Multifunction Power Analyser
MerCs Strider M73
Password Entry
Communication
•
Address
•
Baud rate
Image
Setting-up mode is password protected, so you must enter the correct password. By firmly press the
button for 2 seconds, the password screen appears. The default password is 1000. If an incorrect
password is entered, the display shows ERR.
Image
The RS485 port can be used for communications using Modbus RTU protocol. Parameters such as
Address, Baud rate, Parity, Stop bit can be selected.
Long press to enter the Address option.
Image
An RS485 network can accommodate up to 255 different devices, each identified by an address.
Modbus address range 001~247
Default 001
Long press to enter the selection routine, the address setting will flash. Use and ,
to set the address with the range 001~247. And press for confirmation.
Image
Baud rate options: 2400 4800 9600 19200 38400 (bps).
Default: 9600bps
From the Set-up menu, Use and to select the Baud rate options.
Long press to enter the selection routine. The Baud Rate setting will flash. Use and to
choose Baud Rate.
Example shows:
SET Baud rate 19200 (bps)
And long press for confirmation.