background image

10    Conventional Products—B110LP Plug-In Conventional Low Profile Detector Base

Note: Do not use the tamper-proof capability if the XR2 removal tool

will be used to remove detectors from the base.

This detector base can be made tamper-proof so that the detector cannot be
detached without the use of a tool.

To make the base tamper-proof before installing the detector:

1.

Break off the smaller tab at the scribed line on the tamper-proof tab on
the detector mounting bracket (Figure 4).

tmprprf

Plastic Lever

Break tab at

dotted line by

twisting toward

center of base.

Figure 4:  Enabling the Tamper-Proof Feature

To remove the detector from the base after it has been made tamper-proof:

1.

Remove the decorative ring by rotating it in either direction and
pulling it away from the base.

2.

Insert a small screwdriver into the notch (Figure 5).

3.

Press the plastic lever toward the mounting surface before rotating the
detector counterclockwise for removal.

remdetct

Use small-bladed

screwdriver to

push plastic lever

in direction of arrow.

Figure 5:  Removing the Detector Head from the Base

The tamper-proof feature may be defeated by breaking and removing
the plastic lever from the base.  However, this prevents using the
feature again.

Tamper-Proof
Feature

Содержание B110LP

Страница 1: ...chnical Bulletin Issue Date 1095 1995 Johnson Controls Inc 1 Code No LIT 408110 Introduction Page 3 General Description 4 Installation Procedures 5 General Information 5 Mounting 5 Wiring Installation Guidelines 7 Tamper Proof Feature 10 Limitations 11 B110LP Plug In Conventional Low Profile Detector Base ...

Страница 2: ...2 Conventional Products B110LP Plug In Conventional Low Profile Detector Base ...

Страница 3: ...e system s control panel installation manual the requirements of the authority having jurisdiction National Fire Protection Association NFPA Standards 72 National Fire Alarm Code System Sensor Guide for Proper Use of System Smoke Detectors Technical Bulletin in the Fire Initiating Devices and Notification Appliances Technical Manual FAN 408 that provides detailed information on detector spacing pl...

Страница 4: ...d RA400Z Remote annunciator for 2 or 4 wire systems 3 32V Fits standard single gang box XR2 Detector removal tool XP4 Extension pole for XR2 Three 5 foot sections Table 2 Specifications Summary Base Diameter 6 2 in 157 mm Base Height Front of Backbox to Front of Detector 0 95 in 24 mm Weight 0 3 lb 136 g Mounting 4 in Square Box with or without Plaster Ring 3 1 2 inch Octagon Box Minimum depth is ...

Страница 5: ... wires exposed The detector base mounts directly to 3 1 2 inch 88 9 mm and 4 inch 101 6 mm octagon boxes and 4 inch square boxes with or without plaster rings To mount the base 1 Remove the decorative ring by rotating it in either direction to unhook the snaps before separating the ring from the base 2 Use the screws supplied with the junction box to attach the base to the box through the appropri...

Страница 6: ...ional Products B110LP Plug In Conventional Low Profile Detector Base S nap on Decorative R ing S crew s Not S upplied Detector B ase Box Not S upplied m ntbase3 Shorting Jum per Figure 1 Mounting Detector to Box ...

Страница 7: ... and installed in a separate grounded conduit to protect the IDC from other types of circuits in the system Smoke detectors and alarm system control panels have specifications for the maximum allowable IDC resistance and supervision current Consult the control panel manufacturer s specifications for the total IDC resistance and supervisory current allowed The IDC zone wiring of the detector base s...

Страница 8: ...f the wire 2 Slide the bare end of the wire under the clamping plate 3 Tighten the clamping plate screw 4 Use the strip gauge molded into the base for ease of wiring to terminals The smoke detectors and mounting bases are marked with a compatibility identifier located as the last digit of a five digit code stamped on the back of the product Connect detectors mounting bases only to compatible contr...

Страница 9: ...ntact with the base of Terminal 3 This temporary connection shorts the negative in and negative out leads and permits the wiring of the IDC to be checked for continuity Once all the detector bases have been wired and mounted and the IDC wiring has been checked the detector heads may be installed in the bases The shorting spring in the base will disengage when the detector head is turned into place...

Страница 10: ...ted line by twisting toward center of base Figure 4 Enabling the Tamper Proof Feature To remove the detector from the base after it has been made tamper proof 1 Remove the decorative ring by rotating it in either direction and pulling it away from the base 2 Insert a small screwdriver into the notch Figure 5 3 Press the plastic lever toward the mounting surface before rotating the detector counter...

Страница 11: ...tecting fast flaming fires than slow smoldering fires Photoelectronic detectors sense smoldering fires better than flaming fires Because fires develop in different ways and are often unpredictable in their growth neither type of detector is always best and a given detector may not always provide warning of a fire In general detectors cannot be expected to provide warnings for fires resulting from ...

Страница 12: ...ts B110LP Plug In Conventional Low Profile Detector Base Notes Controls Group FAN 408 507 E Michigan Street Fire Initiating Devices and Notification Appliances Technical Manual P O Box 423 Printed in U S A Milwaukee WI 53201 ...