23
5
LOCAL USER INTERFACE (LUI)
The local user interface may be used to monitor the device
behaviour as well as configuring and commissioning the
controller during installation and normal operation. The
local user interface consists of 2 row LCD and 4 button key-
pad interface. There are also custom graphical characters
for special conditions.
5.1
Measurement monitoring
When the device is powered, it enters the measurement
monitoring view. The following measurements may be
viewed from the display. The Table 5 identify the default
unit and also optional unit of the measurement.
If the unit selection is altered from the FieldCare software to
US units, the pressure default unit will automatically be
changed to psi and temperature unit to Fahrenheit.
The active unit may be changed by pressing the
?
key
constantly. The display shows the current unit selection on
the top row of the display. You may change the selection by
pressing
+
or
-
key while keeping the
?
key pressed
down. When the buttons are released the current selection
will be activated.
If the device has been idle for 1 hour, and there is no user
activity on the local user interface, the measurements will
start scrolling on the display. This enables the user to view
all the measurements through the window of the main
cover.
Fig. 15
Local user interface (LUI)
Table 6
Default / optional units of measurements
Measurement
Default unit
Optional unit
valve position
Percentage
(of full scale)
Angle, where 0 % refers
to 0 deg.
target position
Percentage
(of full scale)
none
current loop set-
point (ND9000H,
ND7000H)
mA
Percentage
(of full scale)
setpoint
(ND9000F, P)
Percentage
(of full scale)
actuator pressure
difference
bar
psi
supply pressure
bar
psi
device
temperature
degree Celsius
degree Fahrenheit
Fig. 16
Measurement unit change, ND9000H and ND7000H
Fig. 17
Measurement unit change, ND9000F and ND9000P
— continuous push
— brief push
— continuous push
— brief push