20
Chapter 4 • Connection
User Manual FSK700-2 / FSK700-2SX
4
Connection
The locking bolt supplied in the accessory kit must only be installed in the outer door after
both the Fire Brigade Key Safe and the connected controlling and monitoring device are
fully operational! Should the electrical unlocking device not be fully operational upon clos-
ing the outer door with installed locking bolt, the Key Safe can only be opened again by
means leading to the destruction of some of its componentry (e.g., outer door, Drill Protec-
tion Board). Additional advice can be found on page 29 and onwards in chapter 5.4: "Com-
missioning instructions".
The connection between the controlling and monitoring device and the Fire Brigade Key Safe is to
be made continuously, as well as preferably in-wall, or protected by other means.
Before beginning to make the connections, disconnect the cables connected to Connection Board
APL-4 (closure device, Locking Cylinder Mounting Bracket, etc.), to gain additional working
space.
4.1
Preparation of the connection cables
The cables inserted through the back side of the Fire Brigade Key Safe are to be prepared as fol-
lows:
Trim the connection cable leading from the controlling and monitoring device to a length of
approximately 60cm (measured from the cable insertion opening).
The cables leading from the Drill Protection of Flush Mounting Frame EZBS700-2, as well as
those leading from the Tamper Switch of the Key Safe Column are not to be trimmed. The
excess length of these cables can be housed in the hollow space between the Flush Mounting
Frame and the Key Safe (approx. 17mm).
Strip off 15cm of the insulation of the cable leading from the controlling and monitoring device.
The cables leading from the Drill Protection of Flush Mounting Frame EZBS700-2, as well as
those leading from the Tamper Switch of the Key Safe Column have already been prepared
accordingly.
If a cable with a large outer diameter is used to connect the controlling and monitoring device,
it is suggested to strip the insulation off the cable (starting at the cable insertion opening), to
ensure the small bending radius required inside the Key Safe can be achieved.
Insert the cables into the Key Safe according to Fig. 12 below, and fix the cables in place using
the nylon cable clamp located right below the Connection Board.
HB_FSK700_1020_9161690_Englisch_D.odt / 1022 D / AN9161690