ADB-2F50B
Instructions Manual
4-3.Setting DRIVE CURRENT SELECT switch
Erroneous setting may cause burn on the
skin, injury or damage to the motor due to
overheating of the motor.
Ensure correct setting.
DRIVE CURRENT is set up with the DRIVE I.SEL switch.
The switch is factory-set to [No.6].
(1) Set the switch No. to the setting specified in the table "10-4. Applicable Motors."
● Relationship between the DRIVE I.SEL switch and DRIVE CURRENT.
(Factory setting)
Switch No.
A/phase
0
1
0.90
1.08
2
3
1.26
1.44
4
5
1.62
1.80
6
7
1.98
2.16
8
9
2.34
2.52
A
B
2.70
2.88
C
D
3.06
3.24
E
F
3.42
3.60
-16-