7 VG9H 70 en
51
15
TYPE CODING
*) Slash shall always be marked in places shown above.
NELES VALVGUARD VG9000
1.
2.
3.
4.
5.
6.
7.
8.
VG
9
2
15
H
E6
/
D33
1. sign
PRODUCT GROUP
VG
Neles ValvGuard VG9000, intelligent safety solenoid.
TÜV SIL 3 certified according to IEC 61508.
2. sign
SERIES CODE
9
Series 9000 intelligent safety solenoid with universal shaft and
attachment face according to standard VDI/VDE 3845. Relevant shaft
adapter included in mounting kits. When VG9000 is separate delivery,
shaft adapter kit needs to be ordered separately (see type coding for
accessories).
3. sign
ENCLOSURE
IP66 / NEMA 4X.
Standard temperature range -40° to +85 °C / -40° to +185 °F.
M20 x 1.5 conduit entry; 1 pcs (VG9_H), 2 pcs (VG9_F) in extension
housing.
2
Standard epoxy coated anodized aluminium enclosure.
3
Full 316 stainless steel enclosure, no glass window.
4. sign
SPOOL VALVE
CONNECTIONS
12
Restricted capacity
Stroke volume of actuator 0.3 - 6.7 dm
3
S, C1, C2 = 1/4 NPT
15
Standard capacity
Stroke volume of actuator > 0.6 dm
3
S, C1, C2 = 1/4 NPT
35
High capacity
Stroke volume of actuator > 3.5 dm
3
Not applicable to 3. sign "3"
S, C1, C2 = 1/2 NPT
37
Extended capacity, for single acting
actuators.
Stroke volume of actuator > 6.5 dm
3
Not applicable to 3. sign "3"
S = 1/2 NPT, C2 = 1 NPT
5. sign
COMMUNICATION / INPUT SIGNAL RANGE
H
4-20 mA, HART communication.
6. sign
APPROVALS FOR HAZARDOUS AREAS
X
ATEX and IECEx certifications:
ATEX and IECEx certifications:
II 1 G Ex ia IIC T6...T4 Ga
II 1 D Ex ia IIIC T95 °C...T125 °C Da
II 2 G Ex ib IIC T6...T4 Gb
II 2 D Ex ib IIIC T95 °C...T125 °C Db
Temperature range: T4 or T125 °C: < +80 °C; T5 or T110 °C:
< +65 °C; T6 or T95 °C: < +50 °C.
II 3 G Ex nA IIC T6...T4 Gc
II 3 G Ex ic IIC T6...T4 Gc
II 3 D Ex ic IIIC T95 °C...T125 °C Dc
Temperature range: T4 or T125 °C: < +85 °C;
T5 or T110 °C: < +75 °C; T6 or T95 °C: < +60 °C.
Available without limit switches or
with certified inductive limit switches.
U
cCSAus certification:
IS Class I, Division 1, Groups A, B, C, and D; T4/T5/T6
Ex ia IIC T4/T5/T6 Ga IS Class I, Zone 0 AEx ia IIC T4/T5/T6 Ga
Temperature range: T4: -40° to +80 °C; T5: ≤+65 °C; T6: ≤ +50 °C
1/2" NPT conduit entries. No glass window.
Z
INMETRO certification:
Ex ia IIC T6...T4 Ga
Ex ib IIC T6...T4 Gb
T4: -40° a +80 °C; T5: < +65 °C; T6: < +50 °C.
Ex ic nA IIC T6...T4 Gc
T4: -40° a +85 °C , T5: < +75 °C; T6: < +60 °C.
Available without limit switches or with ATEX or IECEx certified
inductive limit switches.
6. sign
APPROVALS FOR HAZARDOUS AREAS
E2
cCSAus certification:
Class I, Div 1, Groups B, C, D; Class II, Div 1, Groups E, F, G; Class III; T6...T4,
Enclosure type 4X
Ex d IIC T6...T4
AEx d IIC T6...T4
Ex tb IIIC T100 °C IP66
AEx tb IIIC T100 °C IP66
T4: -40° to +85 °C; T5: <+75 °C; T6: <+60 °C.
Available with or without limit switches.
1/2" NPT conduit entries. No glass window.
E5
INMETRO certification:
Ex d IIC T5 Gb (-40°C or -25 °C Ta +85 °C)
Ex d IIC T6 Gb (-40°C or -25 °C Ta +70 °C)
Available with or without limit switches.
E6
ATEX and IECEx certifications:
II 2 GD
Ex d IIC T6...T4 Gb
Ex tb IIIC T80 °C...T105 °C Db IP66
Temperature range: a separate table
Available with or without limit switches
E7
ATEX and IECEx
certifications with Russian machine plate:
II 2 GD
Ex d IIC T6...T4 Gb
Ex tb IIIC T80 °C...T105 °C Db IP66
Temperature range: a separate table
Available with or without limit switches
7. sign
OPTIONS
Several options can be selected, but the order shown below needs to
be maintained.
T
Internal 2-wire (passive) position transmitter output.
Analog position feedback signal, output 4-20 mA, supply voltage 12 -
30 VDC, external load resistance 0 – 780 Ω.
Not applicable to 5. sign "F" or 7. sign "S".
NOTE: This option is not SIL certified. For SIL certified PT option use 8.
sign "T01"
S
Internal 2-wire (passive) device status output.
Analog device status feedback signal, output 4-20 mA.
Output mA value is based on the device status, supply voltage 12 -
30 VDC, external load resistance 0 – 780 Ω.
Not applicable to 5. sign "F" or 7. sign "T".
NOTE: This option is not SIL certified.
P
For partial stroke test (PST) only. To be used together with additional
solenoid valve for safety action. 4 mA normal state, signal failure does
not affect to the valve position.
Applicable to 5. sign "H" and 6. sign "X", U, "E6" or "E7"(other approvals
pending).
Not applicable to 7. sign "S". NOTE: SIL certification pending.
J
External junction box, 2 pcs M20x1.5 conduit entries.
VG9_H_J_:
Junction box for all 4-20 mA wirings, including position transmitter, if
applicable. Junction box is attached to the standard enclosure.
Not applicable to 7. sign "L1"
NOTE:
This option should be selected if both 7. sign "L2" (for Local
Control Panel LCP9H_) and 8. sign (limit switches) are specified.
VG9_F_J_:
Junction box for FF and 24 VDC wiring. Junction box is attached to the
standard enclosure. If limit switches (8. sign) are not specified,
extension housing is excluded.
L1
Extension housing with additional conduit entries, 2 pcs M20x1.5.
Applicable to 5. sign "H" and 7. sign "T" or "S", if additional conduit entry
is required.
Not applicable to 7. sign "J" or "L2" or limit switches (8.sign).
L2
Extension housing with additional conduit entries and terminal strip for
externally 24 VDC powered Local Control Panel (LCP9H_), 4 pcs
M20x1.5.
Applicable to 5. sign "H". Not applicable to 7. sign "L1" or "L3".
NOTE:
7. sign "J" should be selected, if 8. sign (limit switches) is
specified.
NOTE:
Local Control Panel LCP9H_ needs to be ordered separately!
L3
Extension housing with additional conduit entries and terminal strip for
loop powered Local Control Panel (LCP9H_L), 4 pcs M20x1.5.
Applicable to 5. sign "H". Not applicable to 7. sign "L1 or L2".
NOTE:
: 7. sign "J" should be selected, if 8. sign (limit switches) is
specified.
NOTE:
: Local Control Panel LCP9H_L need to be ordered separately!
Y
Special construction, to be specified.