MEP Fire Brigade Key FSK700 Series Скачать руководство пользователя страница 13

User Manual FSK700-2 / FSK700-2SX

Chapter 2   •  Function

13

2.3 

Activation of the unblocking device

The unblocking device (a specially realised key switch – see, for example, Unblocking Device 
FSE/PHZ900-1, MEP Article No. 265662) is connected to the fire detection control panel in the 
same way as a manual call point. Upon activation of the unblocking device, fire alarm will be 
activated, thus unlocking the outer door of the Fire Brigade Key Safe via the confirmation signal of 
the transmitting device connected to the fire brigade.

Activation of the fire detection control panel by the unblocking device must not affect Fire Con-
trol procedures of the fire detection control panel.

2.4 

Fire alarm reset

The outer door of the Key Safe will only lock again after the fire detection control panel is reset, 
thereby terminating the confirmation signal, the/all master keys have been reinserted, and the inner 
and outer door have been closed. Successful locking can be confirmed by pulling the outer door.

By locking the outer door, monitoring of opening or sabotage of the Key Safe, as well as – if 
available – monitoring of the Flush Mounting Frame with Drill Protection and the Key Safe 
Column will be reactivated.

Should a master key not have been inserted correctly after resetting the fire detection control panel, 
a sustained buzzing tone generated by the Key Safe's integrated buzzer will sound upon closing the 
outer door.

This function is only available if the Key Safe is connected to the Key Safe Controlling and 
Monitoring Device AD900-1 by MEP (also see page 28 and onwards in chapter 5.3.2: "Acoustic
warning signal when missing master key"
).

If the Key Safe remains unopened during fire alarm, the outer door will be automatically locked 
again upon termination of the confirmation signal, and monitoring of opening or sabotage of the 
Key Safe, as well as – if available – monitoring of the Flush Mounting Frame with Drill Protection 
and the Key Safe Column will be reactivated.

2.5 

Sabotage alarm

The following states are constantly monitored by the Key Safe Controlling and Monitoring Device 
AD900-1:

Outer door closed,

Drill Protection Board undamaged,

master keys correctly inserted,

Drill Protection of the Flush Mounting Frame undamaged (if available),

Tamper Switch of the Key Safe Column closed (if available).

The Key Safe Controlling and Monitoring Device AD900-1 will generate an alarm signal if – e.g., 
by forcefully breaking into the Key Safe – one of these monitored states is violated insofar as caus-
ing the monitor loop's resistance to deviate more than 40% from normal condition.

DIN 14675 / chapter C.2.2.3: The report (sabotage report) must, under application according to 
Class FSD 3 (high risk), be forwarded to an office or authority that is available at all times, such 
as a police department or security company.

If the Key Safe has been unlocked by the confirmation signal, sabotage monitoring is disabled 
until a reset is performed correctly (see page 13 and onwards in chapter 2.4: "Fire alarm reset").

HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690
ZN62163/38/13

13

Содержание Fire Brigade Key FSK700 Series

Страница 1: ...by MEP Gefahrenmeldetechnik GmbH Fire Brigade Key Safe FSK700 2 FSK700 2SX User Manual Description Installation Connection Commissioning Maintenance VdS Approval G 199055...

Страница 2: ......

Страница 3: ...cylinder in the Locking Cylinder Mounting Bracket 16 3 5 3 Installation of additional locking half cylinders in Key Safe FSK700 2SX 17 3 5 4 Installation of the inner door 18 3 6 Installation of the F...

Страница 4: ...or FSK700 2SX PHZAW700 2S1 36 7 5 Auxiliary Locking Cylinder for FSK700 2 2SX PHZ700 2 36 7 6 Weather Protection Hood for FSK700 2 2SX WSD FSK 36 8 Certifications 37 8 1 VdS Certificate 37 8 2 EC Decl...

Страница 5: ...hrenmeldetechnik GmbH abbreviated MEP hereafter are distin guished by application of solid high quality materials as well as intelligent details in design achieving high security against unauthorised...

Страница 6: ...justing magnetic closure device automatically assumes the optimal position therefore the closure device is able to function at the highest precision level even during long time opera tion under unfavo...

Страница 7: ...chapter five commissioning of the Fire Brigade Key Safe is described in detail for the spe cialist installer In chapter six notes on inspection and maintenance of the unit are given Also described in...

Страница 8: ...nected controlling and monitoring device are fully operational Also take note of the advice given from page 15 onwards in chapter 3 5 Preparation of the Fire Brigade Key Safe as well as from page 29 o...

Страница 9: ...ocking cylinders compliant with VdS 2156 Class B with a length of 30 5mm Locking cylinder is not included 265748 Inner Door for FSK700 2 2SX PHZ 35 5mm ITA 3 Includes pre installed lock for locking cy...

Страница 10: ...ed for the safekeeping of master keys A key depot consists of a mechanically stable case of which the outer door can be electro magnetically unlocked by an unlocking device Located inside the key depo...

Страница 11: ...C of the European Parliament and of the Council regarding Electromagnetic Compatib ility EMC With the CE marking see page 38 in chapter 8 2 EC Declaration of Conformity the manufacturer confirms that...

Страница 12: ...ure device is rendered currentless 2 2 Fire alarm condition Fire alarm is reported to the fire brigade by the fire detection control panel using a transmitting device The fire brigade will transmit th...

