5.2 MX2034 ONLY
Symptom
Possible Problems
Recommended Action
Maximum current below
20 mA
Loop resistance too large or
power supply too low.
Verify that total loop resis-
tance does not exceed the
maximum per Installation
Manual 100545.
Current output stuck < 3.5
mA
Probe is disconnected or out
of range
Verify that the probe is con-
nected and the gap is in the
specified OK region.
Current output high or low
Incorrect 4 – 20 Scale
selected
Upload the device informa-
tion (see Section 3.5.2) and
verify the configured scale.