background image

34

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

K. Fan will not stop.

1.  Control Board is in flame failure mode.

2.  Fan improperly wired.

3.  Defective board.

4.  Defective fan relay.

5.  High limit trip.

1.  Turn 115V power off to the unit, wait 10 seconds and 

reapply voltage to the unit.

2.  Check wiring of fan circuit to wiring diagram.

3.  If unit is not calling for heat and board is not in a flash code 

mode, replace board. 

4.  Check for 0 volts on terminals 24 and 0. Check for 0 on 

normally open relay contact when calling.

5.  See High Limit Tripping in troubleshooting section.

L. Not enough heat.

1.  Incorrect gas input.

2.  Heater undersized.

3.  Thermostat malfunction.

4.  Heater cycling on limit.

5.  Incorrect orifice size. 

1.  Refer to OPERATION.

2.  Is the heater output sized correctly for heat loss of the 

space. Has the space been enlarged.

3.  Check thermostat circuit, 24V on terminals “R” and “W” on 

terminal strip.

4.  Check air movement across heat exchanger. Check 

voltage and amps at the fan motor. Check gas input to 

ensure unit is not over fired. Check heat exchanger to 

ensure unit is not dirty.

5.  Check orifice size, replace if undersized.

M. Too much heat.

1.  Unit is over fired.

2.  Thermostat malfunction.

3.  Heater runs continuously.

4.  Control board configured for incorrect size.

1.  Refer to OPERATION. Check orifice size. If too big replace.

2.  Check thermostat for operation, to ensure circuit open and 

closes.

3.  Check wiring per diagram; check operation at the gas 

valve, look for a short in thermostat circuit.

4.  Check control board dip switch configuration.

N. Cold air is delivered 

during heater operation.

1.  Incorrect gas input.

2.  Air throughput too high.

1.  Refer to OPERATION.

2.  Refer to OPERATION.

O. High limit tripping.

1.  Unit is over fired.

2.  Air flow is low.

3.  Defective switch.

4.  Defective control board.

1.  Burner orifices may be too large, verify and replace.

2.  Check for proper voltage, ensure fan blade is correct and 

free of debris.

3.  Check operation of switch, did the switch open when unit is 

running or is the switch open during start-up.

4.  Check for 24V on line side of the high limit. Constant 

voltage should be recorded if not control board is suspect. 

Check flash code.

P. Power venter will not 

run.

1.  Loose wiring or connections.

2.  Motor overload is tripped or bad motor.

3.  Bad control board.

1.  Check all wring in the power vent circuit to ensure good 

connection, including “Neutral”.

2.  Check for 115V between motor leads and check amp draw 

of motor. Replace if needed.

3.  Check for continuous 115V on molex plug on inducer and 

neutral during call for heat. If not present and all checks 

are normal, replace.

Q. Power venter turns 

on and off during 

operation.

1.  Power venter improperly wired.

2.  Motor overload cycling or defective motor.

3.  Defective control board. 

4.  Unit not reaching proper delta pressure.

1.  Check power venter circuit per wiring diagram.

2.  Check motor voltage and amp draw to motor name plate, 

replace if motor found defective.

3.  Check for continuous 115V on terminal molex plug during 

call for heat, replace board if found defective.

4.  Check pneumatic tubing and vent pipe for blockages. 

Check condensate trap for proper seal.

R. Power venter will not 

stop.

1.  Power venter improperly wired.

2.  Main burner did not light on call for heat.

3.  Defective control board.

1.  Check power venter circuit per wiring diagram.

2.  Heater is in lockout mode check flash code table for problem.

3.  No flash codes present along with no call for heat, replace 

control board.

S. Combustion Blower will 

not run.

1.  Loose wiring or connections.

2.  Motor overload is tripped or bad motor.

3.  Defective control board.

1.  Check all wring in the power vent circuit to ensure good 

connection, including “Neutral”.

2.  Check for 115V between motor leads and check amp draw 

of motor. Replace if needed.

3.  Check for continuous 115V between black and white 

wires on molex plug and neutral during call for heat. If not 

present and all checks are normal, replace.

T. Combustion Blower 

turns on and off during 

operation.

1.  Combustion Blower improperly wired.

2.  Motor overload cycling or defective motor.

3.  Defective control board.

1.  Check Combustion Blower circuit per wiring diagram.

2.  Check motor voltage and amp draw to motor name plate, 

replace if motor found defective.

3.  Check for continuous 115V between black and white wires 

on molex plug of combustion blower during call for heat, 

replace board if found defective.

U. Combustion Blower will 

not stop.

1.  Combustion Blower improperly wired.

2.  Main burner did not light on call for heat.

3.  Defective control board.

1.  Check Combustion Blower circuit per wiring diagram.

2.  Heater is in lockout mode check flash code table for problem.

3.  No flash codes present along with no call for heat, replace 

control board.

V. Flue Temperature 

Switch tripping.

1.  Unit over fired.

2.  Blocked heat exchanger

3.  Blocked combustion air or flue vent pipe.

4.  Clogged heat exchanger coil.

1.  Refer to operation section.

2.  Clean heat exchanger/flue collector.

3.  Clean combustion air or flue vent pipe.

4.  Clean heat exchanger coil fins. 

Содержание NXIM-2

Страница 1: ...r s responsibility to inspect and correct any problem that may be found RECEIVING INSTRUCTIONS Inspect shipment immediately when received to determine if any damage has occurred to the unit during shi...

Страница 2: ...ffolding or other apparatus required to perform emergency service or annual periodic maintenance to this equipment DESCRIPTION The High Efficiency Gas Fired Unit Heaters are factory assembled power ve...

Страница 3: ...cated in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice versa will create risk of gas leaks carbon monoxide...

Страница 4: ...4 Figure 2 Dimensional Drawing High Efficiency Unit Heater CAT 10081B T CONNECTION CONNECTION FLUE P B H C A G J L K D E W U N SPECIFICATIONS...

Страница 5: ...n Dia 2 3 4 4 51 76 102 102 P Flue Connection Diameter 2 2 4 4 51 51 102 102 Q Side Panel to Centerline Gas Connection 2 5 8 2 5 8 2 5 8 2 5 8 67 67 67 67 R Bottom Panel to Centerline Gas Connection 2...

Страница 6: ...tat setting must be maintained If the ambient temperature drops to below freezing it may result in damage to heat exchanger and or components AIR FOR COMBUSTION The unit heater shall be installed in a...

Страница 7: ...cal conduit for support Failure to heed these warnings may result in property damage personal injury or death Unit Heaters must be hung level from side to side and from front to back Failure to do so...

Страница 8: ...5A THREADED INSERT LAG BOLT WASHER 3 8 THREADED ROD 2 X 6 LAG BOLTED ACROSS JOISTS JOIST WASHER NUT 22 216758 7 21 2 676 FRONT OF UNIT HEATER 300 400 SIZES CAT 10165A LAG BOLT WASHER 1 2 THREADED ROD...

Страница 9: ...3 1 05 0 99 3 4 0 824 360 250 200 170 151 138 125 118 110 103 93 84 77 72 10 2 7 08 5 66 4 81 4 28 3 91 3 54 3 34 3 11 2 92 2 63 2 38 2 18 2 04 1 1 049 680 465 375 320 285 260 240 220 205 195 175 160...

Страница 10: ...gas manifold and controls Supports should be spaced in accordance with the latest edition of ANSI Standard Z223 1 NFPA 54 National Fuel Gas Code in Canada according to CSA B149 4 To prevent the mixing...

Страница 11: ...National Electrical Code ANSI NFPA No 70 or CSA Standard C22 1 THERMOSTAT WIRING AND LOCATION NOTICE The thermostat must be mounted on a vertical vibration free surface free from air currents and in a...

Страница 12: ...12 ELECTRICAL CONNECTIONS continued Figure 7A Unit Wiring Diagram High Efficiency Unit Heater Size 100 Equipped with Natural or Propane LP Gas Modulating with Outside Air Reset Master...

Страница 13: ...13 ELECTRICAL CONNECTIONS continued Figure 7B Unit Wiring Diagram High Efficiency Unit Heater Size 200 Equipped with Natural or Propane LP Gas Modulating with Outside Air Reset Master...

Страница 14: ...14 ELECTRICAL CONNECTIONS continued Figure 7C Unit Wiring Diagram High Efficiency Unit Heater Size 300 400 Equipped with Natural or Propane LP Gas Modulating with Outside Air Reset Master...

Страница 15: ...des with current CSA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CSA B149 2 Installation Codes for Propane Gas Burning Appliances and Equipment 2 Any reference to U S...

Страница 16: ...5 2 m Equivalent length is total length of straight sections PLUS 5 feet 1 5 m for each 90 degree elbow and 2 5 feet 0 76 m for each 45 degree elbow 4 The vent terminal must be at least 12 inches 305...

Страница 17: ...ar attach in place if not already factory mounted to outlet 3 The top of the vent pipe should extend at least 2 feet 0 61 m above the highest point on the roof within 10 feet 3 05 m of the termination...

Страница 18: ...within the building on high efficiency unit heaters This can result in death serious injury or substantial property damage Use of cellular core pipe for any exhaust vent component is prohibited Use o...

Страница 19: ...mm 24 610 mm MINIMUM FROM ADJACENT WALL OR BUILDING TO COMBUSTION 8 MINIMUM 204 mm CAT 10075A FLUE PIPE COMBUSTION AIR INLET PIPE FLUE PIPE COMBUSTION AIR INLET PIPE ROOF FLASHING REQUIRED AT ALL PENE...

Страница 20: ...es 12 inches 305 mm is the minimum allowable length and 60 inches 1 5 m is the maximum allowable length for this dimension Only SDR 26 PVC ASTM D2241 may be used for extendingpipes Donotextendpipeswit...

Страница 21: ...t 10 Check installation by allowing unit to run through one cycle Figure 14 Horizontal Concentric Vent Kit Installation SEPARATED COMBUSTION CONCENTRIC VENTING continued MAX 60 1524 mm 1 25 mm COMBUST...

Страница 22: ...e to roof using metal strapping or equivalent support material field supplied refer to Figure 18 7 Install combustion air inlet cap and small diameter pipe assembly into roof Cement and fully insert s...

Страница 23: ...remove the 6 screws that attach the mixing chamber to the combustion blower 9 Place mixing chamber on flat surface and unthread the 90 degree elbow from orifice nipple Then unthread the orifice nipple...

Страница 24: ...Figure 21A Gas Valve Adjustment Locations Sizes 100 200 Figure 21B Gas Valve Adjustment Location Sizes 300 400 Run Potentiometer High Fire Adjustment Low Fire Adjustment Figure 21C Run Potentiometer...

Страница 25: ...as Propane LP Gas to Natural Gas 100 1 3 4 CW 1 3 4 CCW 200 2 1 2 CW 2 1 2 CCW 300 2 1 2 CCW 2 1 2 CW 400 4 CCW 4 CW Note CW indicates clockwise rotation and CCW indicates counterclockwise rotation Un...

Страница 26: ...stat will determine how the unit runs A Fan Only G demand will cause the unit run its propeller fan only A first stage demand W1 will cause the unit to run at the minimum input set by the Run potentio...

Страница 27: ...ch and Master DIP Switch must be ON for the Master OPERATION HIGH EFFICIENCY PROPELLER UNITS DIRECT SPARK IGNITION continued The OADIP Switch must be ON for all Members All units must be connected usi...

Страница 28: ...ter The GLOBAL DIP Switch must be set to ON for Members Each Member uses its own RUN potentiometer Run for the lowest input level All units must be connected using the Network communication ports Note...

Страница 29: ...MS using the RS485 Modbus Port The MASTER Switch must be ON for the Master The GLOBAL DIP Switch must be set to ON for Members Each Member uses its own RUN potentiometer P1 for the lowest input level...

Страница 30: ...t this ignition period for one minute The orange ignition LED will become solid OPERATION HIGH EFFICIENCY PROPELLER UNITS DIRECT SPARK IGNITION continued 6 Set Run potentiometerto100 onthecontrolboard...

Страница 31: ...UDE DERATION This high efficiency unit heater has been manufactured utilizing standard burner orifices and gas pressure setting as per the specifications shown on the unit rating plate The main contro...

Страница 32: ...H PRESSURE TAP 1 8 TUBING TO BULK HEAD FITTING ON FLUE COLLECTOR 1 8 TUBING TO BULK HEAD FITTING ON PARTION PANEL 1 8 TUBING TO GAS VALVE PRESSURE TAP ON SIZE 100 200 UNITS CONNECTION IS CAPPED ON SIZ...

Страница 33: ...for 24V at gas valve terminals during trial for ignition period if present and valve does not open Replace valve 9 Clean condensate trap 10 Replace ignition control 11 Re install cap on tubing F Burn...

Страница 34: ...eads and check amp draw of motor Replace if needed 3 Check for continuous 115V on molex plug on inducer and neutral during call for heat If not present and all checks are normal replace Q Power venter...

Страница 35: ...ulty switch 4 Power venter is not working properly or producing correct delta pressure Red LED 3 Flash High Limit Switch Fault 1 Gas supply off or gas supply pressure too high 2 Unit is over fired 3 B...

Страница 36: ...of the automatic gas valve by lowering the setting of the thermostat stopping the operation of the unit The gas valve should close tightly completely extinguishing the flame on the burners 9 Inspect...

Страница 37: ...halogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 This limited warranty is conditional upon a advising the installing contractor who in turn noti...

Страница 38: ...KET DRAFTER MOUNTING PLATE SELF DRILL SCREW 8 18 INDUCER THREADED HEX INSERT 10 24 FLUE COLLECTOR ASSEMBLY DRAFTER GASKET CAT 10085A MACHINE SCREW 10 24 MACHINE SCREW 6 32 AIR GAS INLET COVER PLATE IN...

Страница 39: ...istance is needed contact the manufacturer s customer service department Unit Number Serial Number Part Description and Number as shown in Replacement parts Catalog TURBULATOR COMBUSTION TUBE COMBUSTI...

Страница 40: ...W2 40005 Modbus Input 8 bit unsigned 1 0 Modbus Input see BMSTimer If no wired operating mode demands are present and the unit is operating per the Modbus Mode variable the unit will run at this inpu...

Страница 41: ...Air Rest Limit 33 100 30011 Fault Code 8 bit unsigned Indicates the highest priority Fault set on the unit See the Fault Code Table 30012 Inducer Blower RPM 16 bit unsigned 1 0 Current RPMs of the in...

Страница 42: ...V 1 115 1 60 5 230 3 60 2 208 1 60 6 460 3 60 3 230 1 60 7 575 3 60 4 208 3 60 Z Special Note Supply Voltages SV 2 7 include field mounted step down transformer 12 Motor Type MT 1 Open Drip Proof 13 B...

Страница 43: ...you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP AND INSPECTION SHEE...

Страница 44: ...260 NORTH ELM ST WESTFIELD MA 01085 TEL 413 564 5540 FAX 413 562 5311 www mestek com...

Отзывы: