background image

 

 

 

 

 

22318.37.01     15.09.05

 

2

 

 

 

 

 

 

 

1. System Description. 

 

Cooper Lighting and Security MAB50R / MAB100R detectors comprise a Transmitter and Receiver contained 
within one enclosure. 
 
The Detector installs to the building fabric between 0.5 and 0.6 metres from the ceiling. 
 
The Transmitter emits an invisible infrared light beam that is reflected via a prism mounted directly opposite and 
within a clear line of sight. The reflected infrared light is detected by the Receiver and analysed. 
 
The Detector has maximum lateral detection of 7.5 metres either side of the beam. 
 

 

2. System Operation. 

 

Smoke in the beam path will reduce the received infrared light proportionally to the density of the smoke. The 
Detector analyses this attenuation or obscuration of light and acts accordingly. 
  
Alarm thresholds of 25%, 35%, and 50% can be selected to suit the environment, where 25% is the most 
sensitive. If the received infrared signal reduces to below the selected threshold, and is present for 
approximately 10 seconds, a Fire condition is activated. 
 
The Fire condition will automatically reset after 10 seconds once the beam signal increases above the selected 
fire threshold.  
 
If the infrared beam is obscured rapidly to a level of 90% or greater for approximately 10 seconds a Fault 
condition is activated. 
This condition can be entered in a number of ways, for example, an object being placed in the beam path, 
transmitter failure, loss of the prism, or sudden misalignment of the Detector. The fault condition will reset within 
5 seconds of the condition being rectified. 
 
The Detector monitors long term degradation of signal strength caused by component ageing or build up of dirt 
on optical surfaces. This operates by comparing the received infrared signal against a standard every 15 
minutes; differences of less than 0.7dB/Hour are corrected automatically. 
 

 

3. Detector Positioning. 

 

It is important that the MAB50R / MAB100R detectors are positioned correctly to minimise the detection time. 
 
Experiments have shown that smoke from a fire does not rise directly upwards, but fans out or mushrooms due 
to air currents and heat layering effects. The time to signal a fire condition depends on the location of the 
Detector within the premises, the volume and density of smoke produced, construction of the roof, ventilation 
arrangements and airflow within the detection area. 
 
Smoke layering, where smoke does not reach the ceiling level due to layers of static hot air is overcome by 
mounting the Detector/Prism(s) at the recommended height below the ceiling of between 0.5 and 0.6 metres, 
bringing the infrared beam below the heat layer and into the smoke layer. However, if there are objects below 
the ceiling that could obscure the beam path, the detector/prism(s) positioning may need to be adjusted. This is 
to allow for a beam path clearance radius of 0.5 metres. 
 
The maximum distance either side of the beam axis is found to be typically 7.5 metres for satisfactory detection 
under flat ceilings. 
 
 
 
 
 
 
 
 
 

Single Beam 

15 m 

15 m 

0.5 

 7.5 m

Multiple Beams 

0.5 to 0.6 m

0.5 

 7.5 m

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание MAB100R

Страница 1: ...100 Metres Unique simple alignment Loop powered Selectable alarm thresholds Low current consumption Automatic contamination compensation MAB50R MAB100R Reflective Beam Detectors Addressable 22318 37 0...

Страница 2: ...tion page 4 5 5 Prism Targeting page 5 6 Alignment page 5 to 7 7 System Testing page 7 8 Connection and configuration Settings page 8 9 Detector Back View page 9 10 Beam Clearance page 10 11 Technical...

Страница 3: ...of the Detector The fault condition will reset within 5 seconds of the condition being rectified The Detector monitors long term degradation of signal strength caused by component ageing or build up o...

Страница 4: ...2 the lateral beam distance covered can be increased in relation to the angle of pitch up to a maximum of 25 For Example If the pitch angle is 20 degrees the lateral coverage can be increased from 7...

Страница 5: ...r before installation this is only to prevent the cover becoming dislodged during handling Do not mount on plasterboard or cladded walls as these surfaces do and will move Determine the position of th...

Страница 6: ...adjustment thumb wheels on two sides of the Detector positioned just behind the Detector Head cover Adjustment is achievable in both axes 6 1 Enabling Alignment Mode Do not remove the detector from t...

Страница 7: ...ode and enter the Operating Mode LED flashing Slowly adjust a thumbwheel in one direction and observe the LED s LED flashing For optimum alignment deflection of the beam in all four planes should caus...

Страница 8: ...fault 35 Select obscuration mark on filter to correspond with the Detector alarm threshold see fig 3 Place the filter over the receiver optics Top of Detector Head opposite end to the status indicatio...

Страница 9: ...configuration settings is through the back plate of the Detector Head See Fig 4 The 4 way DIP is used to select the beams sensitivity 8 3 Typical Single Zone Wiring MAB50R MAB100R Connections Fire Pa...

Страница 10: ...22318 37 01 15 09 05 9 9 Detector Interface Assembly Configuration Settings Fig 4 www acornfiresecurity com www acornfiresecurity com...

Страница 11: ...re should be at least 0 5m diameter clearance down the entire beam path If there are highly reflective objects within 1 metre diameter of the beam path for the first 20 metres of the beam path for the...

Страница 12: ...urrent into direct short circuit isolator open 13mA max Parallel Fault Resistance to be seen at the Control Panel for isolators to open 200 typ 12 Service Application Notes For full compliance with BS...

Отзывы: