From the Set Set-up menu, use and
buttons to select the CT option.
Secondary CT setting
Press to enter the CT secondary current
selection routine. routine.:5A/1A
Set CT Ratio value
Press to enter the CT Ratio setting screen. The
range is from 0001 to 9999.
M
P
E
E
CT Settings
The CT option sets the secondary current (CT2 1A or 5A) of the current transformer (CT) that wires to the meter.
For example, if using a 100/5A current transformer you will enter 0020, as you need to divide the primary by the secondary to get the ratio
(CT rate).
* Please note for the MID approved version device,you will only have one opportunity to set the ratio.
From the Set Set-up menu, use and
buttons to select the CT option.
M
P
PT Settings
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that wires to the meter.