Operating instructions
M-WRG-S/Z-T(-F,-FC) / M-WRG-S/Z-T(-F,-FC)-FU ventilation unit
- 21 -
Meltem Wärmerückgewinnung GmbH & Co. KG
Am Hartholz 4 · D-82239 Alling
[email protected] · www.meltem.com
VENTILATION THE RIGHT WAY
V E N T I L AT I O N & H E AT R E C O V E R Y
8.4
Connect wireless remote control M-WRG-FUFB to ventilation unit (for
M-WRG-S/Z-T(-F, -FC)-FU only)
When the ventilation unit is started for the first time, a connection must be established between the
ventilation unit and the wireless remote control. The procedure is as follows:
►
Switch the ventilation unit off at the mains switch (see section 7.1 on page 17).
►
Switch the ventilation unit on again.
►
Press the top left button on the wireless remote control several times within 5 s. The LED
for the pressed button lights up on the wireless remote control.
The connection is established between the ventilation unit and wireless remote control.
NOTE
You can only connect one wireless remote control to the ventilation unit at a time. The ventilation
unit will be controlled by the most recently connected wireless remote control.
9 Operating the ventilation unit
9.1
Operation with the InControl pushbutton sensor
9.1.1 Select ventilation program
—
Press one of the six buttons on the InControl pushbutton sensor to select the required
ventilation program (see section 10 on page 23). The LED on the corresponding button
lights up.
—
When the button with the currently selected ventilation program is pressed again, the LED
goes out and the ventilation unit switches to the lowest ventilation level with an air flow of
15 m
3
/h.
—
If there are multiple ventilation units connected to an InControl pushbutton sensor, the
same ventilation program is activated for all the ventilation units.
—
If there are multiple ventilation units of the same type with humidity and/or CO
2
control con-
nected to an InControl pushbutton sensor, each ventilation unit regulates the air exchange
on the basis of its own measured values.
—
The ventilation unit starts the most recently selected ventilation program in the following
situations:
— after a power cut
— when the switched off ventilation unit is switched on again at the mains switch.
9.1.2 LED night mode
With the LED night mode, you can switch off the LED steady light for the activated ventilation pro-
gram so as not to disturb sleep, for example.
►
Hold down any button on the InControl pushbutton sensor for roughly 5 s to activate the
night mode.
►
When the night mode is active, hold down any button on the InControl pushbutton sensor
for roughly 3 s; the LED for the activated ventilation program will light up for roughly 2 s.
►
Hold down any button on the InControl pushbutton sensor for roughly 5 s to deactivate the
night mode once more.