background image

 

Mercury Security © 2015 

EP4502 

DOC  10107-0039  

REV 1.02 

 Page   3 

 

DIP Switches: 

The four switches on S1 DIP switch configure the operating mode of the EP4502 processor.  
DIP switches are read on power-up except where noted.  Pressing reset switch S2 or the processor reset 
switch S1 (on the processor board) causes the EP4502 to reboot. 

Definitions 

OFF 

OFF 

OFF  OFF  Normal operating mode. 

ON 

OFF 

OFF  OFF 

After initialization, enable default User Name (admin) and Password 
(password).  The switch is read on the fly, no need to re-boot.   
See IT Security section for additional information 

OFF 

ON 

OFF  OFF  Use factory default communication parameters. 

ON 

ON 

OFF  OFF  Use OEM default communication parameters.  Contact system 

manufacture for details.  See Bulk Erase below. 

ON 

ON 

OFF  OFF  Bulk Erase prompt mode at power up.  See Bulk Erase below. 

All other switch settings are unassigned and are reserved for future use. 

 

In the factory or OEM default modes, downloaded configuration/database is not saved to flash memory. 

Factory Default Communication Parameters:

 

Network: static IP address: 192.168.0.251 
Communication address: 0 
Primary Host port: IP server, no encryption, port 3001. 

4.  The bulk erase function can be used for the following purposes: 

  Erase all configuration and cardholder database (sanitize board). 

  Update OEM default parameters after OEM code has been changed.  

  Recover from database corruption causing EP4502 board to continuously reboot.   

 
If clearing the memory does not correct the initialization problem, contact technical support. 
 

Bulk Erase Steps: 

Do not remove power during steps 1-8.  

1.  Set S1 DIP switches to: 1 & 2 "ON", 3 & 4 "OFF". 
2.  Apply power to the EP4502 board. 
3.  Watch for LEDs 1 & 2 and 3 & 4 to alternately flash at a 0.5 second rate. 
4.  Within 10 seconds of powering up, change switches 1 or 2 to "OFF".  If these switches are not 

changed, the EP4502 board will power up using the OEM default communication parameters. 

5.  LED 2 will flash indicating that the configuration memory is being erased. 
6.  Full memory erase takes up to 60 seconds. 
7.  When complete, only LEDs 1 & 4 will flash for 8 seconds. 
8.  The EP4502 Board will reboot 8 seconds after LEDs 1 & 4 stop flashing (no LEDs are on during this 

time). 

5.  Input Power, Cabinet Tamper and UPS Fault Input Wiring: 

The EP4502 requires 12-24 Vdc power.  Locate power source as close to the unit 
as possible.  Connect power with minimum of 18 AWG wire.  

Connect the GND 

signal to earth ground in ONE LOCATION within the system!  Multiple earth 
ground connections may cause ground loop problems and is not advised.

 

 

Observe POLARITY on 12-24 Vdc input! 

There  are  two  dedicated  inputs  for  cabinet  tamper  and  UPS  fault  monitoring.  
Normal (safe) condition is a closed contact.  If these inputs are not used, install a 
jumper wire. 

 

 

12 TO 24Vdc

VIN

+

-

CABINET

TAMPER

POWER

FAULT

TB1

TMP

GND

FLT

GND

GND

Содержание EP4502

Страница 1: ...al signaling standards and also provides tri stated LED control and buzzer control one wire LED mode only Four Form C relay outputs may be used for strike control or alarm signaling The relay contacts...

Страница 2: ...NO Normally Open Contact Input 4 IN4 C Common IN4 NC Normally Closed Contact TB6 Input 5 IN5 Out 4 NO Normally Open Contact IN5 C Common Input 6 IN6 NC Normally Closed Contact IN6 TB7 Input 7 IN7 IN7...

Страница 3: ...fault parameters after OEM code has been changed Recover from database corruption causing EP4502 board to continuously reboot If clearing the memory does not correct the initialization problem contact...

Страница 4: ...the communication channel 7 Reader Wiring Each reader port supports Wiegand magnetic stripe and 2 wire RS 485 electrical interfaces Power to the reader is selectable 12 Vdc VIN must be greater than 2...

Страница 5: ...door lock mechanisms or alarm signaling The relay contacts are rated at 5 A 30 Vdc dry contact configuration Each relay has a Common pole C a Normally Open pole NO and a Normally Closed pole NC When...

Страница 6: ...tions are available to disable SNMP Zeroconf discovery as well as the web configuration module itself Additionally data encryption can also be enabled over the host communication port 12 Status LEDs P...

Страница 7: ...f this device must comply with all local fire and electrical codes Primary Power 12 to 24 Vdc 10 500 mA maximum reader current not included Memory and Clock Backup Battery 3 Volt Lithium type BR2325 B...

Страница 8: ...ury Security assumes no responsibility for products damaged by improper handling or installation This warranty is limited to the repair or replacement of the defective unit There are no expressed warr...

Отзывы: