Mercury SR-10K Скачать руководство пользователя страница 11

Doc. 10107-0007  Rev 1.04

Page 11

Mercury Security Corporation, 

©

 2005

SR-10K

Description

Restricted Access Control with Door Monitoring restricts Level 1 user access based on the
status of Input I2 and provides door use annunciation on Output K2.

Level 1 cards are accepted only if the Input I2 sees a closed contact. Level 2 or 3 cards are not
dependent on Input I2.

A downward read of all valid User Cards pulse Output K1, the strike control relay.

The upward read of a Level 2 card toggles the strike control relay, K1, in effect performing a
lock/unlock function. The  upward read of a Level 1 card will release an unlocked condi-
tion.

Output K2 is pulsed to annunciate improper door use, such as
a)  Forced Open condition, which occurs if the door opening was not preceded by the use

of a valid card or an exit request, or

b) Held Open condition, which occurs if the door is kept open longer than the preset open

time.

User Level Specifications

User Level 1

A downward read will pulse Output K1 only if Input I2 is closed.

A upward read ends an unlocked condition, regardless of the status of Input I2.

User Level 2 (and 3)

A downward read will pulse Output K1 (no effect if the door is unlocked).

A upward read will toggle the state of Output K1, locking or unlocking the door.

Configuration

Input assignments:

Input I1 is connected to a door contact: closed contact signifies a closed door

Input I2 is connected to the access control control contact, such as an external timer. User
Level 1 cards are accepted only when a closed contact is presented to this input.

Upper LED assignment:

The upper LED follows Input I2, the Access Control Input:

 Open Contact is displayed as RED

 Closed Contact is displayed as GREEN.

Notes

This mode is very similar to Operating Mode 1. The same caution should be observed
regarding the ability to permanently unlock the door:

The 10 cards included in the original shipment are enrolled as Level 1 users. Be aware,
that if they are modified or any subsequent cards are added as 

Level 2 users, an up-

ward read will unlock the door

 - requiring another upward read (by any user Level) to

release the locked condition. Add Level 2 users only if the lock/unlock function is desired.

Consider using Operating Mode 4 or 5 if restricted access is required, but the
unlock function is not.

Operating Mode 02:

Restricted Access Control with Door Monitoring

Содержание SR-10K

Страница 1: ...Doc 10107 0007 Rev 1 04 Page 1 Mercury Security Corporation 2005 SR 10K SR 10K Mag Stripe Access System Users Guide...

Страница 2: ...ode 6 Two Door Access Control 14 Mode 7 Access Control with Door Bell Feature 15 Mode 8 Dual Output Toggle on Valid Access 15 Installation 16 Maintenance 17 Specifications 17 Dimensions and Typical Co...

Страница 3: ...p to 100 users factory default This mode allows the use of any magnetic stripe card with standard track 2 encod ing such as the MS SR10CC25 pre encoded packs of 25 cards or cards from many other acces...

Страница 4: ...isplay the status of an exter nal device connected to an input such as an alarm panel s armed disarmed indicator An Operating Mode is a collection of these functions intended for a specific applicatio...

Страница 5: ...etermines the installation wiring details and User Level assignment Lost Master Card Follow the steps outlined below to set a new Master Card in case the current Master Card is lost remove power from...

Страница 6: ...on Command 12 Delete a card using the card 1 2 select Command 12 user card read the card to be deleted from that slot Command 13 Delete a range of cards 1 3 select Command 13 0 9 0 9 select the first...

Страница 7: ...mmand 22 1 3 select the user level 1 3 0 1 0 9 0 9 0 9 enter the first user slot to activate 0000 through 1599 0 1 0 9 0 9 0 9 enter the last user slot to activate 0000 through 1599 Command 23 Delete...

Страница 8: ...s to indicate transfer in progress The transfer of the entire block mode card database 1 600 users may take up to 1 minute The completion of a succesful transfer is indicated with the long beep A tran...

Страница 9: ...with the Block Database Mode 4 The Block Number Command 94 must be set for Block Database Mode operation 5 In Facility Code Database Mode the digit count specifies the the number of card digits to rea...

Страница 10: ...rd read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configuration Inputassignments Input I1 is connected to a...

Страница 11: ...the status of Input I2 User Level 2 and 3 A downward read will pulse Output K1 no effect if the door is unlocked A upward read will toggle the state of Output K1 locking or unlocking the door Configur...

Страница 12: ...rd pulses Output K2 allowing the momentary closure to simulate a key switch input to an alarm panel User Level Specifications User Level 1 Both downward and upward read will pulse Output K1 User Level...

Страница 13: ...etosimulate a key switch input to an alarm panel User Level Specifications UserLevel1 CardshavingthisUserLevelarerejectedifthecontactonInputI2isopen IfthecontactonInput I2 is closed Both downward and...

Страница 14: ...t to Output K2 and functions as the access control input User Level 1 users are valid only when a closed contact is presented to this input UpperLEDassignment The upper LED follows Input I2 displaying...

Страница 15: ...th Door Buzzer Control Description This mode is intended for applications where the outputs need to be toggled instead of the standard momentary pulse operation Both outputs are toggled Level 1 users...

Страница 16: ...l off moisture for outdoor mounting To avoid having ESD electrostatic discharge interfering with the operation of the reader the reader casing shall be grounded This can be accomplished be tying the m...

Страница 17: ...g nominal Interface Dimension 3 25 83mm W x 2 9 74mm L x 1 4 36mm H Weight 4 oz 120 g nominal Environmental Temperature 55 to 85 degrees C storage 40 to 75 degrees C operating Humidity Reader 100 RHN...

Страница 18: ...ss over cable Maximum distance between reader and interface is 500 feet using 22AWG wires 6 COND STRAIGHT Typical Wiring Configuration Communication Wiring Maximum total cable length 4 000 ft 1 200 m...

Страница 19: ...nap track The new module dimension is 4 25 x 2 75 inches Connection to the card reader is also changed from modular jack to a screw terminals for more convenient termination GND BLK BZR ORG LED BRN CL...

Отзывы: