Mercury SR-10K Скачать руководство пользователя страница 8

Doc. 10107-0007  Rev 1.04

Page 8

Mercury Security Corporation, 

©

 2005

SR-10K

Command 33 - Set the Auxiliary Relay Pulse Time (Output K2)

* 3 3

- select Command 33

0-9

0-9

- select the pulse time for Output K2: 00 to 99 seconds (+1/2 second)

Configuration Settings 

(Commands 31through 34)

Command 32 - Set the Door Strike Relay Pulse Time (Output K1)

* 3 2

- select Command 32

0-9

0-9

- select the strike pulse time: 00 to 99 seconds (+1/2 second)

Command 34 - Set the Auxiliary Relay's Pulse Time (Output K2)

* 3 4

- select Command 34

1 or 2

- select the pulse type: 1 for normal, 2 for intermittent output

Configuration and Database Copy Commands 

(Commands 41through 44)

The following commands allow the configuration and database to be copied from one SR-10K to
another SR-10K. These commands transfer the selected database elements from the SR-10K where
the command is being entered to the SR-10K whose address is specified in the command.

The SR-10K addresses are set by installing the jumper pattern for the desired address on the Inter-
face Module as shown on the installation diagram.

The color of the upper LED is set to flashing amber for the duration of the the data transfer. Periodic
short beeps are used by longer transfers to indicate "transfer in progress". The transfer of the entire
"block mode" card database (1,600 users) may take up to 1 minute.

The completion of a succesful transfer is indicated with the "long-beep". A transfer error condition is
signalled with three short beeps along with a red flash on the upper LED. A transfer error is caused
by either incorrect  wiring, or by incorrect jumper settings. Notice: the transfer commands are not
'broadcast'; each SR10K must be set to a unique address 0 to 15.

Command 42 - Copy the Cipher Database only

* 4 2

- select Command 42 - copies cipher users 0 through 9

0-9

0-9

- select the address of the SR-10K to copy the data to - 00 to 15

Command 43 - Copy the Card Database only

* 4 3

- select Command 43 - copies users 00 through 99, or through 1599

0-9

0-9

- select the address of the SR-10K to copy the data to - 00 to 15

Command 44 - Copy ALL: Configuration Settings, Card and Cipher databases

* 4 4

- select Command 44 - combines Commands 41, 42, and 43

0-9

0-9

- select the address of the SR-10K to copy the data to - 00 to 15

Command 41 - Copy the Configuration settings only 

- no card or cipher databases

* 4 1

- select Command 41 (copies seetings enterd with commands 31-34, and 91-95)

0-9

0-9

- select the address of the SR-10K to copy the data to - 00 to 15

Command 31 - Set the Door Held Open Time

* 3 1

- select Command 31 (from door opening to held open alarm)

0-9

0-9

- select the held open time: 00 to 99 seconds

Содержание SR-10K

Страница 1: ...Doc 10107 0007 Rev 1 04 Page 1 Mercury Security Corporation 2005 SR 10K SR 10K Mag Stripe Access System Users Guide...

Страница 2: ...ode 6 Two Door Access Control 14 Mode 7 Access Control with Door Bell Feature 15 Mode 8 Dual Output Toggle on Valid Access 15 Installation 16 Maintenance 17 Specifications 17 Dimensions and Typical Co...

Страница 3: ...p to 100 users factory default This mode allows the use of any magnetic stripe card with standard track 2 encod ing such as the MS SR10CC25 pre encoded packs of 25 cards or cards from many other acces...

Страница 4: ...isplay the status of an exter nal device connected to an input such as an alarm panel s armed disarmed indicator An Operating Mode is a collection of these functions intended for a specific applicatio...

Страница 5: ...etermines the installation wiring details and User Level assignment Lost Master Card Follow the steps outlined below to set a new Master Card in case the current Master Card is lost remove power from...

Страница 6: ...on Command 12 Delete a card using the card 1 2 select Command 12 user card read the card to be deleted from that slot Command 13 Delete a range of cards 1 3 select Command 13 0 9 0 9 select the first...

Страница 7: ...mmand 22 1 3 select the user level 1 3 0 1 0 9 0 9 0 9 enter the first user slot to activate 0000 through 1599 0 1 0 9 0 9 0 9 enter the last user slot to activate 0000 through 1599 Command 23 Delete...

Страница 8: ...s to indicate transfer in progress The transfer of the entire block mode card database 1 600 users may take up to 1 minute The completion of a succesful transfer is indicated with the long beep A tran...

Страница 9: ...with the Block Database Mode 4 The Block Number Command 94 must be set for Block Database Mode operation 5 In Facility Code Database Mode the digit count specifies the the number of card digits to rea...

Страница 10: ...rd read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configuration Inputassignments Input I1 is connected to a...

Страница 11: ...the status of Input I2 User Level 2 and 3 A downward read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configur...

Страница 12: ...rd pulses Output K2 allowing the momentary closure to simulate a key switch input to an alarm panel User Level Specifications User Level 1 Both downward and upward read will pulse Output K1 User Level...

Страница 13: ...etosimulate a key switch input to an alarm panel User Level Specifications UserLevel1 CardshavingthisUserLevelarerejectedifthecontactonInputI2isopen IfthecontactonInput I2 is closed Both downward and...

Страница 14: ...t to Output K2 and functions as the access control input User Level 1 users are valid only when a closed contact is presented to this input UpperLEDassignment The upper LED follows Input I2 displaying...

Страница 15: ...th Door Buzzer Control Description This mode is intended for applications where the outputs need to be toggled instead of the standard momentary pulse operation Both outputs are toggled Level 1 users...

Страница 16: ...l off moisture for outdoor mounting To avoid having ESD electrostatic discharge interfering with the operation of the reader the reader casing shall be grounded This can be accomplished be tying the m...

Страница 17: ...g nominal Interface Dimension 3 25 83mm W x 2 9 74mm L x 1 4 36mm H Weight 4 oz 120 g nominal Environmental Temperature 55 to 85 degrees C storage 40 to 75 degrees C operating Humidity Reader 100 RHN...

Страница 18: ...ss over cable Maximum distance between reader and interface is 500 feet using 22AWG wires 6 COND STRAIGHT Typical Wiring Configuration Communication Wiring Maximum total cable length 4 000 ft 1 200 m...

Страница 19: ...nap track The new module dimension is 4 25 x 2 75 inches Connection to the card reader is also changed from modular jack to a screw terminals for more convenient termination GND BLK BZR ORG LED BRN CL...

Отзывы: