer is used, this will adjust between a minimum set
with the parameter
ht
and this maximum value. The absolute maximum settable is 500°.
code 13
Operating mode. See operating modes section of the manual
0
= adjustment only activates when inputs activate at the relevant temperatures set
1
= adjustment activates at the input pre-heating temperature for heating.
2
= timed heating cycle aborts if input removed.
3
= timed heating cycle after impulse on heating input.
code 14
Timers unit of measurement selection. It allows to operate with times up to 99.9 sec.
CEn
(timing in hundredths of a second)
dEC
(timing in tenths of a second)
code 15
Select temperature unit of measurement.
C
(degrees Centigrade)
F
(degrees Fahrenheit)
code 16
Analogue input voltage selection. Allows you to adjust the temperature with a
potentiometer connected to the device or with an external 0-10V voltage connected instead of
the potentiometer.
POt
input 0-5V with potentiometer
U01
input 0-10V
code 17
Alloy used in heater. Indicates to the TR-evo which material the heating element is made
of, to allow the correct temperature indication.
1
= Nichrome40
2
= AISI 316
3
= Alloy20
4
= MS500
5-9
= Others
code 18
Increment at minimum firing TRIAC This parameter allows you to change how the
heating element is powered to improve performance in certain specific cases. The parameter
can take values between 0 and 20. Normally it should be left at 0.
code 19
Loop gain setting. It allows to adapt the temperature control according to the specific
power used in particular situations. The parameter can assume values between 0 (very low
gain, when specific power is very high) and 30 (high gain to try to compensate very low
specific power). The default value is 5 valid for most configurations.
code 20
Serial bus mode. Select communication format depending on the other connected
devices.
72
= (7 + 2stop)
17