Chapter 3   •  Installation

User Manual FSK700-2 / FSK700-2SX

The locking bolt supplied in the accessory kit must only be installed in the outer door after 
both the Fire Brigade Key Safe and the connected controlling and monitoring device are 
fully operational! Should the electrical unlocking device not be fully operational upon clos-
ing the outer door with installed locking bolt, the Key Safe can only be opened again by 
means leading to the destruction of some of its componentry (e.g., outer door, Drill Protec-
tion Board). Additional advice can be found on page 29 a
nd onwards in chapter 5.4: "Com-
missioning instructions"
.

3.5.1 

Removal of the inner door angle

For the tasks of installing the Fire Brigade Key Safe in the Flush Mounting Frame, setting up cable 
connections, as well as for the installation of the locking cylinder(s) for the master key(s), the inner 
door angle must be removed.
Removal of the inner door angle is to be performed as follows:

Open the outer and inner doors.

Remove all master keys.

Remove the 4 mounting screws on the inner door angle (see Fig. 6 below).

Pull out the inner door angle in a forward direction.

Fig. 6:

Location of the mounting screws for the inner door angle
The figure shows an already installed locking cylinder for the master key, as well as an inner  
door including lock – these parts are not pre-installed in a newly shipped Key Safe!

Reinstallation of the inner door after completion of the planned tasks is to be performed with the 
steps in reverse order.

3.5.2 

Installation of a locking half cylinder in the Locking Cylinder Mounting Bracket

Depending on the case of application, either a locking half cylinder identical to the locking mech-
anisms used on-site, or alternatively, an auxiliary locking cylinder (see page 10 and onwards in 
chapter 1.10: "Special terms") must be installed.

Locking cylinders that meet the requirements listed in the technical specifications on page 35 and 
onwards in chapter 7.1: "Fire Brigade Key Safe FSK700-2, FSK700-2SX" are to be used exclus-
ively.

Remove the inner door angle, see page 16 and onwards in chapter 3.5.1: "Removal of the inner
door angle"

Adjust the locking cam of the locking half cylinder so that it points downwards when assuming 
the key removal position, see Fig. 7 below.

Fig. 7:

Position of the locking cam with key removed

Insert the locking half cylinder into the Locking Cylinder Mounting Bracket and fix it in place 
using the M5×12mm hex head screw included in the accessory kit.

HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690

ZN62163/38/16

16

Содержание Fire Brigade Key FSK700 Series

Страница 1: ...by MEP Gefahrenmeldetechnik GmbH Fire Brigade Key Safe FSK700 2 FSK700 2SX User Manual Description Installation Connection Commissioning Maintenance VdS Approval G 199055...

Страница 2: ......

Страница 3: ...cylinder in the Locking Cylinder Mounting Bracket 16 3 5 3 Installation of additional locking half cylinders in Key Safe FSK700 2SX 17 3 5 4 Installation of the inner door 18 3 6 Installation of the F...

Страница 4: ...or FSK700 2SX PHZAW700 2S1 36 7 5 Auxiliary Locking Cylinder for FSK700 2 2SX PHZ700 2 36 7 6 Weather Protection Hood for FSK700 2 2SX WSD FSK 36 8 Certifications 37 8 1 VdS Certificate 37 8 2 EC Decl...

Страница 5: ...hrenmeldetechnik GmbH abbreviated MEP hereafter are distin guished by application of solid high quality materials as well as intelligent details in design achieving high security against unauthorised...

Страница 6: ...justing magnetic closure device automatically assumes the optimal position therefore the closure device is able to function at the highest precision level even during long time opera tion under unfavo...

Страница 7: ...chapter five commissioning of the Fire Brigade Key Safe is described in detail for the spe cialist installer In chapter six notes on inspection and maintenance of the unit are given Also described in...

Страница 8: ...nected controlling and monitoring device are fully operational Also take note of the advice given from page 15 onwards in chapter 3 5 Preparation of the Fire Brigade Key Safe as well as from page 29 o...

Страница 9: ...ocking cylinders compliant with VdS 2156 Class B with a length of 30 5mm Locking cylinder is not included 265748 Inner Door for FSK700 2 2SX PHZ 35 5mm ITA 3 Includes pre installed lock for locking cy...

Страница 10: ...ed for the safekeeping of master keys A key depot consists of a mechanically stable case of which the outer door can be electro magnetically unlocked by an unlocking device Located inside the key depo...

Страница 11: ...C of the European Parliament and of the Council regarding Electromagnetic Compatib ility EMC With the CE marking see page 38 in chapter 8 2 EC Declaration of Conformity the manufacturer confirms that...

Страница 12: ...ure device is rendered currentless 2 2 Fire alarm condition Fire alarm is reported to the fire brigade by the fire detection control panel using a transmitting device The fire brigade will transmit th...

Страница 13: ...nly available if the Key Safe is connected to the Key Safe Controlling and Monitoring Device AD900 1 by MEP also see page 28 and onwards in chapter 5 3 2 Acoustic warning signal when missing master ke...

Страница 14: ...ring of the Key Safe must be performed using a VdS certified controlling and monitoring device such as Key Safe Controlling and Monitoring Device AD900 1 MEP Art icle No 265900 Instructions for instal...

Страница 15: ...cement or similar from entering while setting the Flush Mounting Frame into the wall Protect the drill protection film inlaid in the Flush Mounting Frame with Drill Protection EZB S700 2 and the conn...

Страница 16: ...for the inner door angle The figure shows an already installed locking cylinder for the master key as well as an inner door including lock these parts are not pre installed in a newly shipped Key Safe...

Страница 17: ...S1 is required for every additional locking half cylinder Key Safe type FSK700 2 is not applicable for installation of additional locking half cylinders Installation is to be performed as follows Remo...

Страница 18: ...d by local authorities Install the variable lock in the inner door or with inner doors ITA 2 an ITA 3 insert the lock ing half cylinder into the lock and fix it using an M5 65mm countersunk head screw...

Страница 19: ...lumn through the lower cable lead through in the back wall of the Key Safe Be careful that the cable s do not get crushed between the back wall of the Key Safe and the Flush Mounting Frame and the com...

Страница 20: ...ade Key Safe are to be prepared as fol lows Trim the connection cable leading from the controlling and monitoring device to a length of approximately 60cm measured from the cable insertion opening The...

Страница 21: ...l endurance cable earth cable is used the insulation should be stripped off the cable starting at the cable insertion opening to ensure the small bend ing radius required inside the Key Safe can be ac...

Страница 22: ...s ible by removing Locking Cylinder Mounting Bracket No 1 see Fig 11 detail A on page 19 by which the L bracket can be removed as well Be careful that no cables get crushed during reassembly Key to Fi...

Страница 23: ...FSK700 2SX and Key Safe Controlling and Monitoring Device AD900 1 fire detection control panel transmitting device unblocking device Power Supply Unit for Heating Device NT700 1 as well as Flush Mount...

Страница 24: ...Safe Column the Drill Protection of the Flush Mounting Frame is to be connected to terminals 12 and 15 on the Connection Board as well as the 2 2k resistor colour code red red red included in the acc...

Страница 25: ...age of the fire detection control panel 12VDC or 24VDC is performed automatically Should the cable of the closure device not be properly connected to connector ST6 on Connec tion Board APL 4 the closu...

Страница 26: ...ion diagram for connecting a fire detection control panel to Series FSK700 Fire Brigade Key Safe Key Safe Controlling and Monitoring Device AD900 1 transmitting device as well as optional devices Unbl...

Страница 27: ...tion control panel 4 6 3 Connection diagram of a system comprising burglar alarm control panel and Fire Brigade Key Safe without fire detection control panel The example shows the burglar and sabotag...

Страница 28: ...epots Planung Einbau und Instandhaltung VdS 2350 it is possible that no insurance protection is available for damages due to burg lary in case the building has been opened using the real key taken fro...

Страница 29: ...the Key Safe is connected not to the Key Safe Controlling and Monitoring Device AD900 1 by MEP but to a controlling and monitoring device by another manufacturer some of its functional ity can differ...

Страница 30: ...nd connect pins 1 and 2 for the duration needed to measure the current see Fig 20 on page 28 Remember to press the jumper back down again after completing the measurement 5 Normal condition of the Key...

Страница 31: ...he Key Safe Column with Tamper Switch triggering the Tamper Switch 10M and returning it to normal position e g by lifting the top cover then reinstalling it Afterwards release the tamper switch of the...

Страница 32: ...e outside Clean the outer surface 1 2 Drill holes for water outlet on the bottom side must be free of residue Clean 3 Outer door alignment clearance flexibility Readjust grease the bearings 4 Function...

Страница 33: ...ies or the fire brigade is not required for this purpose To be able to measure resistances the appropriate wires must be disconnected from the Key Safe Controlling and Monitoring Device The values spe...

Страница 34: ...2V 8VDC UB 24V 16VDC Voltage with master key removed 0 5VDC Resistance with master key inserted 10M Resistance with master key removed 10 Table 3 Overview of the various states and corresponding nomin...

Страница 35: ...ons W H D 280 264 145 mm Weight without Flush Mounting Frame and inner door approx 16kg 1 The locking cylinder is not part of the product contents of the Fire Brigade Key Safe It is either provided as...

Страница 36: ...terial Back wall Sheet steel 3mm zinc coated Case Sheet steel 1mm zinc coated Resistance of the sabotage circuit 1 1k 5 Protective earth connection 4mm2 Dimensions W H D 275 245 160 mm Weight approx 3...

Страница 37: ...User Manual FSK700 2 FSK700 2SX Chapter 8 Certifications 37 8 Certifications 8 1 VdS Certificate Fig 22 VdS Certificate G 199055 HB_FSK700_1020_9161690_Englisch_D odt 1022 D AN9161690 ZN62163 38 37 37...

Страница 38: ...38 Chapter 8 Certifications User Manual FSK700 2 FSK700 2SX 8 2 EC Declaration of Conformity Fig 23 EC Declaration of Conformity HB_FSK700_1020_9161690_Englisch_D odt 1022 D AN9161690 ZN62163 38 38 38...

Отзывы: