![MerCs Strider M73 Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/mercs/strider-m73/strider-m73_user-manual_1772969006.webp)
02 4047 0777
www.mercs.com.au
02 4047 0788
MerCs Pty Ltd, 55 Pendlebury Rd, Cardiff, NSW, 2285, Australia | 2018 V1.1
6
Multifunction Power Analyser
MerCs Strider M73
Number of measurement points per circle
128
128
128
Auxiliary power supply
•
•
•
Note:
•
= included
* = optional
— = excluded
5. Unit Characteristics
The Unit can measure and display:
The unit has password-protected set-up screens for:
•
Line voltage and THD% (total harmonic distortion) of all phases
•
2~63rd voltage IHD% (Individual Harmonic distortion) of all phases
•
Line Frequency
•
Phase Sequence
•
Currents, Current demands and current THD% of all phases
•
2~63rd current IHD% of all phases
•
Active power, reactive power, apparent power, maximum power demand and power factor
•
Max./ Min.Current and voltage, Max.current demand
•
Import / export / total active energy
•
Import / export / total reactive energy
•
Total active energy of each phase
•
DPF ( Displacement Power factor, Modbus read only)
•
Voltage crest factor (Modbus read only)
•
Current K factor (Modbus read only)
•
Communication setting: Modbus address, Baud rate, Parity, Stop bit
•
CT setting: CT 1 ( Primary) , CT2 ( Secondary), CT rate
•
PT setting: PT1 (Primary), PT2 (Secondary) , PT rate
•
Demand setting: demand method, Demand interval time
•
Time setting: Backlit time, display scroll time, system RTC
•
System configuration: System type, System connect, Change password, Auto display scroll
•
Ethernet (TCP/IP) Communication setting: IP Address, IP port , Mode
•
SOE (sequence of event) Information: 20 SOE and times
•
Reset: Energy, Demand, Max.Min value, SOE, All
CT and PT
CT1 (primary current): 1~9999A
CT2 (secondary current): 1A or 5A
PT1 (primary voltage): 100V ~ 500,000V
PT2 (secondary voltage): 100 to 480 V AC (L-L)
RS485 Serial-Modbus RTU
This unit uses a RS485 serial port with Modbus RTU protocol to provide a means of remote monitoring and controlling.
Please check the Part 4.2 for the details of setting.
Ethernet TCP/IP
This unit equipped with an Ethernet (TCP/IP) communication port for rapid and reliable data transfer. It would be easy to integrate the meter into a network.