2

Rapid temperature change
This   error   occurs   in   the   tuning   procedure   and   highlights   the   operation 
started with the heating element hot. Wait for it to cool and repeat the 
operation.

3

Insufficient voltage reading;
this   error   occurs   in   the   tuning   procedure   and   highlights   an   error   in 
transformer   connection   or   in   its   dimensioning.   During   the   first   tuning 
operation after installation, it may also indicate improper connections.

4

Insufficient current reading;
this error highlights breakage of a heating element when using elements in 
parallel,   if   it   occurs   during   the   tuning   procedure   it   highlights   a 
dimensioning error of the pulse transformer or in jumper configuration on 
the   temperature   controller.   During   the   first   tuning   operation   after 
installation, it may also indicate improper connections.

5

Too high voltage reading;
this error highlights voltage is too high in the equipment feedback and 
requires   a   tuning   procedure.   During   the   tuning   procedure,   an   error 
highlights in the transformer connection. During the first tuning operation 
after installation, it may also indicate improper connections.

6

Too high current reading;
this error highlights the short circuit of one of the heating elements when 
using   elements   in   series,   if   it   occurs   during   the   tuning   procedure   it 
highlights   a   dimensioning   error   of   the   pulse   transformer   or   in   jumper 
configuration   on   the   temperature   controller.   During   the   first   tuning 
operation after installation, it may also indicate improper connections.

7

Voltage not reaching the heating element
Possible causes:
- Power adjustment element (TRIAC) faulty.
- Connections between the temperature controller and the heating element 
interrupted.
- pulse transformer faulty.

8

Current not passing through the heating element
Possible causes:
- heating element damaged.
- loose heating element fastening.

9

Voltage reaching the heating element not read.
Possible causes:
- the feedback cable to the temperature controller is interrupted.
- loose connections on the temperature controller terminals.
- distortion on the power supply line too high.

 14     

Содержание TR-EVO

Страница 1: ...TR EVO 220 240Vac INSTRUCTIONS FOR USE MG MGINDUSTRY srl Via Casa Celeste 14 36014 Santorso VI Italy E mail mg mgonline it Draft 2 13 02 2020 EN...

Страница 2: ...Warranty 19 Appendix 20 System dimensioning 20 Editor s notes This manual contains confidential information All rights reserved The manufacturer reserves the right to make changes or improvements wit...

Страница 3: ...ctional and compact this system is the strength of heat sealing processes including with hot air temperature control hot cutting etc Warnings ATTENTION for correct use of your temperature controller i...

Страница 4: ...ltage contact Temperature adjustment range 30 to 500 degree with lockable limits Unit operational temperature 0 to 50 degree Adjustments and configuration through integrated keypad and numeric display...

Страница 5: ...d element during the tuning phase the temperature can be found on measurement Based on these calculations the power necessary to bring or maintain the temperature set is calculated and a solid state s...

Страница 6: ...fastening clips supplied An adapter for DIN rail installation EN 50022 50035 can be supplied on request in this case reserve 60mm next to the power unit Power transformer Positioning of the transforme...

Страница 7: ...connections can cause problems Warning remember that during heating for example of a bar elongation and shortening caused by heating and cooling of the heating element must not affect the quality of...

Страница 8: ...e power supply of the device between 220 and 240 Vac 15 15 This line is protected inside the device with a 100mA fuse Connect mains neutral to terminal 5 shared with the neutral of power output Connec...

Страница 9: ...e a voltage between 12 Vac and 24Vac or from 12Vdc to 30Vdc by applying the positive to terminal 11 and 13 and the negative to terminal 12 In the presence of the START signal terminal 11 the heating e...

Страница 10: ...side of this paragraph how to make two passages Do reference to the section Transformer sizing for more information User interface connector The power unit should be connected to the display user inte...

Страница 11: ...S500 it is not an alloy but is used to adapt the air heater to the temperature controller Nickrome40 and Alloy20 are registered trademarks of the relevant manufacturer Transformer dimensioning Conside...

Страница 12: ...are used to calculate the secondary voltage Vs of the transformer in volts according to the formula Vs Pr The power of the transformer Pt must be calculated in Watts using the formula Pt Pr 1 1 where...

Страница 13: ...ies If the device detects anomalies in its operation it blocks and signals the type of anomaly on the display and activates a signal output In standby mode the equipment does not adjust the temperatur...

Страница 14: ...ture control at the pre heating temperature 2 and the start input allows you to activate the temperature control at the heating temperature 4 The start input has priority over the pre heating input On...

Страница 15: ...ivated at the right moment 5 Heating the temperature is brought to the work value for the time selected on the relevant timer 6 Cooling the heating element is no longer powered and when the temperatur...

Страница 16: ...During the tuning procedure an error highlights in the transformer connection During the first tuning operation after installation it may also indicate improper connections 6 Too high current reading...

Страница 17: ...directly using the associated keys With serial bus connection In this mode configuration is executed using the commands sent via the EIA TIA485 interface by a PLC or PC remote device The communication...

Страница 18: ...nd keep pressed the key until the counter on the second line reaches zero Warning The counter may continue to restart even if you press and hold the button signalling that the conditions are not right...

Страница 19: ...measurement C degrees Centigrade F degrees Fahrenheit code 16 Analogue input voltage selection Allows you to adjust the temperature with a potentiometer connected to the device or with an external 0 1...

Страница 20: ...vo devices On code 23 the display shows rEt and allows you to exit parameter programming status by pressing the key The key returns you to the beginning parameter 11 display Maintenance ATTENTION befo...

Страница 21: ...g high temperatures or variation of electrical voltage earthquakes fires etc The warranty also excludes all parts subject to normal wear for which replacement is planned as ordinary maintenance In all...

Страница 22: ...20...

Страница 23: ...Maximum power available Watt Material to seal Name Thickness m Layers q q q q 2 layers 2 layers 3 layers 4 layers Frequency Speed max n strikes min Sealing speed m sec Sealing time sec Choice of heati...

Страница 24: ...pplication diagram Cooling q no q air q water Timed management of sealing no on machine on temperature controller Desired user interface q numerical display and potentiometer q dnumerical disply and a...

Отзывы: