Installation manual
M-WRG-S/Z-T(-F, -FC)
- 10 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
6 Connecting 2 to 5 ventilation units
Up to five ventilation units can be controlled with one InControl pushbutton sensor. The following
conditions must be met:
—
The ventilation units must all be of the same type.
—
All the ventilation units that are connected to the same InControl pushbutton sensor should
be located in the same room.
—
If possible, the control cables should be arranged and connected in a star configuration
(see Fig. 8) from the ventilation units to the InControl pushbutton sensor.
—
The cable between the ventilation unit and InControl pushbutton sensor should be no more
than 15 m long.
—
Ventilation unit 1 (master) must
always be switched on. It gener-
ates the feedback for the LED on
the InControl pushbutton sensor.
Ventilation units 2 to 5 (slaves) only
respond to switching commands
from the InControl sensor.
NOTE
►
Connect “+” only to the first ventila-
tion unit (master).
►
Connect “GND” to all the ventila-
tion units ( slaves).
6.1
Connecting the InControl pushbutton sensor to M-WRG-S/Z-T ventilation units
Terminal blocks
InControl pushbutton sensor
Number
Ventilation unit M-WRG-S/Z-T
Pushbutton
LED
1 (master) 2 (slave)
3 (slave)
4 (slave)
5 (slave)
+
2
1
3
3
3
3
3
2
4
4
4
4
4
3
5
5
5
5
5
4
6
6
6
6
6
5
11
11
11
11
11
6
12
12
12
12
12
GND
1
1
1
1
1
1
7
2
8
3
9
4
10
5
15
6
16
Table 4: Connecting the InControl pushbutton sensor to M-WRG-S/Z-T ventilation units
Fig. 8: Connecting the ventilation units in a star configuration
Master
Slave
Slave
Slave
Slave