VALUE
Description
Backup
Settings
Perform a backup of the settings made.
The settings in “Installation Data”,
“Production Settings” and “User
Settings” (except “Wallbox Date and
Time Configuration”) are saved and the
backup file is downloaded.
Download
System Logfile
Download a log file.
This is designed for fault finding and
can only be read by MENNEKES.
Restore Data
from Backup
Upload the file downloaded in “Backup
Settings”.
The settings saved in the file are
applied.
The IP settings and the name of
the device are overwritten when
restoring a backup. This may
cause an IP address conflict after
the restart.
f
Disconnect the device from
the network and reset the IP
address and the name.
To speed up initial installa-
tion of multiple AMTRONs
with the same settings, use
a (master) backup with acti-
vated DHCP. After restor-
ing, configure the network
settings of the AMTRONs
on each device individually.
Firmware
Update
Upload the current operating software
of the device
Reboot
Restart the device
Procedure “Firmware Update”
The current operating software can be downloaded at
www.AMTRON.info.
f
Enter the address www.AMTRON.info into the address
bar of your Internet browser.
f
Enter the serial number of your device in the input field
“Access”.
f
In the “Download” section, select the “Software
Update” button
f
Download and save the current software (name e.g.
HCC3Application.bin)
f
In the service interface to “System” > “Firmware
Update”
f
Select the downloaded operating software.
f
Click on the button “Update AMTRON” to update the
software.
f
Follow the instructions.
If the update is interrupted prematurely (e.g. due
to power failure), the device must be restarted
(e.g. by the “Reboot” button) before a new update
can be attempted.
6.5 Checking the device
Test according to IEC 60364 (in Germany according to
DIN VDE 0100) as well as national regulations
During the first commissioning and in the specified main-
tenance intervals, carry out a test of the charging station
in accordance with IEC 60364 (in Germany in accordance
with DIN VDE 0100) and the respective applicable national
regulations. The test can be carried out in connection with
the MENNEKES test box and a standard-compliant test
equipment. The MENNEKES test box simulates vehicle
communication. Test boxes are available as accessories
from MENNEKES.
f
Perform a standard test before the device release.
Operating instructions of the test box.
Содержание AMTRON Premium E
Страница 2: ......
Страница 348: ...6 3 3 1 1 2 3 4 5 6 7 RFID 1 8 2 1 9 1 3 2 1 2 3 4 5 6 1 1 2 2 1 1 4 5 2...
Страница 350: ...8 3 4 RFID Premium E RFID Xtra E Premium R RFID Xtra R Premium W RFID Premium RFID Xtra...
Страница 352: ...10 5 T T f f f f f f 5 1 4 5 2 T T f f T T f f f f f f f f f f 25 40 C 24 35 C 2 000 95 5 3 T T f f...
Страница 354: ...12 5 4 2 1 f f f f 2 f f 3 4 5 5 24 8 4 3 3 1 1 2 5 5 1 5 5 2 MENNEKES f f 1 9 300 300 300 300 10 1...
Страница 355: ...13 RU f f f f 45 f f f f 1 2 3 f f 11 5 6 5 6 1 f f 370 f f 12 f f 2 1 f f 5 6 2 WLAN Ethernet RJ45 WLAN 12 1 2...
Страница 411: ......