background image

 

GAS  SUPPLY  REQUIREMENTS 

 

CORRECT  GAS  PRESSURE  AND  PROPER  GAS  SUPPLY  LINE  SIZING  ARE  CRITICAL  TO  THE  SUCCESSFUL  
PERFORMANCE  OF  YOUR  X-62  GAS  LOG  INSERT.    BE  SURE  THAT THE  GAS  SUPPLIER  OR  PLUMBER  CHECKS  FOR  
CORRECT  GAS  PRESSURE  AND  GAS  LINE  SIZING  WHEN  INSTALLING  THE  APPLIANCE. 
GAS  SUPPLY  PIPING  MUST  INCLUDE  A  DRIP  LEG  TO  ELIMINATE  THE  POSSIBILITY  OF  CONTAMINANTS  ENTERING  THE  
GAS  TRAIN.    MANY  LOCAL  CODES  ALSO  REQUIRE  A  SHUT  OFF  VALVE  ON  THE  INCOMING  GAS  LINE.    ADHERE  
STRICTLY  TO  LOCAL  AND  NATIONAL  CODES. 
IF GAS  SUPPLY  PRESSURES  EXCEED ½  PSIG  [3.5KPA],  THE  APPLIANCE  MUST  BE  ISOLATED  FROM  ITS  SUPPLY  WITH  
AN  APPROVED  MANUAL  SHUT-OFF  VALVE.    THIS  MANUAL  SHUT-OFF  VALVE  MUST  BE  CLOSED  DURING  ANY  SUPPLY  
LINE  PRESSURE  TESTING. 

 

GAS  SUPPLY  LINE  SIZING 

The X-62 comes equipped with a 3/8" N.P.T. [1.0 cm] inlet on the main gas valve. 
 
A gas line of sufficient size to deliver 63,000 BTUH to the unit at the normal inlet pressure must be run from the 
supply regulator to the appliance.  Refer to the following table and to local codes to determine the correct pipe 
diameter. 

 

PIPE  LENGTH 

SCHEDULE  40  PIPE  (INSIDE  DIA.) 

TUBING,  TYPE  L  (OUTSIDE  DIA.) 

 
    FEET   

(

Meters

)

 

  NAT. 

  IN   

(

CM

)

 

 L.P. 

  IN   

(

CM

)

 

  NAT. 

  IN   

(

CM

)

 

 L.P. 

  IN   

(

CM

)

 

      0 - 10   (0 - 3.1) 

1/2   (1.3) 

3/8   (1.0) 

1/2   (1.3) 

3/8   (1.0) 

    10 - 40   (3.1 - 12.2) 

1/2   (1.3) 

1/2   (1.3) 

5/8   (1.6) 

1/2   (1.3) 

  40 - 100   (12.2 - 30.5) 

3/4   (2.0) 

1/2   (1.3) 

3/4   (2.0) 

1/2   (1.3) 

100 - 150   (30.5 - 45.7) 

3/4   (2.0) 

1/2   (1.3) 

7/8   (2.3) 

5/8   (1.6) 

150 - 200   (45.7 - 61.0) 

3/4   (2.0) 

1/2   (1.3) 

7/8   (2.3) 

3/4   (2.0) 

Some areas allow the use of copper tubing or galvanized pipe.  Check with local approval agencies and codes.  NEVER use plastic pipe.

 

 

GAS  PRESSURE  REQUIREMENTS 

 

A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLIANCES IS IMPROPER GAS PRESSURE! 

 
Such problems as changes in flame color or configuration, pilot or burner outages, intermittent operation, changes 
in heat output, excessive burner noise, etc. can be the result of changes in gas pressure or improper gas pressure 
at the time of installation.  The most important item to check during installation, and the first thing to check when 
problems occur, is gas pressure! 
 
The natural gas supply normally enters a residence at ½ PSI [13‖ - 15‖ W.C.] [3.5 KPA].  A regulator located inside 
the residence drops this pressure to 7‖ W.C. [1.8 KPA].  This ―inches to inches‖ regulator is sufficient to service 
the existing gas appliances (stove, dryer, furnace, etc.).  If the capacity of the regulator is not sufficient for the 
addition of the X-

62, a second ―inches to inches‖ regulator must be installed.  EXCEPTION: Some codes allow 2 

PSI [1.4 KPA] gas supplies to enter the residence, in which case ―pounds to inches‖ regulators are used. 
 
The following table provides information on the requirements for correct gas pressure.  Be sure your gas supplier 
or plumber follows these requirements carefully. 
 

INLET  GAS  PRESSURE 

 

DESIRED 

PRESSURE 

MINIMUM 

PRESSURE 

MAXIMUM 

PRESSURE 

MANIFOLD 

PRESSURE * 

AIR  SHUTTER 

OPENING 

NATURAL  
GAS 

7.0‖ W.C. 

(1.75 kPa) 

6.5‖ W.C. 

(1.12 kPa) 

10.5‖ W.C. 

