3. SUBJECT______________________________________ 

The subject of this Operating and Maintenance Manual is: 

  Jet fan mcr Bora F400 

  Jet fan mcr Bora F300 

  Jet fan mcr Bora F200 

  Jet fan mcr Bora BO – without fire resistance  

 

4. INTENDED USE___________________________________________________ 

4.1. Application_________________________________________________________________ 

The mcr Bora jet fans are intended to remove smoke and heat generated in indoor rooms in case of fire. 
The equipment facilitates evacuation of persons from the area on fire, protect the building structure and 
its  furnishing  from  high  temperature,  facilitate  fire  fighting,  and  inhibit  spreading  of  fire  to  adjacent  fire 
zones.The  mcr  Bora  without  fire  resistance  jet  fans  are  intered  to  ventilate  rooms  in  case  of  no  fire 
occurance. 
 
The available versions include: 

  single direction fans, with dual-speed motor 

  reversible fans, with dual-speed motor 

 
The fans can be installed indoors on suitable consoles with the motor in the horizontal orientation. 

 

 
 

The  operating  temperature  range  for  fans  in  general  purpose  ventilation 
systems is -20°C to + 40°C. 
The fan may force dry air only, with a maximum particulate content of 0.3 g/m³.  

 

 
This fan is not intended for forcing air with viscous pollutants that may settle 
on the equipment, especially on its rotor.  

 

    

This fan is not intended for forcing air with corrosive pollutants that may be 
detrimental to the equipment.  

 

  
 

The maximum actual rotor RPM must never exceed the nominal (rated) RPM 
speed in operation.  

 

 

Following operation in actual fire conditions, the fan will not be fit for further 
use. 

 
 

 
 

4.2. Fire resistance__________________________________________________________ 

  Class F400 – fire resistance at 400°C for 120 minutes 

  Class F300 – fire resistance at 300°C for 60 minutes 

  Class F200 – fire resistance at 200°C for 120 minutes 

  Without fire resistance 

Содержание mcr Bora BO

Страница 1: ...Ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 0 58 341 42 45 tel fax 0 58 341 39 85 OPERATIONAL AND MAINTENANCE MANUAL Jet fan mcr Bora Revision 19 06 27 4 FIRE VENTILATION SYSTEMS ...

Страница 2: ...e 4 4 3 Versions 5 5 IDENTIFICATION MARKINGS 5 6 DESIGN AND OPERATING PRINCIPLE 5 6 1 Design 5 6 2 Function 5 6 3 Dimensions and technical features 5 7 INSTALLATION 7 7 1 Pre assembly inspection 7 7 2 Location and assembly 7 7 3 Electrical connections 7 7 4 Commissioning 8 8 TRANSPORT STORAGE CONDITIONS 8 9 SAFETY MANUAL 9 10 MAINTENANCE SERVICING 8 11 WARRANTY TERMS CONDITIONS 9 FAN MEASUREMENT R...

Страница 3: ...st fans The design also meets the state of the art in technology while assuring health and safety protection 2 MANUFACTURER S DISCLAIMER__________________________________ The manufacturer shall not be liable for any consequences of non intended use or misuse of the equipment DO NOT install any components that are not included in the equipment composition or accessories Unauthorised modifications o...

Страница 4: ...re occurance The available versions include single direction fans with dual speed motor reversible fans with dual speed motor The fans can be installed indoors on suitable consoles with the motor in the horizontal orientation The operating temperature range for fans in general purpose ventilation systems is 20 C to 40 C The fan may force dry air only with a maximum particulate content of 0 3 g m T...

Страница 5: ...ing assembly and silencers The motor is coupled directly to an aluminium rotor on bearings and on the rotor the profiled blades are installed The angle and number of blades depend on the required thrust and capacity of the fan The motor bearings are high temperature resistant and maintenance free On the inlet and outlet side the engine is connected to silencers The medium which is fire gases and a...

Страница 6: ...00 2410 482 495 657 400 750 720 167 26 12 mcr Bora 500 500 2650 3060 533 547 708 480 780 750 200 30 14 mcr Bora 560 560 2650 3060 608 622 798 650 950 920 255 30 14 7 INSTALLATION_____________________________________________ The mcr Bora smoke exhaust jet fan is intended for use in rooms designed for moving air and fire gases in the fire zone 7 1 Pre assembly inspection_____________________________...

Страница 7: ...g through the gland and into the terminal box on the fan casing then connect the wiring to the terminals in accordance with the diagram shown in the box The electrical wire with the proper fire resistance rating is installed in standard by the manufacturer between the fan motor and the terminal box Each fan motor must be connected to the electrical power system through an overcurrent switch The sa...

Страница 8: ...omponents of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature is between 20ºC and 40ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Operating and Maintenance Manual before commissioning and servicing the product The smoke exhaust fan is not hazardous when firmly attached to a ventilati...

Страница 9: ... or sales contract subject to Item 10 5 MERCOR SA has the right to extend the time of repair if the defect removal is complicated or requires purchase of custom components or spare parts 6 The warranty liability only covers all defects arising from causes present in the equipment at the date of sale 7 Defects caused by improper operation or otherwise as listed in Item 10 herein the buyer warranty ...

Страница 10: ...this Operating and Maintenance Manual and or good construction practice The equipment and or parts thereof with removed or damaged nameplate rating plate and or warranty seals 11 The buyer warranty rights holder is required to operate the equipment properly and carry out technical inspection and maintenance in accordance with the section MAINTENANCE AND SERVICING in the following Operating and Mai...

Страница 11: ...ent draw in steady state operation of the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than within 8 weeks from the date of equipment purchase equivalent to the date of the ...

Отзывы: