MI 3295 Step Contact Voltage Measuring System
Measurements
33
Connections for synchronization
For connection of the instruments see
Figure 7.18: Examples of synchronization screens
NOT SYNCHRONIZED: number of non-synchronized results.
Note
:
Synchronization of Step voltage, Contact /Touch voltage and Potential results can
last up to several 10 seconds. A bargraph is showing the progress (
)
7.3 Current measurement
Figure 7.19:
Current measurement screen
Test parameters for current measurement
Type
Current clamp type
(
A1018, A1587)
Mode
Test mode
(TRMS, 50 Hz, 55 Hz, 60 Hz
)
Rang
Range of A1587 clamp
(
30 A, 300 A, 3000 A)
Ilim
A1018
No limit, 10 mA … 9.0 A
A1587 (Range: 30 A)
No limit, 30 mA … 25.0 A
(Range: 300 A, 3000 A)
No limit, 30 mA … 45.0 A
Current measurement
Select
CURRENT
function.
Set test parameters / limits (optional).
Connect the current clamp to the instrument and to the test object.
Press the
TEST
key to start the continuous measurement.
Wait until the test result is displayed on the screen.
Press and hold the
TEST
key to stop the measurement.
Store the result by pressing the
MEM
key (optional).