Страница 13: ...nly available if the Key Safe is connected to the Key Safe Controlling and Monitoring Device AD900 1 by MEP also see page 28 and onwards in chapter 5 3 2 Acoustic warning signal when missing master ke...

Страница 14: ...ring of the Key Safe must be performed using a VdS certified controlling and monitoring device such as Key Safe Controlling and Monitoring Device AD900 1 MEP Art icle No 265900 Instructions for instal...

Страница 15: ...cement or similar from entering while setting the Flush Mounting Frame into the wall Protect the drill protection film inlaid in the Flush Mounting Frame with Drill Protection EZB S700 2 and the conn...

Страница 16: ...for the inner door angle The figure shows an already installed locking cylinder for the master key as well as an inner door including lock these parts are not pre installed in a newly shipped Key Safe...

Страница 17: ...S1 is required for every additional locking half cylinder Key Safe type FSK700 2 is not applicable for installation of additional locking half cylinders Installation is to be performed as follows Remo...

Страница 18: ...d by local authorities Install the variable lock in the inner door or with inner doors ITA 2 an ITA 3 insert the lock ing half cylinder into the lock and fix it using an M5 65mm countersunk head screw...

Страница 19: ...lumn through the lower cable lead through in the back wall of the Key Safe Be careful that the cable s do not get crushed between the back wall of the Key Safe and the Flush Mounting Frame and the com...

Страница 20: ...ade Key Safe are to be prepared as fol lows Trim the connection cable leading from the controlling and monitoring device to a length of approximately 60cm measured from the cable insertion opening The...

Страница 21: ...l endurance cable earth cable is used the insulation should be stripped off the cable starting at the cable insertion opening to ensure the small bend ing radius required inside the Key Safe can be ac...

Страница 22: ...s ible by removing Locking Cylinder Mounting Bracket No 1 see Fig 11 detail A on page 19 by which the L bracket can be removed as well Be careful that no cables get crushed during reassembly Key to Fi...

Страница 23: ...FSK700 2SX and Key Safe Controlling and Monitoring Device AD900 1 fire detection control panel transmitting device unblocking device Power Supply Unit for Heating Device NT700 1 as well as Flush Mount...

Страница 24: ...Safe Column the Drill Protection of the Flush Mounting Frame is to be connected to terminals 12 and 15 on the Connection Board as well as the 2 2k resistor colour code red red red included in the acc...

Страница 25: ...age of the fire detection control panel 12VDC or 24VDC is performed automatically Should the cable of the closure device not be properly connected to connector ST6 on Connec tion Board APL 4 the closu...

Страница 26: ...ion diagram for connecting a fire detection control panel to Series FSK700 Fire Brigade Key Safe Key Safe Controlling and Monitoring Device AD900 1 transmitting device as well as optional devices Unbl...

Страница 27: ...tion control panel 4 6 3 Connection diagram of a system comprising burglar alarm control panel and Fire Brigade Key Safe without fire detection control panel The example shows the burglar and sabotag...

Страница 28: ...epots Planung Einbau und Instandhaltung VdS 2350 it is possible that no insurance protection is available for damages due to burg lary in case the building has been opened using the real key taken fro...

Страница 29: ...the Key Safe is connected not to the Key Safe Controlling and Monitoring Device AD900 1 by MEP but to a controlling and monitoring device by another manufacturer some of its functional ity can differ...

Страница 30: ...nd connect pins 1 and 2 for the duration needed to measure the current see Fig 20 on page 28 Remember to press the jumper back down again after completing the measurement 5 Normal condition of the Key...

Страница 31: ...he Key Safe Column with Tamper Switch triggering the Tamper Switch 10M and returning it to normal position e g by lifting the top cover then reinstalling it Afterwards release the tamper switch of the...

Страница 32: ...e outside Clean the outer surface 1 2 Drill holes for water outlet on the bottom side must be free of residue Clean 3 Outer door alignment clearance flexibility Readjust grease the bearings 4 Function...

Страница 33: ...ies or the fire brigade is not required for this purpose To be able to measure resistances the appropriate wires must be disconnected from the Key Safe Controlling and Monitoring Device The values spe...

Страница 34: ...2V 8VDC UB 24V 16VDC Voltage with master key removed 0 5VDC Resistance with master key inserted 10M Resistance with master key removed 10 Table 3 Overview of the various states and corresponding nomin...

Страница 35: ...ons W H D 280 264 145 mm Weight without Flush Mounting Frame and inner door approx 16kg 1 The locking cylinder is not part of the product contents of the Fire Brigade Key Safe It is either provided as...

Страница 36: ...terial Back wall Sheet steel 3mm zinc coated Case Sheet steel 1mm zinc coated Resistance of the sabotage circuit 1 1k 5 Protective earth connection 4mm2 Dimensions W H D 275 245 160 mm Weight approx 3...

Страница 37: ...User Manual FSK700 2 FSK700 2SX Chapter 8 Certifications 37 8 Certifications 8 1 VdS Certificate Fig 22 VdS Certificate G 199055 HB_FSK700_1020_9161690_Englisch_D odt 1022 D AN9161690 ZN62163 38 37 37...

Страница 38: ...38 Chapter 8 Certifications User Manual FSK700 2 FSK700 2SX 8 2 EC Declaration of Conformity Fig 23 EC Declaration of Conformity HB_FSK700_1020_9161690_Englisch_D odt 1022 D AN9161690 ZN62163 38 38 38...

Отзывы: