7.2. Location and assembly_______________________________________________________ 

The  mcr  Bora  fan  is  designed  for  horizontal  installation.  Prior  to  installation  of  the  fan,  verify  the  load 
bearing capacity of the ceiling or other structural element where the equipment is to be suspended. Use 
the  mounting  frame  (part  of  the  fan  itself)  or  the  fasteners  supplied  with  the  fan.  Using  the  above 
mentioned  element,  the  device  is  fitted  to  the  structural  elements  using  bolts  or  using  hangers  (not 
supplied). 
Fan due to his construction, does not require vibration isolation between the structural elements and the 
device.  In  case  of  demanded  by  bulining  project  assembly  by  means  of  vibration  insolation,  the 
manufacturer recommend to instal the device according to drawing 2. Other assembly may be provided, 
providing  that  the  device  is  safe  and  undisturbed,  in  normal  operation  and  fire  condtions.  Screws, 
anchors, suspensions (diameter, length) and other assembly elements must be selected for the size of 
the device and the required fire resistane.  

 

 

Drawing 2 Example illustrating how to install the mcr Bora with 

vibration isolation elements. 

 

 

7.3. Electrical connections_____________________________________________________ 

Having  properly  located,  placed  and  fastened  the  smoke  exhaust  fan,  connect  the  equipment  to  the 
relevant electrical system wiring. Lead the wiring through the gland and into the terminal box on the fan 
casing; then connect the wiring to the terminals in accordance with the diagram shown in the box. The 
electrical wire with the proper fire resistance rating is installed in standard by the manufacturer between 
the fan motor and the terminal box.  Each fan motor  must  be connected to  the electrical power  system 
through an overcurrent switch. The safety level must be set in accordance with the nominal current draw 
of the fan motor. The protective earth shall be made in accordance with relevant electrical engineering 
standards. 
Once the smoke exhaust fan has been commissioned as a part of the system, measure the current draw 
and  verify  that  it  meets  the  motor  rating  plate  data.  The  smoke  exhaust  fan  current  draw  in  steady 
operation must not exceed 1.1 times the rated current. 
The  electrical  power  supply  from  the  control  cabinet  to  the  fan  power  junction  box  must  guarantee 
uninterrupted operation in the case of a fire. This can be achieved with high temperature resistant wiring 
or  with  protective  tubing  and  proper  safe  routing  of  the  electrical  power  system.  No  external 
service/maintenance  switches  are  to  used,  which  is  to  prevent  inadvertent  shutdown  of  the  smoke 
exhaust fan (with the sole exception of the fan-dedicated service switch with remote indication of current 
circuit  switching).  The  smoke  exhaust  fan  control  cabinets  must  be  powered  directly  from  main 
switchboards with guaranteed uninterrupted power supply, even if the entire building is cut off from the 
power  grid.  If  a  main  fireman's  switch  is  installed  to  isolate  power  from  the  entire  building,  the  smoke 

Содержание mcr Bora BO

Страница 1: ...Ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 0 58 341 39 85 OPERATIONAL AND MAINTENANCE MANUAL Jet fan mcr Bora Revision 19 06 27 4 FIRE VENTILATION SYSTEMS ...

Страница 2: ...e 4 4 3 Versions 5 5 IDENTIFICATION MARKINGS 5 6 DESIGN AND OPERATING PRINCIPLE 5 6 1 Design 5 6 2 Function 5 6 3 Dimensions and technical features 5 7 INSTALLATION 7 7 1 Pre assembly inspection 7 7 2 Location and assembly 7 7 3 Electrical connections 7 7 4 Commissioning 8 8 TRANSPORT STORAGE CONDITIONS 8 9 SAFETY MANUAL 9 10 MAINTENANCE SERVICING 8 11 WARRANTY TERMS CONDITIONS 9 FAN MEASUREMENT R...

Страница 3: ...st fans The design also meets the state of the art in technology while assuring health and safety protection 2 MANUFACTURER S DISCLAIMER__________________________________ The manufacturer shall not be liable for any consequences of non intended use or misuse of the equipment DO NOT install any components that are not included in the equipment composition or accessories Unauthorised modifications o...

Страница 4: ...re occurance The available versions include single direction fans with dual speed motor reversible fans with dual speed motor The fans can be installed indoors on suitable consoles with the motor in the horizontal orientation The operating temperature range for fans in general purpose ventilation systems is 20 C to 40 C The fan may force dry air only with a maximum particulate content of 0 3 g m T...

Страница 5: ...ing assembly and silencers The motor is coupled directly to an aluminium rotor on bearings and on the rotor the profiled blades are installed The angle and number of blades depend on the required thrust and capacity of the fan The motor bearings are high temperature resistant and maintenance free On the inlet and outlet side the engine is connected to silencers The medium which is fire gases and a...

Страница 6: ...00 2410 482 495 657 400 750 720 167 26 12 mcr Bora 500 500 2650 3060 533 547 708 480 780 750 200 30 14 mcr Bora 560 560 2650 3060 608 622 798 650 950 920 255 30 14 7 INSTALLATION_____________________________________________ The mcr Bora smoke exhaust jet fan is intended for use in rooms designed for moving air and fire gases in the fire zone 7 1 Pre assembly inspection_____________________________...

Страница 7: ...g through the gland and into the terminal box on the fan casing then connect the wiring to the terminals in accordance with the diagram shown in the box The electrical wire with the proper fire resistance rating is installed in standard by the manufacturer between the fan motor and the terminal box Each fan motor must be connected to the electrical power system through an overcurrent switch The sa...

Страница 8: ...omponents of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature is between 20ºC and 40ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Operating and Maintenance Manual before commissioning and servicing the product The smoke exhaust fan is not hazardous when firmly attached to a ventilati...

Страница 9: ... or sales contract subject to Item 10 5 MERCOR SA has the right to extend the time of repair if the defect removal is complicated or requires purchase of custom components or spare parts 6 The warranty liability only covers all defects arising from causes present in the equipment at the date of sale 7 Defects caused by improper operation or otherwise as listed in Item 10 herein the buyer warranty ...

Страница 10: ...this Operating and Maintenance Manual and or good construction practice The equipment and or parts thereof with removed or damaged nameplate rating plate and or warranty seals 11 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance in accordance with the section MAINTENANCE AND SERVICING in the following Operating and Mai...

Страница 11: ...ent draw in steady state operation of the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than within 8 weeks from the date of equipment purchase equivalent to the date of the ...

Отзывы: