User manual ZSP135-DR

                               

0404.00.95-05.4                                               14/36 

 

Warnings 
 

Please read all these tips and regulations. 

Mistakes in their observance may cause damage, electric 

shock, fire or serious injury. 

 

 

It is forbidden to carry and transport the device with mounted and connected batteries

This can cause severe internal faults and can lead to the loss of operation safety. 

 

Installation and connections can be made only when batteries removed. 

 

When connecting batteries that may pose a threat due to high energy level, pay special 
attention to the compatibility of their polarity with the description on the connector 

 

Do not block ventilation openings.

 Provide a free space of at least 10 cm at the sides of the 

device, enabling its proper ventilation. Otherwise, it can lead to damage of the device or early 
battery deterioration. 

 

Please, install the device in a place where it is not exposed to direct sunlight. 

 

The device must be powered from the mains with a protective earthing terminal. 

 

Before starting the device, please, check the quality of all connections

 

The device may interfere with operation of sensible radio and television equipment 
located nearby. 

 

The device may be operated only by authorized and trained personnel. 

 

The device must be serviced by servicemen of the manufacturer or specialized service 
companies authorized by the manufacturer. 

 

1.  Technical description 
 

This user manual refers to the power supply with remote indication of faults defined as the 

mains fault and the battery fault. These two signals can be combined into a collective fault 
indication 

– see the section 2.3. 

In this respect it differs from the previous version, offering the collective fault indication 

(including the mains fault too) and a separate signal about the mains fault.  

Types of the available indications can be recognized by reading descriptions next to 

connectors or on the wiring diagram (a sticker inside the casing). 

 

 

1.1.  Application 

The power supplies are dedicated to uninterruptible supply of power in the range of 55 W to 190 W 

at the voltage 24 V to devices of fire detection and fire alarm systems, systems of smoke and heat 
control as well as other fire protection devices, where compliance with EN 54-4:1997 + AC:1999 + 
A1:2002 + A2:2006 or EN 12101-10:2005 + AC:2007, guidelines of VdS 2541:1996-12, 2882:2004-11, 
2824:2004-03, 2593:2002-09 or the Polish Ordinance (specified on the title page) is required. 

The battery backup power supplies ZSP135-DR supply power from the utility power grid or 

– in 

case of a power failure 

– from internal bank of VRLA batteries (known also as AGM or gel batteries). 

They have two outputs, protected by fuses. The power supply can be optionally equipped with an 
ZSP135-OUT6 additional outputs module (see the section 2.4). During a transition from the mains 
power to the battery power and vice versa there are no voltage dropouts on the outputs. 

 
The power supplies fulfill the requirement of EN 54-4 to offer a collective fault indication by an 

appropriate connection of relay outputs of the signals (see the section 2.3). 

The power supplies can manage an external binary fault signal and optionally can be equipped with 

the device to detect unauthorized opening of the door (see the section 4.3) 

 
Depending  on the  battery bank capacity the power supplies  are assembled  into three  types of wall 

boxes (see the section 1.2). 

1.2. 

Technical data

 

General electrical and environmental parameters 

Nominal input voltage 

230 V +10% -15% 

Nominal output voltage 

*1)

 

27.1 V 

Output voltage range 

*2)

 

20.8…28.0 V 

Minimal battery voltage 

21.3 V 

Current consumption from the battery for own needs 

max 35 mA 

Содержание ZSP135-DR-2A-1

Страница 1: ...ZSP135 DR 7A 2 ZSP135 DR 7A 3 zgodnych z normami EN 54 4 1997 AC 1999 A1 2002 A2 2006 i EN 12101 10 2005 AC 2007 wytycznymi VdS 2541 1996 12 2882 2004 11 2824 2004 03 2593 2002 09 oraz Rozp MSWiA z d...

Страница 2: ...konfigurowa sygna zbiorczy patrz punkt 2 3 Pod tym wzgl dem zasilacz r ni si od poprzedniej wersji w kt rej udost pniano sygna zbiorczy uszkodzenia uwzgl dniaj cy tak e zanik sieci oraz osobny sygna z...

Страница 3: ...Niemniej jednak w wysokiej temperaturze otoczenia dochodzi do bardzo du ego skr cenia ywotno ci akumulator w Dlatego temperatura otoczenia przekraczaj ca 40 C nie powinna przewa a w miejscu instalacj...