(2.61 kPa) 

3.5‖ W.C. 

(0.87 kPa) 

1/4 ‖  

(6 mm) 

L.P. GAS 

11.0‖ W.C. 

(2.75 kPa) 

12.2‖ W.C. 

(2.75 kPa) 

13.0‖ W.C. 

(3.24 kPa) 

10.0‖ W.C. 

(2.5 kPa) 

7/16 ‖ 

(13 mm) 

*  A pressure tap fitting is located on the gas valve (see Fig. 4).  A qualified installer must  measure the manifold 

pressure at this fitting with the burner operating on its highest setting.  Gas pressure may vary by ± 5%. 

Содержание X-62

Страница 1: ...il QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez aucun interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous vous trouvez Appelez...

Страница 2: ...S 7 W C 6 5 W C MIN 10 5 W C MAX L P GAS 11 W C 12 2 W C MIN 13 W C MAX GAS INLET 3 8 N P T INTERTEK TESTED TO AGA ANSI STANDARD Z21 60 2003 CAN CGA 2 26 M03 CGA CR93 0004 This appliance may be used w...

Страница 3: ...outside in accordance with the latest edition of the Natural Fuel Gas Code Do not connect this appliance to a chimney flue serving a separate solid fuel burning appliance The X 62 is a decorative gas...

Страница 4: ...E 4 V A LV E P R E S S U R E T A P F IT T IN G F O R T E S T IN G M A N IF O LD P R E S S U R E B LO W E R A D JU S T M E N T D A M P E R O P E N N A T L P C O N V E R S IO N S T E M R E D R E D B LA...

Страница 5: ...uld not be installed in any fireplace that is normally subject to severe downdrafts Downdraft conditions exist if when starting a wood fire it is difficult to establish a good upward draw i e smoke an...

Страница 6: ...ies and codes NEVER use plastic pipe GAS PRESSURE REQUIREMENTS A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS APPLIANCES IS IMPROPER GAS PRESSURE Such problems as changes in flame color or configuration...

Страница 7: ...uired by local codes or if the supply gas pressures exceed PSIG 3 5KPA and a regulator of sufficient capacity b Flex hose used to connect the appliance must have brass to brass fittings c The gas pres...

Страница 8: ...to L P Gas remove the rubber cap that covers the valve conversion stem Depress the stem and rotate it clockwise until it locks in place in the depressed position Replace the rubber cap See Fig 4 page...

Страница 9: ...ls Spread the coals on top of the burner to produce a glowing ember effect and also around the base of the burner to conceal it see Fig 6 DO NOT spread any coals over the slots at the front of the app...

Страница 10: ...f the flame improves Tighten the nut of the air shutter Replace the front vent plate and screw it to the firebox floor NOTE If sooting persists turn off the appliance and call your Mendota dealer 19 I...

Страница 11: ...of the grate bar as shown Make sure that the log is tight against the back of the firebox Place the notch on log 2 over the left grate bar Slide log 2 back against the tabs that are located on the to...

Страница 12: ...osition pinned log 6 so that its left end is in contact with the right end of log 2 Log 3 rests on log 2 with its right end against the grate bar as shown in the circled area Log 5 rests in the notche...

Страница 13: ...nuously until it is turned off Press the HI button on the remote to operate the appliance with maximum flame and heat Press the LOW button on the remote to operate the appliance with minimum flame and...

Страница 14: ...The gas supply is turned off C The batteries in the remote and or receiver need replacing D The remote needs to be synchronized with the receiver E The pilot assembly is dirty F Any other cause A Mak...

Страница 15: ...valve and the air shutter on the venturi Use a brush or wire to clean the inlet of the venturi Clean foreign matter and carbon deposits from the burner pan and burner tiles Check to see that the burne...

Страница 16: ...COALS HA 74 00028 VALVE ASSEMBLY 05 02 00331 VALVE 05 02 00330 VALVE SOLENOID HA 74 00003 BURNER ASSEMBLY 05 04 00045 PILOT ASSEMBLY 65 14 00025 NATURAL GAS ORIFICE 25 65 14 00043 L P GAS ORIFICE 43...

Страница 17: ...the back of the firebox and the brick pattern must face forward NOTE The rear brick panel is held in place by the left and right brick panels DO NOT let the rear panel fall forward before the side pan...

Страница 18: ...18 NOTES...

Страница 19: ..._____________________________ DATE INSTALLED __________________________________ REF X 62 INSTALLATION MANUAL THE EXISTING FIREPLACE CHIMNEY MEET ALL OF THE REQUIREMENTS see page 5 THE GAS SUPPLY MEETS...

Страница 20: ...20...

Страница 21: ...nty does not cover glass or log breakage Cracks in the burner ceramic plaques is normal and not covered under warranty unless pieces of the ceramic are missing Mendota has the right to investigate and...

Страница 22: ...22 Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division 85 03 00738 C...

Отзывы: