LP GAS PRESSURE REQUIREMENTS
Inlet and manifold gas pressure checking taps are located on gas valve. These ports are only accessible from the
outer left side of the fireplace. A qualified installer shall take pressure measurements at these ports to verify and
set the correct gas pressures during the LP Kit installation and before facia materials are installed over the front of
this fireplace.
Manifold pressure must be taken at the “MANIFOLD PRESSURE" tap and inlet pressure at the
"INLET PRESSURE" tap
with the burner
operating
by a qualified installer.
DESIRED
INLET
PRESSURE
MINIMUM
INLET
PRESSURE
MAXIMUM
INLET
PRESSURE
MANIFOLD
OUTLET
PRESSURE
AIR SHUTTER
POSITION
L.P. GAS
11.0" W.C
.
(2.75 kPa)
11" W.C.
(2.75 kPa)
13.0" W.C.
(3.24 kPa)
10.0" W.C.
(2.5 kPa)
1/4" OPEN MIN.
(5 mm)
REGULATE THE FLAME HEIGHT TO "HIGH" POSITION. OUTLET GAS PRESSURES MAY VARY PLUS OR MINUS 5%.
LPG PROPER INPUT RATES:
With the proper orifices installed, as specified above, this
fireplace utilizing LP Gas will have a maximum input rate of
31,000 Btu/Hr.
LEAK TESTING REQUIREMENTS
Prior to completing the conversion process
, c
heck for gas
leaks with soap and water solution at all plumbing joints
prior to placing this appliance into operation. It is recom-
mended that all gas-plumbing joints, factory installed and
field installed are checked for leaks.
PILOT FLAME AND MAIN BURNER
RELATIONSHIP VERIFICATION
Prior to completing the conversion process, the qualified
service technician must, light the pilot light and verify the relationship between the
pilot light flames and the main burners. The pilot light flames directed towards the propagation ports on the rear
and front burner must overlap the propagation ports on the burners. The pilot light flames must be a minimum of
¾” long and must overlap the propagation ports on both the rear and front burners as shown in the diagram, be-
low. Verify that the burner tubes ignite quickly and the burner flames propagate smoothly along the entire length
of the burners.
PILOT FLAME LENGTH ADJUSTMENT
If the pilot light flame length is too short and the system
does not maintain a standing pilot, a qualified installer
may increase the length of the pilot light flames to meet
the two requirements: Minimum pilot light length to
maintain a standing pilot light and the pilot light flames
must be long enough to overlap the front and rear burn-
er ports.
Figure 1: Pressure Test Port
1" MIN.
FRONT
BURNER
REAR
BURNER
PILOT LIGHT FLAMES
MUST OVERLAP
BURNER PORTS.