background image

4

The  outlet  from  the  chimney  should  be  above  the  roof  of  the  building  in  accordance  with  the  provisions  of    Building

Regulations Approved Document J. If installation is into an existing chimney then it must be sound and have no cracks or
other faults which might allow fumes into the house. Older properties, especially, may have chimney faults or the cross
section may be too large .

Mendip Stoves recommend the use of a solid fuel flue lining system for all installation into existing chimneys. All chimney
systems must be used in accordance with Building Regulations Approved Document J.

If an existing chimney  is used the  chimney must be clear of obstruction and  be swept clean immediately before installation
of the stove. The chimney should be tested to confirm the chimney will provide the correct chimney pressure for the stove.
If the stove is fitted in place of an open fire  the chimney should be swept one month after installation to clear any soot falls
which may have occurred due to the difference in combustion between the stove and the open fire. If there is no existing
chimney then either a prefabricated block chimney in accordance with Building Regulations Approved Document J or a twin
walled insulated stainless steel flue to BS 1856-1 . These chimneys must be fitted in accordance with the manufacturer’s
instructions and Building Regulations. A single wall metal flue pipe is suitable for connecting the stove to the chimney but
is not suitable for using for the complete chimney. The chimney and connecting flue pipe must have a minimum diameter
of 150 mm and its dimension should be not less than the size of the outlet socket of the stove. Any bend in the chimney or
connecting flue pipe should not exceed 45

°

.  90

°

 bends should not be used other than  within 150 mm of stove rear flue

outlet.

A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of the chimney

should be satisfactory. Alternatively the calculation procedure given in BS5854:1980 may be used as the basis for deciding
whether a particular chimney design will provide sufficient draught.

If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternately a draught
stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should in its closed position
leave a minimum continuous opening free area of at least 20 % of the total cross sectional area of the flue or flue pipe.

Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and connecting flue

pipe.

Your appliance needs to be maintained routinely, the throat plate/baffle should be cleaned regularly (monthly) . The flue

pipe can be cleaned using a flexible brush. Only Use a dry cloth on external surfaces. Over time the glass may become
dirty, clean with a damp cloth and polish off with damp cloth.  If the stove has not been used for some time  the flue
should be checked for blockages before use. Do not modify the appliance; only use spares authorised by the

FLUE & CHIMNEY CONNECTION TO STOVE

Chimney Connection

In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate
draught to clear the products of combustion and prevent smoke problems into the room.

Tested Gas flow rates flue
gas temperatures

Flue gas flow rate
Wood /coal

Test flue gas temperature
wood /coal

@ pascals of pressure

Burcott

2.8/4.0g/sec

217/184 deg C

12 pa

Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues could

ignite it. Therefore when installing the stove in the presence of combustible materials due account must be taken of the
guidance on the separation of combustible material given in Building Regulations Approved Document J and also in these
stove instructions.

Distance to
combustibles above

Distance to
combustbles  sides

Distance to
combustibles  sides
Convection models

Suitable for 12mm
non-combustible floor
plate

Burcott

300mm

75mm

N/a

N/a

DISTANCE TO COMBUSTIBLE MATERIALS

Содержание Burcott Multi-fuel

Страница 1: ...Burcott Fireplace inset stove ENG FR OPERATION AND INSTALLATION MANUAL Multi fuel and SE models Guide d utilisation et Mode d Emploi...

Страница 2: ...blems Please note that all local regulations including those referring to national and European Standards need to be complied with when installing this appliance For further information on installing...

Страница 3: ...fitted in the same room as the appliance Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufacturer s instructions Provision of...

Страница 4: ...actory Alternatively the calculation procedure given in BS5854 1980 may be used as the basis for deciding whether a particular chimney design will provide sufficient draught If it is found that there...

Страница 5: ...liance from the opening 2e Using a masonry bit drill corresponding holes in the hearth and fit 1 x 6mm floor bolt 2f The appliance is now ready to be secured to the hearth afterthe flue system has bee...

Страница 6: ...ppliances can be affected by temporary atmospheric conditions which may allow fumes to enter the house Building regulations require that whenever a new or replacement fixed solid fuel or wood biomass...

Страница 7: ...STOVE DIMENSIONS AND CONNECTION MEASUREMENTS...

Страница 8: ...x 7cm x 6 cm Output wood fuel Efficiency CO 13 o2 Recommended for smoke control Oct 2014 Output coal fuel Efficiency CO 13 o2 Burcott 4 1kw 83 0 38 YES 3 9kw 79 0 36 Mendip Stoves Burcott models are...

Страница 9: ...oor of the combustion chamber HEARTH COMBUSTION AIR COMBUSTION CHAMBERS Mendip Stoves are fitted internally with vermiculite heat deflection panels and baffles these panels are designed to ensure the...

Страница 10: ...TIME Before lighting your stove for first time make sure you have read this manual fully and acquainted yourself with the controls of this appliance see page 9 The heat resistant paint on your stove w...

Страница 11: ...t closed To Open door lift handle To close push door closed and push handle down until located When opening the door of your Mendip stove always wear the glove that is provided to protect your hand fr...

Страница 12: ...e the primary slider again 6 Once established close the secondary air slider by 50 for the stove to burn cleanly plenty of secondary air is needed do not be tempted to shut the fire down too early as...

Страница 13: ...ld not be attempted Mendip smoke control stoves should not be burnt with the door left open The refuelling procedure allow the newly charged fuel to burn with the secondary air control set at maximum...

Страница 14: ...ed when operating air controls and door Re fueling solid fuel To re fuel your stove Before refuelling open Primary and secondary air controls to fully open Open door gently and de ash your stove with...

Страница 15: ...cleanly if it is burnt hotter Mendip stoves do not recommend that their stoves are burnt overnight for this reason As a night time regime we recommend that the fire is loaded when hot and burnt for fi...

Страница 16: ...there is an adequate air supply into the room e that an extractor fan is not fitted in the same room as the fire 2 Fire Blazing Out Of Control check a the doors are tightly closed b the air controls a...

Страница 17: ...le po le est en cours d utilisation Votre po le comprend les l ments suivants dans le po le This section shows the parts contained in your stove each stove has over 80 spare parts and each part is det...

Страница 18: ...Baffle plate and remove left front brick Then remove steel baffle plate This will leave the flue free for cleaning Fig 5 Slide rear brick to the left and remove Fig 3 Fig 4 Fig 1 Fig 2 Fig 5 Fig 1 Bur...

Страница 19: ...with the front right brick the front brick has a routed out section for the handle mount to fit see fig 9 Place the bricks back in the chamber as they where taken out Ensure the baffle is put back in...

Страница 20: ...Somerset BS26 2UG Tel 01934 750 500 Fax 01173 156 207 www Mendipstoves co uk E mail info mendipstoves co uk Distribu en France par la soci t Distributed in France and Benelux by Eurostove SAS Centre...

Отзывы: