![MerCs ME-PM-M4-5 Скачать руководство пользователя страница 2](http://html.mh-extra.com/html/mercs/me-pm-m4-5/me-pm-m4-5_user-manual_1772967002.webp)
02 4047 0777
www.mercs.com.au
02 4047 0788
2
Strider M4 V2
ME-PM-M4-5
MerCs Pty Ltd, 55 Pendlebury Rd, Cardiff, NSW, 2285, Australia | 2019 V1.1
1
2
3
The first screen lights up all display seg-
ments and can be used as a display check.
Software version information
The interface performs a self-test and
indicates the result if the test passes.
1
2
3
4
Selects the Voltage and
Current display screens. In
Set-up Mode, this is the “Left”
or “Back” button.
Select the Frequency and
Power factor display screens. In
Set-up Mode, this is
the “Up” button.
Select the Power display
screens. In Setup Mode, this is
the “Down” button.
Select the Energy display
screens. In Setup mode, this is
the “Enter” or “Right” button.
Start-up Screens
Measurements
The buttons operate as follows:
*After a short delay, the screen will display active energy measurements.
Current Transformer Primary Current
RS485 Serial Modbus RTU
Pulse output
Strider M4 V2 Series is CT operated. you will need to set the correct ratio.
As an example: If using 100/5A CT, you will need to insure CT2 (Secondary) is set to 5 and CT rate is 0020. You divide
the primary by the secondary to get the CT rate to be entered (100/5=20).
This uses an RS485 serial port with Modbus RTU protocol to provide a
means of remotely monitoring and controlling the Unit.
Set up screens are provided for setting up the RS485 port.
This provides two pulse outputs that cloc k up measured active
and reactive energy. The constant for active energy is 3200imp/k
W h (Terminals 11& 12). The pulse width for pulse 1(Terminals 9&10)
can be set from the s et up menu.
C1C2
U/I
ESC
M
P
E