Important Pre-Installation Information
Before you begin
, review the information and safeguards
below regarding the installation and operation of the gas
fireplace.
This fireplace is designed for use only with the ANSI Z21.50
Decorative Gas Logs and Burner tested and approved for
this fireplace and may only be connected to the gas supply
listed on the label
. Never use propane gas in a gas fireplace
designed for natural gas or natural gas in a gas fireplace
designed for use with propane gas.
The gas fireplace must be installed by an NFI Certified
or other qualified professional installer.
The installation,
including provisions for combustion and ventilation air, must
conform with local codes, or, in the absence of local codes, with
the latest edition of the National Fuel Gas Code, ANSI Z223-1,
and NFPA54.
Keep the fireplace area clear and free from combustible
materials, gasoline, and other flammable vapors and liquids.
The fireplace must have a gas supply line that has been installed
by a qualified technician in accordance with all local
codes. The gas supply line must be ½” minimum interior
diameter. If the gas line to the fireplace is longer than 5’, a
larger diameter line may be necessary.
Burner P/N
BTU*
(x 1000)
Orifice Drill
Size (top/front)
Included in
NG
LP
GML-2-
39/44(P)A
90
23/45 44/55 MGFPST43
*Nominal BTU based on gas inlet pressure. Nominal gas inlet
pressure for natural gas is 5” W.C..
Required Gas Pressure:
The minimum inlet gas supply pres-
sure for the purpose of input adjustment is 5” of water column
(w.c.) for natural gas. The maximum inlet gas supply pressure
is 10.5” w.c. for natural gas. The minimum inlet gas supply pres
-
sure for the purpose of input adjustment is 11” of water column
(w.c.) for propane gas. The maximum inlet gas supply pressure
is 13” w.c. for propane gas.
Testing the Gas Supply System:
The gas fireplace and its
required individual shut-off valve must be disconnected from
the gas supply piping system while performing any tests of the
piping system at pressures in excess of ½ psig. The gas fire
-
place must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system at test pressures equal
to or less than ½ psig. This is accomplished by closing the gas
supply line valve required by NFPA 54.
A fireplace screen must be replaced after service and be in
place when the appliance is in operation and, unless other
provisions are provided, the screen shall have an opening(s)
for introduction of combustion air. When glass fireplace doors
are used, operate the gas fireplace with the doors open.
Important:
To comply with building code acceptances, and
for safe operation and proper performance of this fireplace, use
ONLY MASON-LITE parts and accessories.
Use of other controls, parts, and accessories which are not
designed for use with MASON-LITE gas fireplaces is prohibited
and will void all warranties, certifications, listings, and building
code approvals, and may cause property damage, personal
injury, or loss of life.
The burner included with this gas fireplace is non-convertible
and only meant to be used with the gas listed on the rating
plate.
WARNING
:
THIS FIREPLACE HAS
NOT BEEN TESTED FOR USE
WITH AN UNVENTED GAS LOG SET. TO REDUCE
THE RISK OF FIRE OR INJURY, DO NOT INSTALL AN
UNVENTED GAS LOG SET INTO FIREPLACE.
WARNING
:
This Fireplace has been tested for use
only with
optional
Glass Doors Crown-Breckinridge (or) Mckenzie-Pendelton
(by Portland Willamette)
If optional arches are used, doors need to be customized.
WARNING
:
Install only approved, 12” B-Vent or listed UL 103-12” I.D.
Class A Chimney System.
Chimney maximum height: 40 feet
Chimney minimum height: 14 feet (with offset = 17 feet)
2 offsets maximum.
Important
: Follow the chimney pipe manufacturer’s
instructions on the installation of their specific flue system.