Figure 22: Custom Calibration Shortened Curve
If this occurs, verify that the voltages you entered were correct. Verify that your system
components combine to the correct length. If all is correct, you can choose to accept the
shortened curve or hit cancel and use a different probe and cable. In some cases, probes
and cables that are far out of specification can be brought into specification by iterating the
custom calibration process several times.
4.2.1
CURRENT LOOP VERIFICATION (MX2034 ONLY)
Follow the steps in this section to verify the current loop output for Position or Radial Vibra-
tion configured DPS units.
4.2.1.1 POSITION CONFIGURED UNITS
The transmitter current output is linearly proportional to the average probe gap (position)
between 4 mA and 20 mA. Use the instruments and equipment shown in Figure 23 to verify
a position transmitter current output.
NOTE:
Metrix does not recommend using the custom
calibration feature to calibrate mismatched systems. Mis-
matched systems degrade probe and cable temperature
performance.