3.2. Detector Positioning In Atrium.

 

 

If the detector is to be placed in an atrium, or near glass/polished surfaces, the prism(s) should be offset from the central 
line of sight (approximately 300mm), and angled back to the beam detector. This can be either on the vertical or horizontal 
axis. This will reduce the amount of spurious returned signal from the glass/polished surfaces. The reflected signal from the 
prism(s) will be returned to the detector in the normal way. 

 
 
 
 
 
 
 
 
 

4. Installation. 

 
Pre-installation at Ground Level. 
 
Confirm that all parts have been supplied as listed in the parts list. See page 11. 
 
Select the required alarm threshold using switches 3 and 4 (See fig. 4. for switch configuration settings). The 
factory default setting is 35% this should be adequate for most environments, if the Detector is to be installed 
into an exceptionally dirty environment change the threshold to 50%. 
 
The Detector Head Assembly is now ready for installation. If switches 3 and 4 require resetting after installation, 
a power down reset is required (entering into Alignment Mode can also be used as a reset). 
 
 

4.1. Detector Head Assembly Installation.

 

 
Remove the outer cover before installation; this is only to prevent the cover becoming dislodged during 
handling. 
 

 

Do not mount on plasterboard or cladded walls as these surfaces do, and will move. 

 
Determine the position of the Head Assembly, which

 

must be mounted on a 

solid structure

 between 0.5 and 

0.6 metres below the ceiling, and no closer than 0.5 metres to an adjacent wall or structure. Ensure that there is 

clear line of sight

 to the proposed position of the prism, which is to be mounted on a solid structure between 

5 and 100 metres directly opposite the Detector (range dependent on model). 
 
Using the template provided mark and install all 4 fixing points to the structure. The rear mounting plate of the 
Detector Head Assembly is provided with 4 keyhole slotted apertures to allow for easy installation onto the 4 
fixing points. 
 
Replace the outer cover. 
 
Terminate the field wiring. See section 8. 
 
 

4.2. Prism Installation.

 

 

Due to the principle of the detector i.e. reflective, the prism must NOT be mounted on glass or a 
polished reflective surface. 

 
Mount the Prism on a 

solid structure

, 90º to the beam path, between 5 to 50 metres (MAB50R), and 50 to100 

metres (MAB50R) directly opposite the Detector. 
 

MAB50R =  

 

     MAB100R =  

1 Prism   

 

     4 Prisms 

 
 
 

Offset Prism(s) position and beam path 

Normal Prism(s) position and 

central line of sight 

Detector 
head 

Plan View 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание MAB100R

Страница 1: ...100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation MAB50R MAB100R Reflective Beam Detectors Addressable 22318 37 0...

Страница 2: ...tion page 4 5 5 Prism Targeting page 5 6 Alignment page 5 to 7 7 System Testing page 7 8 Connection and configuration Settings page 8 9 Detector Back View page 9 10 Beam Clearance page 10 11 Technical...

Страница 3: ...of the Detector The fault condition will reset within 5 seconds of the condition being rectified The Detector monitors long term degradation of signal strength caused by component ageing or build up o...

Страница 4: ...2 the lateral beam distance covered can be increased in relation to the angle of pitch up to a maximum of 25 For Example If the pitch angle is 20 degrees the lateral coverage can be increased from 7...

Страница 5: ...r before installation this is only to prevent the cover becoming dislodged during handling Do not mount on plasterboard or cladded walls as these surfaces do and will move Determine the position of th...

Страница 6: ...adjustment thumb wheels on two sides of the Detector positioned just behind the Detector Head cover Adjustment is achievable in both axes 6 1 Enabling Alignment Mode Do not remove the detector from t...

Страница 7: ...ode and enter the Operating Mode LED flashing Slowly adjust a thumbwheel in one direction and observe the LED s LED flashing For optimum alignment deflection of the beam in all four planes should caus...

Страница 8: ...fault 35 Select obscuration mark on filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of Detector Head opposite end to the status indicatio...

Страница 9: ...configuration settings is through the back plate of the Detector Head See Fig 4 The 4 way DIP is used to select the beams sensitivity 8 3 Typical Single Zone Wiring MAB50R MAB100R Connections Fire Pa...

Страница 10: ...22318 37 01 15 09 05 9 9 Detector Interface Assembly Configuration Settings Fig 4 www acornfiresecurity com www acornfiresecurity com...

Страница 11: ...re should be at least 0 5m diameter clearance down the entire beam path If there are highly reflective objects within 1 metre diameter of the beam path for the first 20 metres of the beam path for the...

Страница 12: ...urrent into direct short circuit isolator open 13mA max Parallel Fault Resistance to be seen at the Control Panel for isolators to open 200 typ 12 Service Application Notes For full compliance with BS...

Отзывы: