Installation
Rev 1.0
Mellanox Technologies
36
2. Choose which side of the gateway you want even with the rack vertical support. Either the
side with the power supply units or the side with the QSFP connectors can be even with one
of the vertical rack supports.
Figure 22: Placement of Gateway in Rack
Consider the following when deciding where and how to mount the rails and rail slides:
The distance between the rack and the door can be as little as 1.57” (4 cm) on one side of the rack
and as much as 7”(18 cm) on the other side of the rack. Keep in mind that there can be as many
as36 cables connected to the gateway.
• Do you want the connector side recessed in the rack to allow for a larger cable bending
radius? It is possible to recess the connector side by 2” (5cm) by optional placement of
the gateway rails. See Figure 23,“Mounting Options”.
• Will the connector side be recessed past other equipment in the rack and will this be
problematic?
• The installation kit allows for a 2” (5cm) recess of the gateway past the vertical support.
• Make sure the gateway air flow is compatible with your installation selection.
19" (482.6mm)
Connector side
Power / Spine side
Doors
Doors
Gateway
This edge of the gateway
is even with the rack verti-
cal support
Cable with recom-
mended bending
radius
Insufficient room for
recommended bend-
ing radius