background image

 

Mercury Security © 2015 

MR51e 

DOC  10107-0035  

REV 1.06 

 Page   6 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

9.  Status LEDs: 

At power up, LEDs 2 through 6 are turned ON then OFF in sequence. 

After the above sequence has completed succes

sfully, the MR51e goes to the “Waiting for IP Address” 

mode, when in the MSC-Specific DHCP or Public DHCP addressing modes: 

Waiting for IP Address mode: 

LED 

DESCRIPTION  

Off-line:  0.2 second ON, 0.8 second OFF 

 

Waiting for application firmware to be downloaded: .1 sec ON, .1 sec OFF 

Waiting for IP address: 0.5 second ON, 0.5 second OFF 

The  following  table  describes  the  LED

’s  in  the  Normal  Running  mode.    If  communication  is  lost,  the 

MR51e reverts back to the “Waiting for IP Address” mode, when in the MSC-Specific DHCP or  Public 
DHCP addressing modes: 

Normal Running mode: 

LED 

DESCRIPTION 

 

On-line, encryption disabled = 0.8 second ON, 0.2 second OFF 

On-line, encryption enabled = four pulses; 0.1 second ON, 0.1 second OFF per second 

 

Off-line:  0.2 second ON, 0.8 second OFF (static addressing mode only) 

 

Waiting for application firmware to be downloaded: .1 sec ON, .1 sec OFF 

Flashes when there is host communication (approximately every 5 seconds) 

Flashes when data is received from either reader/downstream devices 

Input IN1 Status: OFF = Inactive, ON = Active, Flashing = Trouble.  See note 1 

Input IN2 Status: OFF = Inactive, ON = Active, Flashing = Trouble.  See note 1 

Input IN3 Status: OFF = Inactive, ON = Active, Flashing = Trouble.  See note 1 

YEL 

Ethernet speed: OFF = 10 Mb/S, ON = 100 Mb/S 

GRN 

OFF = No Link, ON = Good Link, Flashing = Ethernet Activity 

Note 1:  If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1 

second, otherwise, the LED is off. 

 

 

 

 
MOV Selection: 

 
Clamp voltage: 1.5x Vac RMS.   
Use UL recognized MOV with appropriate 
ratings 

 

TB

6

1

NO
1-C
NC

NC

NO

2-C

Содержание MR51e

Страница 1: ...ED mode only Reader port 2 can accommodate a reader that TTL D1 D0 Clock Data or F 2F signaling and also provides tri stated LED control and buzzer control one wire LED mode only Two Form C relay outputs may be used for door strike control or alarm signaling The relay contacts are rated at 5 A 30 Vac dc dry contact configuration Four inputs are provided that may be used for monitoring the door con...

Страница 2: ...T Data 0 Input TB5 1 VO Auxiliary Power Output 12 Vdc TB5 2 GND Auxiliary Power Output Ground TB5 3 VIN Input Power 12 Vdc from local power supply TB5 4 GND Input Power Ground TB6 1 NO Relay K1 Normally Open Contact TB6 2 1 C Relay K1 Common Contact TB6 3 NC Relay K1 Normally Closed Contact TB6 4 NO Relay K2 Normally Open Contact TB6 5 2 C Relay K2 Common Contact TB6 6 NC Relay K2 Normally Closed ...

Страница 3: ...e MR51e is Ethernet 10Base T 100Base TX It is not recommended to connect the MR51e to a public intranet 6 Reader Wiring Reader port 1 supports TTL D1 D0 Clock Data F 2F or 2 wire RS 485 device signaling Reader port 2 supports TTL D1 D0 Clock Data or F 2F signaling Power to reader port 1 is 12 Vdc at 180 mA maximum Reader port 2 may be powered from the auxiliary power supply output TB5 1 and TB5 2 ...

Страница 4: ...TR FIRST READER PORT 12 Vdc D1 GROUND DO GREEN LED F 2F Reader 1 VO 12 Vdc GND LED BZR CLK D1 DAT D0 TB3 FIRST READER PORT TB4 1 BZR DAT D0 CLK D1 LED 1 TB5 GND VIN GND VO 12 Vdc D1 GROUND DO GREEN LED F 2F Reader SECOND READER PORT 1 TB3 VO 12 Vdc GND LED BZR CLK D1 DAT D0 12 Vdc D1 GROUND DO GREEN LED F 2F Reader NORMALLY CLOSED CONTACT DOOR MONITOR SWITCH REQUEST TO EXIT SWITCH NORMALLY OPEN CO...

Страница 5: ...rated at 5 A 30 Vac dc dry contact configuration Each relay has a Common pole C a Normally Open pole NO and a Normally Closed pole NC When you are controlling the delivery of power to the door strike the Normally Open and Common poles are used When momentarily removing power to unlock the door as with a mag lock the Normally Closed and Common poles are used Check with local building codes for prop...

Страница 6: ...e encryption disabled 0 8 second ON 0 2 second OFF 1 On line encryption enabled four pulses 0 1 second ON 0 1 second OFF per second Off line 0 2 second ON 0 8 second OFF static addressing mode only Waiting for application firmware to be downloaded 1 sec ON 1 sec OFF 2 Flashes when there is host communication approximately every 5 seconds 3 Flashes when data is received from either reader downstrea...

Страница 7: ...above LED Output TTL compatible high 3 V low 0 5 V 5 mA source sink maximum Buzzer Output Open collector 12 Vdc open circuit maximum 40 mA sink maximum Data Inputs Reader port 1 TTL compatible F 2F or 2 wire RS 485 Reader port 2 TTL compatible or F 2F Cable Requirements Communication Ethernet Category 5 minimum Power 1 twisted pair 18 AWG Alarm Inputs 1 twisted pair per input 30 ohm maximum Reader...

Страница 8: ...IC TAMPER SWITCH 11 Additional Mounting Information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 Side View Mounting Plate Dimensions 3 85 97 8 2 35 59 7 5 50 139 7 3 63 92 1 3 30 83 8 3 63 92 1 Ø0 16 Ø4 0 MR50 MGT HOLES 4PL Ø0 16 Ø4 0 3 GANG MGT HOLES ...

Страница 9: ...entative to make any other warranties or implied warranties and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose All returns must be accompanied by a Return Material Authorization RMA number obtained from customer service and prepaid postage and insurance Liability The Interface should only be used to control exits from areas where an a...

Отзывы: