Masterpact ® circuit breaker
accessories
secondary disconnects
Electrical accessories are UL Listed for field
installation per UL file E1 1 3554.
They are provided with terminals. They are
located on secondary disconnecting blocks
above the circuit breaker.
•
fixed-mounted:
By one or two connecting plugs (provided).
M P 1 035P.O
•
drawout-mounted:
To a terminal block
a
located in the front of
the stationary assembly making the
connections easy.
This terminal block is then wired to another
connection block
b
that operates
automatically to isolate the internal
accessories when the circuit breaker is in
the disconnected position.
location
disconnected
position
switches
terminal
connection:
Accessory terminals are of screwless type
(maintenance-free) and may be connected
by standard copper wires # 1 8 to # 1 4 AWG.
Cable strip length: 3/8 in. ( 1 0 mm)
secondary disconnects
spring
charging
motor
M P 1 034A.O
additional connections (BS):
Single connection only is allowed in the
terminal block.
Multiple connections have to be made by
adding extra terminals in the block located
on the stationary assembly.
BS option consists of five additional
terminals.