6.4. Exiting Alignment Mode.

 

 

Do not remove the detector from the wall during this action. 

 

Using the mode switch (See fig. 4) select Run Mode (Switch will be in the down position).  
 
On exiting alignment mode the Detector will perform an internal calibration check. If this fails, which would be 
due to bad alignment or either electrical or optical noise, the power level will try to compensate. If, after 60 
seconds, the power level is still not correct, a Fault will be signalled to the control panel. The alignment 
procedure must be repeated. 
 
If the internal calibration check completes satisfactory, the Detector will enter its normal running mode. 
 

7. System Testing. 

 
After successful installation and alignment the System will require testing for both alarm and fault conditions. 
 

7.1. Alarm (smoke) Test.

 

 

Taking note of the threshold selected during installation (default 35%). 

 

Select obscuration mark on filter to correspond with the Detector alarm threshold (see fig. 3). 

 

Place the filter over the receiver optics (Top of Detector Head 

 opposite end to the status indication LED’s) at 

the correct obscuration value determined by the threshold selected, i.e. if a threshold of 35% has been selected 
position the filter just past the 35% obscuration value on the filter (see fig 3.). 

 

Take care not to cover the transmitter optics. 

 

The Detector will indicate a fire within 10 seconds by illuminating the Red LED and activating the panel. 
 

7.2. Fault Test.

 

 
Cover the Prism totally with a non-reflective material and confirm that the Detector signals to the control panel a 
fault condition after approximately 10 seconds. When the prism is uncovered, the fault condition will 
automatically reset after a period of 10 seconds when the obstruction is removed. 
 
 
 

      

 

 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 3. 

Í

 obscuration value 

Align filter for correct obscuration/threshold setting 

Transmitter Optics 

Receiver Optics 

Status Indication LED’s 

RED 

AMBER

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание MAB100R

Страница 1: ...100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation MAB50R MAB100R Reflective Beam Detectors Addressable 22318 37 0...

Страница 2: ...tion page 4 5 5 Prism Targeting page 5 6 Alignment page 5 to 7 7 System Testing page 7 8 Connection and configuration Settings page 8 9 Detector Back View page 9 10 Beam Clearance page 10 11 Technical...

Страница 3: ...of the Detector The fault condition will reset within 5 seconds of the condition being rectified The Detector monitors long term degradation of signal strength caused by component ageing or build up o...

Страница 4: ...2 the lateral beam distance covered can be increased in relation to the angle of pitch up to a maximum of 25 For Example If the pitch angle is 20 degrees the lateral coverage can be increased from 7...

Страница 5: ...r before installation this is only to prevent the cover becoming dislodged during handling Do not mount on plasterboard or cladded walls as these surfaces do and will move Determine the position of th...

Страница 6: ...adjustment thumb wheels on two sides of the Detector positioned just behind the Detector Head cover Adjustment is achievable in both axes 6 1 Enabling Alignment Mode Do not remove the detector from t...

Страница 7: ...ode and enter the Operating Mode LED flashing Slowly adjust a thumbwheel in one direction and observe the LED s LED flashing For optimum alignment deflection of the beam in all four planes should caus...

Страница 8: ...fault 35 Select obscuration mark on filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of Detector Head opposite end to the status indicatio...

Страница 9: ...configuration settings is through the back plate of the Detector Head See Fig 4 The 4 way DIP is used to select the beams sensitivity 8 3 Typical Single Zone Wiring MAB50R MAB100R Connections Fire Pa...

Страница 10: ...22318 37 01 15 09 05 9 9 Detector Interface Assembly Configuration Settings Fig 4 www acornfiresecurity com www acornfiresecurity com...

Страница 11: ...re should be at least 0 5m diameter clearance down the entire beam path If there are highly reflective objects within 1 metre diameter of the beam path for the first 20 metres of the beam path for the...

Страница 12: ...urrent into direct short circuit isolator open 13mA max Parallel Fault Resistance to be seen at the Control Panel for isolators to open 200 typ 12 Service Application Notes For full compliance with BS...

Отзывы: