Installing the valve/control box assembly

1. 

Fasten the valve/control box assembly to a stud such that 

the  control  switch  is  facing  in  the  desired  direction  and 

flush with the future location of the finished wall or other 

enclosure.

2. 

Install the two ‘D’ batteries into the battery holder within the 

control box.

3. 

Run  the  wires  for  the  spill  switch  through  the  small  hole 

in the upper wall. Important: This control box must remain 

accessible and removable for service after installation.

Installing Spill Switch and Baffle assembly

1"

4

2

6"

5

8"

1"

4

2

6"

5

8"

1"

4

2

6"

5

8"

1"

4

2

6"

5

8"

Figure 30

1. 

Connect the blade connectors on the spill switch wires to 

the matching wires from the valve/ control box assembly 

coming through the upper hole in the firebox.

2. 

Center  the  black  steel  baffle  with  the  spill  switch  sensor 

pointed toward the room (out of the fireplace). 

 

Figure 31

3. 

Use six (6) drywalls screws to fasten it in place on the front-

most part of the firebox ceiling as shown through the six (6) 

pre-drilled holes.

4. 

Attach the trim plates to the left and right side of the baffle 

with  the  sheet  metal  screws  so  that  the  edges  are  flush 

with the firebrick.   

 

 

  

 

 

Important

: This baffle assembly and only this the supplied 

assembly (with spill switch) must be properly installed for 
the safe operation of this gas fireplace.

    

 

Checking and Adjusting the Pilot

1. 

Follow the lighting instructions to light the pilot. The pilot 

flame should encircle the generator tip which is preset at 

the factory (

Figure 33

). Ordinarily, the pilot will not require 

field adjustment.

2. 

If adjustment is necessary, remove the cap screw (

Figure 

33

)  and  turn  the  smaller  gas  adjustment  screw  inside 

counterclockwise to increase the pilot flame and clockwise 

to decrease the pilot flame. Replace cap screw.

OUT

IN

P

IL

O

T

IN

Figure 32

Pilot

Flame

Electrodes

Figure 33

Open

Figure 34

Figure 35

Note

: This burner system is equipped with an APK-01 valve 

assembly.

Placing the Decorative Lava Rock

If  desired,  open  the  bag  of  lava  rock  and  pour  its  contents 

around the base of the grating in an attractive pattern. Do not 

place the Lava Rock on the logs or grate.

Adjusting Air Mixers

Burners  are  equipped  with  air  mixers  for  the  top  and  front 

burners. Adjust the size and color of the flame by opening (turn 

outward) or closing (turn inward) as shown in 

Figure 33, 34

.

Содержание Mason-Lite MGFPST-43A

Страница 1: ...requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactu...

Страница 2: ...This page has been left intentionally blank...

Страница 3: ...20 500 mm HEARTH EXTENSION BEYOND SIDES 12 300 mm INSULATION FROM FIREBOX 0 0 mm The installation including provisions for combustion ventilation air and required minimum permanent vent opening must...

Страница 4: ...NT 2 8 LOWER DOME FRONT 2 9 LOWER DOME SIDE 2 10 UPPER DOME FRONT 2 11 UPPER DOME SIDE 2 12 DOME TOP FOR 12 B VENT 1 13 INSULATION BLANKET NOT INCLUDED 14 12 VENT PLATE ASSEMBLY NOT INCLUDED 15 3 REBA...

Страница 5: ...log 30 2 11 MFP 214 Burner Grate Brackets 2 2 Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending upon the siz...

Страница 6: ...lt in property damage or personal injury 2 3 8 SPILL SWITCH BAFFLE 43 1 4 53 29 5 8 62 1 8 A A GAS INLET 10 1 4 9 3 4 4 1 4 CHIMNEY OR UL 103 12 ID CLASS A SECTION A A CONNECT TO A 12 B VENT B 38 1 4...

Страница 7: ...he gas fireplace and its required individual shut off valve must be disconnected from the gas supply piping system while performing any tests of the piping system at pressures in excess of psig The ga...

Страница 8: ...plied Model No GML 2 39 44 P A WARNING Any application other than the Intended Use as stated above is in violation of the manufacturer s instructions and is hereby prohibited Such violation may cause...

Страница 9: ...radiant heat is maintained to safe limits Combustible Floor Clearances MGFPST43 Mason Lite Fireplaces have been designed with zero clearance to combustible floors Mason Lite Fireplace Chimney System...

Страница 10: ...Figure 11 for support of anchor rods by the steel support frames For fireplace support foundations installed on concrete refer to Appendix I and II pages 20 21 for specific instructions Rebar locatio...

Страница 11: ...is the task and responsibility of the general contractor installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fireplace installation...

Страница 12: ...quately affix all the fireplace components The mortar is premixed and dry and is to be used to adhere all the fireplace components Be sure to use clean water and work it up into a mixture that is past...

Страница 13: ...e bottle brush prior to placing the epoxy This will ensure a sufficient bond to the concrete Figure 12 Note A DEPUTY INSPECTOR MAY ME REQUIRED FOR THE EPOXY DOWELS PROCESS CHECK WITH YOUR LOCAL BUILDI...

Страница 14: ...till wet 7 Set the remaining lintel as shown in Figure 16 Figure 16 Lintel Lower Dome Side 8 Now you are ready to start the smoke dome assembly Take the lower side dome positioned so that the beveled...

Страница 15: ...the framework to house the chimney system Now that you have completed the smoke dome assembly all the components should stack up for a smooth transition into the flue components Setting the smoke dom...

Страница 16: ...he finished firebrick floor of the fireplace so that it is at least 11 eleven inches above the combustible floor system Disclaimer Masonry Fireplace Industries wishes to express that as the manufactur...

Страница 17: ...hazard MFI cannot be responsible for the make up of material on the exterior of the fireplace you have chosen nor can MFI be held responsible for the materials in a room that may be responding negativ...

Страница 18: ...e sections of vertical pipe that are more than 10 ten feet measuring between elbows you must insert at midpoint a chimney stabilizer When installing the stabilizer pull out the support straps with a g...

Страница 19: ...n 10 feet the top of the chimney still needs to be at least 2 feet above a point measured from a distance of 10 feet horizontally along the roof Though there are many configurations in meeting these r...

Страница 20: ...ht side of the baffle with the sheet metal screws so that the edges are flush with the firebrick Important This baffle assembly and only this the supplied assembly with spill switch must be properly i...

Страница 21: ...and all flames main burner and pilot will go out see important note below OPERATING THE BURNER USING THE REMOTE Move the wall switch to the REMOTE position and follow the instructions included in the...

Страница 22: ...nd chimney system must be completely dry This means that the unit must stand without any firing for a minimum of 28 days Only after that period of time can a first lighting take place Do not let the f...

Страница 23: ...done twice a year In colder climates cleaning should be done more often Always allow the fireplace to completely cool before you work on it which means of course shutting off all gas and electrical c...

Страница 24: ...lts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads...

Страница 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Страница 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 27: ...liate thereof liable in any respect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse...

Отзывы: