MR51e 

DOC  10107-0035  

REV 1.06 

 Page   3 

3.  DIP Switches: 

The addressing mode used is determined by the DIP switch setting on the MR51e: 

Addressing Mode Meaning 

OFF  OFF  OFF  OFF  MSC-Specific DHCP (original method) 

OFF  OFF  OFF  ON 

Public DHCP 

OFF  OFF  ON 

OFF  Static IP 

OFF  OFF  ON 

ON 

Programming Mode for Static IP Address Assignment 

ON 

ON 

ON 

ON 

MSC-Specific DHCP (original method) 

Notes: 

 

Public DHCP and Static IP Addressing Modes are available with MR51e firmware 
revisions 1_4_2 and later 

  All other DIP switch settings are reserved for future use 

  Press S2 to reset board after DIP switch is changed for new address mode 

4.  Input Power:  

The MR51e is powered by one of two ways (jumper selected, J5): 

  Power is supplied via the Ethernet connection using PoE, fully compliant to IEEE 802.3af  

  Or local 12 Vdc power supply, TB5-3 (VIN), TB5-4 (GND). 

5.  Communication Wiring: 

Communication  between  the  EP  controller  and  the  MR51e  is  Ethernet  (10Base  T/100Base-TX).  
It is not recommended to connect the MR51e to a public intranet. 

6.  Reader Wiring: 

 

Reader port 1 supports TTL (D1/D0, Clock/Data), F/2F, or 2-wire RS-485 device signaling.  Reader port 
2 supports TTL (D1/D0, Clock/Data), or F/2F signaling.  Power to reader port 1 is 12 Vdc at 180 mA 
maximum.  Reader port 2 may be powered from the auxiliary power supply output; TB5-1 and TB5-2.  
Readers that require different voltage or have high current requirements must be powered separately.  
Refer to the reader manufacture specifications for cabling requirements.  In the 2-wire LED mode, the 
buzzer output is used to drive the second LED.  Reader port configuration is set via the host software.  

 

When powering any remote device(s) by the MR51e, care must be taken not to exceed the maximum 
current available.  Cable gauge must also be evaluated.  See specifications section for details. 

 

 

 

Reader Port 1 

Typical D1/D0 or Clock/Data Reader 

Reader Port 2 

Typical D1/D0 or Clock/Data Reader 

1

TB3

VO (12 Vdc)

GND

LED

BZR

CLK/D1
DAT/D0

FIRST READER PORT

TB4

1

BZR

DAT/D0

CLK/D1

LED

SECOND READER PORT

1

TB5

GND

VIN

GND

VO

(12 Vdc)

Содержание MR51e

Страница 1: ...ED mode only Reader port 2 can accommodate a reader that TTL D1 D0 Clock Data or F 2F signaling and also provides tri stated LED control and buzzer control one wire LED mode only Two Form C relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 5 A 30 Vac dc dry contact configuration Four inputs are provided that may be used for monitoring the door con...

Страница 2: ...T Data 0 Input TB5 1 VO Auxiliary Power Output 12 Vdc TB5 2 GND Auxiliary Power Output Ground TB5 3 VIN Input Power 12 Vdc from local power supply TB5 4 GND Input Power Ground TB6 1 NO Relay K1 Normally Open Contact TB6 2 1 C Relay K1 Common Contact TB6 3 NC Relay K1 Normally Closed Contact TB6 4 NO Relay K2 Normally Open Contact TB6 5 2 C Relay K2 Common Contact TB6 6 NC Relay K2 Normally Closed ...

Страница 3: ...e MR51e is Ethernet 10Base T 100Base TX It is not recommended to connect the MR51e to a public intranet 6 Reader Wiring Reader port 1 supports TTL D1 D0 Clock Data F 2F or 2 wire RS 485 device signaling Reader port 2 supports TTL D1 D0 Clock Data or F 2F signaling Power to reader port 1 is 12 Vdc at 180 mA maximum Reader port 2 may be powered from the auxiliary power supply output TB5 1 and TB5 2 ...

Страница 4: ...TR FIRST READER PORT 12 Vdc D1 GROUND DO GREEN LED F 2F Reader 1 VO 12 Vdc GND LED BZR CLK D1 DAT D0 TB3 FIRST READER PORT TB4 1 BZR DAT D0 CLK D1 LED 1 TB5 GND VIN GND VO 12 Vdc D1 GROUND DO GREEN LED F 2F Reader SECOND READER PORT 1 TB3 VO 12 Vdc GND LED BZR CLK D1 DAT D0 12 Vdc D1 GROUND DO GREEN LED F 2F Reader NORMALLY CLOSED CONTACT DOOR MONITOR SWITCH REQUEST TO EXIT SWITCH NORMALLY OPEN CO...

Страница 5: ...rated at 5 A 30 Vac dc dry contact configuration Each relay has a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for prop...

Страница 6: ...e encryption disabled 0 8 second ON 0 2 second OFF 1 On line encryption enabled four pulses 0 1 second ON 0 1 second OFF per second Off line 0 2 second ON 0 8 second OFF static addressing mode only Waiting for application firmware to be downloaded 1 sec ON 1 sec OFF 2 Flashes when there is host communication approximately every 5 seconds 3 Flashes when data is received from either reader downstrea...

Страница 7: ...above LED Output TTL compatible high 3 V low 0 5 V 5 mA source sink maximum Buzzer Output Open collector 12 Vdc open circuit maximum 40 mA sink maximum Data Inputs Reader port 1 TTL compatible F 2F or 2 wire RS 485 Reader port 2 TTL compatible or F 2F Cable Requirements Communication Ethernet Category 5 minimum Power 1 twisted pair 18 AWG Alarm Inputs 1 twisted pair per input 30 ohm maximum Reader...

Страница 8: ...IC TAMPER SWITCH 11 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 Side View Mounting Plate Dimensions 3 85 97 8 2 35 59 7 5 50 139 7 3 63 92 1 3 30 83 8 3 63 92 1 Ø0 16 Ø4 0 MR50 MGT HOLES 4PL Ø0 16 Ø4 0 3 GANG MGT HOLES ...

Страница 9: ...entative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose All returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an a...

Отзывы: