Technician Settings (Cont’)
P16 – Enable/Disable Occupancy sensor
“00” - Disable
“01” - Enable
Disable
occ. sensor
Enable
occ. sensor
P17 – PIR (occupancy sensor) delay time
before switching to unoccupied mode (ON delay)
Range: 0…900
minutes.
Default: 20
minutes.
PIR ON delay
(minutes)
P19 – PIR (Occupancy sensor) polarity
“00” - Normally open
“01” - Normally close
PIR
Normally open
PIR
Normally close
P18 – Door switch or key tag configuration
“00” - Switch On/Off by door switch or key tag
“01” - Changing the set point temperature
“02” - Switching fan speed to Low
Switch
On or Off
Change
set-points
Switch to
fan low
P25 – Economy set point for cooling
Range: 5…35°C
/
41…95°F.
Default: 30°C
/
86°F.
EC set point in cooling
(°F)
(°C)
- 36 -