Страница 4: ...nale y zawiesi na cianie wykorzystuj c do tego cztery otwory umieszczone w tylnej cianie szafki Przed rozpocz ciem monta u nale y otworzy szafk odkr ci trzy nakr tki mocuj ce p yt no n zasilacza do t...

Страница 5: ...50 Hz L N i uziemienie przew d 3 y owy 2 0 75 1 5 mm2 2 Z cze do pod czenia baterii akum BATTERY 1 3 4 Z cze do do czenia odbioru OUT 1 OUT 2 przew d 2 y owy 2 typu HDGs 1 5 lub 2 5 mm2 5 Wyj cie sygn...

Страница 6: ...ZSP135 OUT6 Modu zawiera 6 wyj zabezpieczonych bezpiecznikami topikowymi i sygnalizacj LED uszkodzenia ka dego z nich Standardowo modu wyposa ony jest w bezpieczniki topikowe szybkie 0 5 A Dla indywi...

Страница 7: ...Stan przeka nika mo na zbada np omomierzem w czonym mi dzy odpowiednie wyprowadzenia jego styk w 3 2 Badanie obwodu baterii akumulator w Przy zasilaczu pracuj cym z sieci nale y przerwa obw d akumula...

Страница 8: ...ach szafki i uruchomieniem przeka nikowej sygnalizacji uszkodzenia Jednoczesne wyst pienie kt rego z uszkodze wewn trznych zasilacza powoduje trwa e za czenie tej diody Zdarzenie to zosta o przypisane...

Страница 9: ...PERATION umo liwiaj ce rozr nienie zaniku zasilania sieciowego od uszkodzenia zasilacza oraz czerwona dioda BAT wskazuj ca na stan baterii akumulator w Sygnalizacja stanu zasilania sieciowego diody LE...

Страница 10: ...nta lub wyspecjalizowana jednostka upowa niona przez producenta 5 2 Rozpoznawanie i usuwanie uszkodze We wszystkich przypadkach za wyj tkiem zaniku zasilania sieciowego i uszkodzenia przetwornicy w kt...

Страница 11: ...m z wyj 1 Je eli napi cie na baterii jest 21 6 V to akumulator nie zostanie do czony do systemu Nale y najpierw do adowa go zewn trzn adowark lub wymieni na nowy Dioda FAULT b yska 2 Sygnalizacja mog...

Страница 12: ...cza stan w bez konieczno ci ingerowania w uk ad zasilacza i stosowania przyrz d w pomiarowych Mo liwe jest te okre lenie stanu baterii akumulator w w czasie testu oraz wymuszenie testu poza normalnym...

Страница 13: ...s EN 54 4 1997 AC 1999 A1 2002 A2 2006 EN 12101 10 2005 AC 2007 guidelines of VdS 2541 1996 12 2882 2004 11 2824 2004 03 2593 2002 09 as well as to the Ordinance of the Polish Minister of Interior and...

Страница 14: ...fault too and a separate signal about the mains fault Types of the available indications can be recognized by reading descriptions next to connectors or on the wiring diagram a sticker inside the cas...

Страница 15: ...lation location Current parameters Type Type of the box Imax_b Battery capacity Imax_a EN 54 4 Imax_a EN 12101 10 72 h 30 h 4 h ZSP135 DR 2A 1 1 2 A 18 Ah 1 0 A 0 16 A 0 42 A 1 00 A ZSP135 DR 3A 1 1 3...

Страница 16: ...he empty box has to be fixed to the wall by 4 steel sleeves and screws Wall plugs made of PVC can not be applied If there is a need to lead wires between the box and wall one has to fix enclosed brack...

Страница 17: ...flame retardant halogen free 2 1 or 2 5 mm2 5 Battery fault output BATTERY FLT twin solid core telecom flame retardant 2 1x2x0 8 mm2 6 Output of mains fault signal MAINS FLT 7 Input of external fault...

Страница 18: ...tected by fuses and LED signaling of damage to each of them As standard the module is equipped with fast 0 5 A fuses Other fuse values can be used for individual needs but they must be smaller than th...

Страница 19: ...mains please break the battery circuit by disconnecting one of its wires This state shall be detected during the first next test It could last up to 10 minutes In this state the indication FAULT on t...

Страница 20: ...orized access to the box interior Opening the door after having it unlocked causes disconnecting of the contacts of the sensor and triggers a fault indication the blinking LED FAULT on the door of the...

Страница 21: ...PERATION State of mains power Correct mains operation Damaged converter Mains power failure Indication of the state of the battery bank the LED on the circuit pack red LED BAT State of the battery ban...

Страница 22: ...except for the mains power failure and the failure of the converter in which the LED indication FAULT is activated there is an indication generated simultaneously on the relay output BAT FLT In all ca...

Страница 23: ...is blinking 2 The indication could have been triggered during the battery test then red BAT LED is on continuously see the section 4 4 Having the batteries replaced or the connections corrected the i...

Страница 24: ...power supply and without measurement equipment It is also possible to determine the state of the battery bank during the test and to force a test outside the automatic schedule 7 2 2 Communication mod...

Страница 25: ...AC 1999 A1 2002 A2 2006 EN 12101 10 2005 AC 2007 den VdS Richtlinien 2541 1996 12 2882 2004 11 2824 2004 03 2593 2002 09 und der Verordnung des polnischen Ministers f r Inneres und Verwaltung vom 20 0...

Страница 26: ...apitel 2 3 In dieser Hinsicht unterscheidet sich der Netzteil von seinem Vorg nger in dem das Summensignal f r die St rung das auch den Stromausfall umfasste und ein separates Signal f r den Stromausf...

Страница 27: ...atur eine starke Beeintr chtigung der Lebensdauer der Batterien Aus diesem Grund soll die Temperatur ber 40 C an dem Installationsort vermieden werden Stromparameter der Netzteilen Typ Geh usetyp Imax...

Страница 28: ...rausgedreht und das Netzteil entfernt werden Das leere Geh use ist mit vier Buchsen und Stahlschrauben an der Wand zu befestigen Es d rfen keine PVC Spreizd bel verwendet werden Ist es n tig zwischen...

Страница 29: ...mm2 6 Ausgang der St rung Stromausfall MAINS FLT 7 Eingang einer externen St rung EXT FLT 8 LED zur optischen Signalisierung gr n MAINS 9 LED zur optischen Signalisierung gelb OPERATION 10 LED zur opt...

Страница 30: ...tage des Moduls Die Eingangsleistung INPUT des Moduls muss mit Aufrechterhaltung der Polarit t an den Ausgang OUT 2 der Spannungsversorgung angeschlossen werden Mit dem Modul kann man auch Information...

Страница 31: ...tinuierlich berwacht werden um auf m gliche St rungen w hrend des Betriebs reagieren zu k nnen Das Netzger t schaltet die Akkubatterie im Moment des Netzstarts ein nur wenn ihre Spannung ist h her als...

Страница 32: ...beschriftet sind Alle bieten drei potentialfreie Kontakte die von anderen Schaltkreisen vollst ndig isoliert sind Anzeige des Betriebszustands kontinuierliches Leuchten kein Leuchten Blinken Lichtsig...

Страница 33: ...rkung Unabh ngig von ihrem Zustand sollen die Batterien nach den Vorgaben des CNBOP Brandschutzforschungs und Entwicklungszentrum der Polnischen Feuerwehr und VdS ausgewechselt werden 4 6 Inspektionen...

Страница 34: ...erst nach dem erfolgreichen n chsten zyklischen Test automatisch gel scht Dies kann bis zu 10 Minuten dauern unter die Bedienung dass der Akku wird nicht schnell geladen wird Symptome T r Platine berp...

Страница 35: ...Ist die erforderliche Kapazit t der Batterieanlage bekannt kann ein Netzteil aus der Tabelle im Abschnitt 1 1 ausgew hlt werden Man soll sich dabei nach der maximalen Kapazit t der Batterieanlage f r...

Страница 36: ...tilisiert werden Dies wird dazu beitragen die sch dliche Auswirkungen auf die menschliche Gesundheit und die Umwelt zu vermeiden 1438 MERAWEX Sp z o o Toru ska 8 44 122 Gliwice Poland 09 1438 CPD 0163...

Отзывы: