Doc. 10107-0007 Rev 1.04
Page 12
Mercury Security Corporation,
©
2005
SR-10K
Operating Mode 03:
Access Control and Alarm Panel Control
Description
The Access Control and Alarm Panel Control configuration provides for basic access
control and gives some users the ability to send a pulse to arm and disarm alarm panels.
Both a downward and an upward read of all User Cards pulse Output K1, the strike control
relay, to allow entry. In addition, the upward read of a Level 2 card pulses Output K2,
allowing the
momentary closure to simulate a key-switch input
to an alarm panel.
User Level Specifications
User Level 1
•
Both downward and upward read will pulse Output K1.
User Level 2 (and 3)
•
A downward read will pulse Output K1
•
An upward read will pulse both Output K1 and Output K2.
Configuration
Input assignments:
•
Input I1 is connected to the armed/disarmed status output from the alarm panel.
•
Input I2 is connected to a “request to exit” button. Closing the contact initiates the
request.
Upper LED assignment:
•
The upper LED follows Input I1, displaying the status of the alarm panel:
•
Open Contact is displayed as RED
•
Closed Contact is displayed as GREEN