DB-2620Av1
Instructions Manual
4-2.Setting HOLD CURRENT SELECT switch
A high setting value may cause burn on the
skin due to overheating of the motor.
Do not select a high value beyond the
required.
DRIVE CURRENT is set up with the HOLD I.SEL switch.
The ratio of HOLD CURRENT to DRIVE CURRENT can be selected.
(1) Set the HOLD I.SEL switch No. to the ratio of HOLD CURRENT to DRIVE CURRENT required.
● Ratio of HOLD CURRENT
HOLD CURRENT
DRIVE CURRENT
(Factory setting)
● HOLD CURRENT changes relative to DRIVE CURRENT setting.
The ratio of HOLD CURRENT [100%] represents the same as the setting for
DRIVE CURRENT.
● The effective range of the HOLD I.SEL switch varies according to the setting
of the DRIVE I.SEL switch.
●HOLD電流の割合を高くすると、停止時のモータ発熱が高くなります。
The greater the ratio of HOLD CURRENT grows, the more heat the motor
generates when is on holding-state.
ON
ON
OFF
70
ON
ON
ON
-
ON
OFF
OFF
50
ON
OFF
ON
60
OFF
ON
OFF
30
OFF
ON
ON
40
OFF
OFF
OFF
10
OFF
OFF
ON
20
DRIVE I.SEL〔No.B~No.F〕
HOLD I.SEL switch
Ratio of HOLD
CURRENT (%)
H3
H2
H1
ON
ON
OFF
70
ON
ON
ON
100
ON
OFF
OFF
50
ON
OFF
ON
60
OFF
ON
OFF
30
OFF
ON
ON
40
OFF
OFF
OFF
10
OFF
OFF
ON
20
HOLD I.SEL switch
Ratio of HOLD
CURRENT (%)
H3
H2
H1
Ratio of HOLD CURRENT(%) =
×
100
DRIVE I.SEL〔No.0~No.A〕
注意
CAUTION
-13-