Meggitt Fuelling Products
Maintenance Manual (MMF145)
Pressure Fuelling Nozzle
–
F145 Series
USE OR DISCLOSURE OF DATA ON THIS PAGE IS SUBJECT TO THE RESTRICTIONS ON THE TITLE PAGE OF THIS DOCUMENT
05 Jan 2015
Revision 6.4
12
F. Test fixture (P/N F65-0-1130) has a 1/4 inch NPT tap for a test plug. Fill nozzle with test fluid and
let air bleed thru the hole in test fixture (P/N F65-0-1130). Plug up test fixture (P/N F65-0-1130)
after all air has escaped from the nozzle.
G. Apply 180 psig of fluid pressure to the nozzle for 5 minute. Then reduce pressure to 0 psig.
H. Use knob (
IPL Figure 1,
36) on handle (38) to set the nozzle in the closed position.
I.
Disconnect nozzle from test fixture (P/N F65-0-1130).
J. Apply 180 psig of fluid pressure to the nozzle for 5 minute. Then reduce pressure to 0 psig.
K. There must not be any leakage from the exterior of the nozzle, or from the plugs (3).
L. Remove all test fixtures and test plugs from the nozzle.