metrofires Classic Rad Скачать руководство пользователя страница 4

4

Pioneer manufacture an extensive range of Pioneer ‘Ash Floor Protectors’ 
which comply with the minimum floor protector requirements of  
AS/NZS2918:2001, and can be installed with any freestanding Metro 
wood fire. Metro freestanding wood fires do not require an insulated floor 
protector as they comply with the minimum floor protector requirements of 
AS/NZS2918:2001. These minimum floor protector requirements are;

•   They must be of adequate size to give appropriate wall, rear and front 

clearances/projections as detailed below and in the chart illustrated on 
page 7. Note;

•   The floor protector must extend 200mm horizontally to the rear and 

each side directly below the door opening, and 300mm forward of the 
door opening

•  The upper surface of the floor protector must be made of non-

combustible material.

A suitable floor protector for a Metro freestanding wood fire is therefore any 
non-combustible material which could include;

•   Ceramic tiles with grouted joints fixed directly to a hard base over     

timber flooring

•   A sheet of toughened glass, panel steel etc. laid directly onto a wooden 

or other combustible floor.

Metro radiant fires

Lift the Metro fire onto the floor protector and using a suitable measuring 
device, ensure that the minimum wall clearances and front floor protector 
projections as detailed in the chart on page 7 are met or exceeded. 
Once the Metro’s location on the floor protector is established and if the 
installation is within New Zealand, seismic restraint is required.

Using masonry anchors if the floor protector is on a concrete floor or coach 
bolts if a wooden floor, secure through the holes provided at the base, 
behind both rear legs.

Note: The anchors must pass through the floor protector and securely 
anchor the Metro to the floor.

Metro pedestal and base model fires

Prior to lifting the Metro fire onto the floor protector, ensure you have 
removed, rotated and re-assembled the mount plate from the back of the 
pedestal base as detailed in diagrams 3 & 3A above

This rear panel must 

be rotated with the return fold facing back the opposite way to create the 
mount plate and fixing points for seismic restraint of the wood fire. 

Lift the Metro fire onto the floor protector and using a suitable measuring 
device, ensure that the minimum wall clearances and front floor protector 
projections as detailed in the chart on page 7 are met or exceeded.

Once the location of the fire is established, you can then secure the Metro 
through the floor protector into the floor using the two seismic restraint 
holes in the rear edge of the mount plate. Use masonry anchors if the floor 
protector is on a concrete floor or coach bolts if a wooden floor

Note: The anchors must pass through the floor protector and securely 
anchor the Metro to the floor.

Floor protector size, construction and fitting

Correct mount plate position 

Diagram 3

Diagram 3A

Remove the four screws 
from the pedestal base and 
rotate the mount plate so 
the return fold faces back 
the other way. Refix in place.

Preparing the mount plate 

Seismic restraint

Содержание Classic Rad

Страница 1: ...fire in your home 9 Optional wetbacks 9 Getting to know your Metro fire 10 Operating your Metro fire 10 Cleaning and maintenance 11 Troubleshooting 12 Metro Fires warranty 13 Replacement parts 14 15 H...

Страница 2: ...ocated this manual familiarise yourself with the illustrations on pages 2 3 and proceed as follows Metro radiant fires These Metro s are supplied virtually fully assembled Packed inside the firebox yo...

Страница 3: ...ning with one hand holding the flue spigot with the other slowly lift the front of the wood fire all the way back and rest the wood fire on its rear heat shield on the floor Remove the packaging palle...

Страница 4: ...f the installation is within New Zealand seismic restraint is required Using masonry anchors if the floor protector is on a concrete floor or coach bolts if a wooden floor secure through the holes pro...

Страница 5: ...the flue pipe must also be sealed into the Metro fires flue outlet This is critical for optimum operation All Metro fires have been tested with a Pioneer double flue shield For the Metro fire to be i...

Страница 6: ...oints 4 A further three bolt heads will also be visible on the inside rear wall of the firebox these are threaded into the 6mm thick firebox Remove all three 5 Using the tube of sealant supplied with...

Страница 7: ...365 555 615 501 758 Wee Ped 2 263 651 580 490 170 230 350 110 843 825 1274 1050 425 295 485 602 503 665 Classic Rad 3 257 695 780 500 220 229 430 100 1037 728 1487 1168 328 393 583 530 707 680 Xtreme...

Страница 8: ...missing bricks baffle plate promet extension white board on the baffle plate It is critical that the fire not be operated with cracked or broken door glass Please note the above 3 points require regul...

Страница 9: ...our Metro alternative wetbacks will void the Metro s emission approvals and may seriously affect the performance of the appliance and void its warranty Other considerations are Distance from your Metr...

Страница 10: ...ter content and ensure surface area combustion Do not turn the air control down lower than you need to if you want the Metro to burn overnight endeavour to obtain an 8 hour burn time not 12 hours It w...

Страница 11: ...build up takes depends on the density and cleanliness of your fuel To remove the excess ash your Metro should not be operating Open the door and using a hearth shovel or similar empty the excess ash...

Страница 12: ...ntal and can be caused by many variables and it is purely trial and error to ascertain the cause Air turbulence and or negative air pressure influences around the flue termination can be caused by too...

Страница 13: ...be reduced If your Metro wood fire has been neglected by not being regularly maintained and serviced warranty may be declined It is critical the fire not be operated with over worn faulty or missing...

Страница 14: ...t required Type of steel baffle s required Wetback options ECO Tiny Ped ECO Tiny Rad Tiny Promet 500 1550 Tiny Baffle 500 2050 2kW Wetback 450 0050 Tiny Rad Woody Tiny Woody Promet Set 500 2004 Tiny W...

Страница 15: ...d Woody Xtreme Ped Xtreme R2 Promet Set 500 2010 Xtreme R2 Front Baffle 500 2510 Xtreme R2 Rear Baffle 500 2515 3kW Wetback 450 0100 Mega Rad Mega Rad Promet Set 500 2020 Mega Rad Front Baffle 500 253...

Страница 16: ...l models which is generally required when applying for a building consent See your Metro retailer to obtain a copy or visit www metrofires co nz metrofires co nz Visit the Metro website metrofires co...

Отзывы: