16 Conventional Products—6424 Projected Beam Type Smoke Detector
●
For information on the remote outputs for trouble and alarm, see
Figure 10.
●
For the connection necessary for using the remote test station
(RTS451) see Figure 11.
The test coil which is shipped with the RTS451 is not used on the
6424 beam smoke detector.
be am w ir2
A lar m
S ignal
P ower (+ )
P ower (-)
W h ite-G reen S tripe
W h ite-B rown S trip e
O range
T r ouble
S ign al
64 24 R emote O u tpu ts
Figure 10: Remote Annunciators
b e am w r2 a
A larm S ignal
A ux (-)
R eset
T es t
B lue
Yellow
O r an ge
W h ite-B rown S tripe
5
3
4
2
1
R T S 451
Rem ote T est S tation
6424
Figure 11: Remote Test Station
!
WARNING:
Shock hazard. Disconnect the power from the
Initiating Device Circuits (IDC) before installing
the detectors.
1.
Before operation, remove the clear protective film and warning label
on the smoked lens of both the receiver and transmitter.
2.
Do not remove the protective film until all construction in the area is
completed and all dust has been removed.
If construction occurs after the protective film is removed, the smoked
lens should be cleaned after construction is completed and the area
cleaned.
For instructions, read and be familiar with the Maintenance section of
this technical bulletin.
Installation