Masterpact™ MP switch
construction
MasterpactTM switch is designed identically to
M P circuit breaker, except that it is not
equipped with a control unit.
Caution :
switch does not provide overcurrent
protection.
Switch can be protected by a MasterpactTM
circuit breaker.
<D
control un� not required
® not UL listed
MERLIN GERIN
CD
type
ampere
3-pole
rating (A)
MP OSNA 800
MP 1 2NA 1 200
MP 1 6NA 1 600
MP 20NA
2000
MP 25NA 2500
MP 30NA
3000
MP 40NA<2l 4000
MP 50NA®
5000
MP 63NA®
6300
short time rating
(RMS Sym. Amps)
SOOV AC max.
50 000
50,000
50,000
50,000
50,000
50 000
85,000
85,000
85,000
accessories - dimensions -
connections
Switch accessories, dimensions and
connection are identical
to
those of the
corresponding circuit breaker. Overcurrent
trip switch is not available with switch
version.
page
accessories
1 2
wiring diagrams
28
dimensions
30
short circuit withstand when protected
by Maaterpactm circuit breaker (A)
max.
frame
SOOV AC max.
800
50.000
1 200
50.000
1 600
50.000
2000
50.000
2500
50.000
3000
50.000
4000
85.000
5000
85.000
6300
85.000
35
www
. ElectricalPartManuals