MI 3101 EurotestAT: Appendix F
Country notes
119
pre-test in the measuring procedure also influences the RCD and it takes a period to
recover into idle state. Time delay of 30 s is inserted before performing trip-out test to
recover
S
type RCD after pretests and time delay of 5 s is inserted for the same purpose
for
G
type RCD.
Modification of the chapter 5.3.1
RCD type
Contact voltage Uc
proportional to
Rated I
N
AC
,
G
1.05
I
N
AC
S
2
1.05
I
N
any
A
,
G
1.4
1.05
I
N
A
S
2
1.4
1.05
I
N
30 mA
A
,
G
2
1.05
I
N
A
S
2
2
1.05
I
N
< 30 mA
B
2
1.05
I
N
B
S
2
2
1.05
I
N
any
Table F.1: Relationship between Uc and I
N
Technical specifications remain the same.
F.2.2
ES modification - CONTINUITY LOOP Re
The procedure is intended for measurement the resistance of PE wiring between
distribution board and individual wall sockets. This is autotest only accessible procedure
consisting of two special functions: the
LOOP Re
and the
CONTINUITY
with
LOOP Re
sub-function
.
Test parameters for LOOP Re function
This function does not have any parameters.
Test parameters for CONTINUITY LOOP Re function
TEST Test
sub-function
[
LOOP Re
, R200mA, R7mA].
With LOOP Re selected:
Fuse I
Rated
current
of the fuse for over-current protection of tested socket outlet.
Uc Conventional
touch
voltage
limit
[25 V, 50 V].
Limit
Calculated limit value for PE wiring resistance (Uc/I).
Re_DB
Resistance of PE wiring to distribution board (result of LOOP Re
measurement).