16
5.7 Set up three-phase device for single-phase
operation
For single-phase operation of a three-phase device (for
devices with 11 or 22 kW charging power), the potentiom-
eter at the phase sequence relay must be changed.
L1
L2
L3
1 3
N
X
X
16
15 18
f
Connect the device to single phase.
To do this, use the terminals L1, N and PE.
f
Adjust potentiometer (
1
) to position 1 using a slotted
screwdriver.
f
Tick checkbox “Monitoring Relay Wired to 1 Phase Only”
in service interface.
Î
“6.4.2 Menu “Installation Settings””
Setting
Description
1
Single-phase operation
3
Three-phase operation
1
5.8 Closing the device
f
Lift the front panel
(
1
)
upwards and secure it with the
screws
(
2
).
f
Fit the upper part of the enclosure (
3
) and secure it with
the screws (
4
)
and (
5
). Use supplied shortened Allen
key.
Fig.: 16. Closing the device
2
4
3
1
2
5
Содержание AMTRON Premium E
Страница 2: ......
Страница 348: ...6 3 3 1 1 2 3 4 5 6 7 RFID 1 8 2 1 9 1 3 2 1 2 3 4 5 6 1 1 2 2 1 1 4 5 2...
Страница 350: ...8 3 4 RFID Premium E RFID Xtra E Premium R RFID Xtra R Premium W RFID Premium RFID Xtra...
Страница 352: ...10 5 T T f f f f f f 5 1 4 5 2 T T f f T T f f f f f f f f f f 25 40 C 24 35 C 2 000 95 5 3 T T f f...
Страница 354: ...12 5 4 2 1 f f f f 2 f f 3 4 5 5 24 8 4 3 3 1 1 2 5 5 1 5 5 2 MENNEKES f f 1 9 300 300 300 300 10 1...
Страница 355: ...13 RU f f f f 45 f f f f 1 2 3 f f 11 5 6 5 6 1 f f 370 f f 12 f f 2 1 f f 5 6 2 WLAN Ethernet RJ45 WLAN 12 1 2...
Страница 411: ......